Date |
Text |
2004-04-14 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 805 6716 |
| E-MAIL: [email protected] |
| |
| FBC = FLORIDA BUILDING CODE 2001 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| |
| NOTE: |
| CHAPTER 553.80(2)(B) FLORIDA STATUTES |
| STATES THAT A LOCAL GOVERNMENT SHALL |
| IMPOSE A FEE OF FOUR TIMES THE FEE FOR |
| PLAN REVIEW, IF PLANS ARE REJECTED THREE |
| OR MORE TIMES FOR REPEATED FAILURE TO |
| CORRECT A CODE VIOLATION. |
| |
| FOR CONSISTENCY, THE FOLLOWING COMMENTS |
| ARE NUMBERED AS PER THE BUILDING PLAN |
| REVIEW OF 11/21/03: |
| |
| 1) THE COMMENT RESPONSE, DATED 2/11/04, |
| IS NOTED. |
| THE NOTICE OF COMMENCEMENT SHALL BE |
| RECORDED AT PALM BEACH COUNTY COURTHOUSE |
| AND A COPY SUBMITTED TO THIS OFFICE |
| BEFORE A PERMIT CAN BE ISSUED.BLANK |
| FORMS ARE AVAILABLE FROM THIS OFFICE. |
| |
| 2) THE COMMENT RESPONSE, DATED 2/11/04, |
| IS NOTED. |
| IMPACT FEES. THE PLANS SHALL BE TAKEN |
| TO PALM BEACH COUNTY BUILDING DEPARTMENT |
| FOR IMPACT FEE ASSESSMENT. THEY SHALL BE |
| STAMPED AT THAT OFFICE AND A COPY OF THE |
| PAID RECEIPT SUBMITTED TO THE CITY OF |
| WEST PALM BEACH DEPT OF CONSTRUCTION |
| SERVICES BEFORE A PERMIT CAN BE ISSUED. |
| |
| 3) UNITY OF TITLE. THE COMMENT RESPONSE, |
| DATED 2/11/04, IS NOTED BUT THE COMMENT |
| HAS NOT BEEN PROPERLY ADDRESSED.PALM |
| BEACH COUNTY PROPERTY APPRAISERS OFFICE |
| (HTTP://WWW.CO.PALM-BEACH.FL.US/PAPA/) |
| SHOWS THE PROPOSED BUILDING STRUCTURE |
| TRANSGRESSES LEGAL BOUNDARY LINES |
| BETWEEN THREE LOTS (PCN: 74-43-43-21-01- |
| 033-0011, 74-43-43-21-01-033-0012 AND |
| 74-43-43-21-10-074-0010)WHICH FORM THE |
| 'THE SITE'.SUBMIT A COPY OF THE 'UNITY |
| OF TITLE' DOCUMENT SO THAT FBC TABLE 600 |
| BOUNDARY LINE REQUIREMENTS MAY BE DEEMED |
| NOT APPLICABLE. |
| |
| 4) DECLARATION OF CONDOMINIUM BEFORE |
| C.O. ISSUE.THE COMMENT RESPONSE, DATED |
| 2/11/04, IS NOTED. |
| |
| 6)FBC* 105.13.1SPECIAL INSPECTOR. |
| THIS COMMENT HAS NOT BEEN PROPERLY |
| ADDRESSED.THE SUBMITTED 'SPECIAL |
| INSPECTOR AGREEMENT' IS MISSING THE LAST |
| PAGE, WHICH IS TO BE SIGNED BY THE |
| CONTRACTOR AND ARCHITECT/ENGINEER.THE |
| AGREEMENT SHALL ALSO BE SIGNED BY THE |
| OWNER AND THE JOB INSPECTOR IN THE SPACE |
| ALLOCATED.ALL SIGNATURES ARE TO BE |
| NOTARIZED ORIGINALS.ALSO, ON SHEET S-0 |
| THE DRAWING LIST UNDER THE HEADING |
| 'THRESHOLD BUILDING INSPECTION PLAN |
| SHALL INCLUDE ALL RELEVANT ARCHITECTURAL |
| SHEETS SUCH AS A.68, A.69, A.70, A.71. |
| |
| 7) SEPARATE SWIMMING POOL PERMIT APPLIC. |
| THE COMMENT RESPONSE, DATED 2/11/04, IS |
| NOTED. |
| |
| 9) FBC 104.2.2ENERGY CODE COMPLIANCE |
| FORMS.THE COMMENT RESPONSE, DATED |
| 2/11/04, IS NOTED. SHEET 2 OF THE |
| SUBMITTED FORM SHALL HAVE THE ORIGINAL |
| SEAL AND WET SIGNATURE OF ENGINEER THAT |
| PREPARED IT (STEVEN FELLER P.E.).ALSO, |
| SHEET 1 SHALL INCLUDE THE PERMIT NUMBER |
| (03050107), ADDRESS (403 SAPODILLA AVE), |
| ZIP (33401).THREE COPIES ARE REQUIRED. |
| |
| 11) PRODUCT APPROVALS.THIS COMMENT HAS |
| NOT BEEN PROPERLY ADDRESSED.NO PRODUCT |
| APPROVALS HAVE BEEN SUBMITTED FOR THE |
| ROOFING PRODUCTS.THE SUBMITTED MIAMI |
| WALL SYSTEMS INC PRODUCT APPROVAL NOA'S |
| FOR THE SINGLE HUNG WINDOWS AND SLIDING |
| GLASS DOORS DO NOT INCLUDE THE DRAWING |
