Plan Review Notes For Permit 03050107 |
Permit Number |
03050107 |
|
Review Stop |
M |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2004-06-18 00:00:00 | DENIED: | | PLAN SHEETS M1.01 THROUGH M1.03: | | M1.01 GRILLE AT 2 HR WALL, FIRE DAMPER | | REQUIRED. | | | | M1.02, CW PIPE PENTRATING STAIRWELL. | | PENETRATION PROHIBITED PER 2001 FBC | | 1006.1.3.1. | | | | M1.03, DUCT THROUG STAIRWELL, | | PENETRATION PROHIBITED PER 2001 FBC | | 1006.1.3.1. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|