Plan Review Notes
Plan Review Notes For Permit 03050107
Permit Number 03050107
Review Stop FIRE
Sequence Number 4
Notes
Date Text
2004-03-19 00:00:001) HANDRAIL MISSING FROM ONE SIDE OF
 STAIR ON THE EXTERIOR OF THE GENERATOR
 ROOM.
  
 2) HANDRAILS REQUIRED AT ARCH-6 AT
 SOUTH ELEVATION ON PAGE A.22.
  
 3) NOTE ON PAGE A-48 IS INCORRECT. ALL
 DOORS MUST COMPLY WITH NFPA 101, CHAPTER
 SEVEN.
  
 4) DOOR SWINGS IN CORRIDOR ADJACENT TO
 ASST. MGR OFFICE DO NOT APPEAR TO
 SWING IN THE PROPER DIRECTION.
  
 5) IT APPEARS THAT ADDITIONAL STRIPING
 WILL BE REQUIRED ON THE LOADING DOCK
 ADJACENT TO THE EXIT DOOR LOCATED ON
 THE WEST SIDE.
  
 6) THE PLACEMENT OF EXIT SIGNS SHALL
 NOT EXCEED 100 FEET.
  
 7) EXITING FROM THE MAIN ROOF SHALL BE
 OBVIOUS AND DIRECT.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910