2004-06-18 00:00:00DENIED:
 PLAN SHEETS M1.01 THROUGH M1.03:
 M1.01 GRILLE AT 2 HR WALL, FIRE DAMPER
 REQUIRED.
  
 M1.02, CW PIPE PENTRATING STAIRWELL.
 PENETRATION PROHIBITED PER 2001 FBC
 1006.1.3.1.
  
 M1.03, DUCT THROUG STAIRWELL,
 PENETRATION PROHIBITED PER 2001 FBC
 1006.1.3.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.