| SHEETS WHICH FORM PART OF THE APPROVAL. |
| THE SUBMITTED FLEMING DOOR PRODUCTS LTD |
| OUTSWING COMMERCIAL STEEL DOOR PRODUCT |
| APPROVAL NOA# 02-0523.06 INCLUDES |
| DRAWINGS WHICH DO NOT INCLUDE THE |
| REQUIRED MIAMI-DADE PRODUCT CONTROL |
| DIVISION APPROVAL STAMP.ALSO, SUBMIT |
| THREE COPIES OF COMPLETE PRODUCT |
| APPROVALS FOR ALL OF THE PROPOSED |
| WINDOW, STOREFRONT, EXTERIOR DOOR AND |
| ROOF PRODUCTS. |
| |
| 12) FBC* 104.2.1.2BUILDING DATA.THIS |
| COMMENT HAS NOT BEEN PROPERLY ADDRESSED. |
| SHEET A.01 SHOWS A NEW HEADING 'BUILDING |
| AREA' BUT NO BUILDING AREA INFO, EXCEPT |
| THE AREAS OF THE RESIDENTIAL UNIT TYPES, |
| HAS BEEN ADDED.ADD THE BUILDING AREA |
| INFO. |
| NOTE:THE STATED VALUATION FOR PERMIT |
| APPLICATION FEE CALCULATION HAS NOT YET |
| BEEN REVIEWED DUE TO THE LACK OF THIS |
| INFORMATION.ADDITIONAL FEES MAY BE |
| DUE (SEE FBC* 104.6.5). |
| |
| 13) FBC 1606.1.1WIND LOAD. THE COMMENT |
| RESPONSE, DATED 2/11/04, IS NOTED. |
| SUBMIT COPIES OF THE RWDI WIND TUNNEL |
| TEST REPORT REFERENCED ON SHEET S-0 |
| UNDER THE TITLE 'WIND LOADS'.ADD A |
| TITLE AND KEY TO SHEETS A.68, A.69, |
| A.70 AND A.71 TO CLARIFY WHETHER THAT |
| INFORMATION REPRESENTS COMPONENT AND |
| CLADDING WIND PRESSURES IN PSF. |
| |
| 18) FBC 412.6SHEETS A.02 AND A.03, |
| PARKING LEVEL PLANS. IF DOOR #7 IS BEING |
| PROVIDED IN FRONT OF EACH ELEVATOR, IN |
| LIEU OF ELEVATOR LOBBIES, HOW IS THE |
| REQUIREMENT FOR A SMOKE DETECTOR IN EACH |
| ELEVATOR LOBBY (REF: FBC 412.6.3) GOING |
| TO BE MET?AMEND THE PLANS (INCL. |
| SHEETS LS.1 AND LS.2) |
| |
| 34) FBC 411.2.3PARKING GARAGE LOADING. |
| THE 2/11/04 COMMENT RESPONSE AND REVISED |
| ARCHITECTURAL SHEET A.03 REFER TO THE |
| STRUCTURAL PLANS FOR PARKING GARAGE |
| IMPACT LOADING.NO REFERNCE TO THIS |
| LOADING COULD BE FOUND ON THE STRUCTURAL |
| PLANS.PLEASE CLARIFY. |
| |
| 41) FBC 1010.1SHEETS LS.2 AND A.04. |
| ROUTE TO EXIT DISCHARGE FROM STAIR #4. |
| SHEET LS.2 SHOWS TWO STAIRS WHILE |
| SHEET A.04 & A.15 SHOW ONE.ALSO, SHOW |
| DIMENSIONS FOR THE WIDTH OF THE STAIRS |
| AND ASSOCIATED GATE, AND PROVIDE TREAD/ |
| RISER DETAILS FOR THE STAIRS. |
| |
| 42) SHEET S-17, UPPER LEVEL ROOF PLAN. |
| AS THE RWDI WIND TUNNEL TEST REPORT HAS |
| NOT BEEN SUBMITTED (SEE COMMENT 13) THE |
| UPLIFTS ON THE ROOF TRUSSES CANNOT BE |
| VERIFIED AT THIS TIME. |
| |
| 45) 61G1-16.004FL. ADMIN. CODE.PLANS |
| PREPARED BY A REGISTERED ARCHITECT SHALL |
| INCLUDE THE PRINTED NAME OF THE |
| ARCHITECT SEALING THE PLANS.THE |
| PRINTED NAME AND LICENSE NUMBER ARE FOR |
| GUILLERMO J. ENCINOSA BUT THE PLANS ARE |
| SIGNED AND SEALED BY STUART COHEN.THE |
| PRINTED NAME AND LICENSE NUMBER OF THE |
| ARCHITECT MUST MATCH THE SIGNATURE AND |
| SEAL ON THE PLANS. |
| |
| 46) FBC 1003.3EGRESS CAPACITY.AMEND |
| THE LIFE SAFETY PLANS LS.1 TO LS.5 (LS.2 |
| IN PARTICULAR) TO SHOW THE CALCULATED |
| NUMBER OF OCCUPANT USING EACH EXIT. |
| |
| 47) FBC 1012.1EXTERIOR DOOR (#78) TO |
| SOUTH EAST PLAZA.THE WIDTH OF THE EXIT |
| ROUTE IS RESTRICTED.AMENT SHEETS A.04, |
| A.30 AND LS.2 TO SHOW THIS DOOR AS |
| OUTSWING WITH THE HINGES ON THE WEST |
| SIDE SUCH THAT THE WIDTH IS NO LONGER |
| RESTRICTED BY THE PLANTING. |
| |
| 48) FBC 11-4.13.4SHEET A.48, DOUBLE |
| LEAF DOORWAYS 21, 27 & 31 (MIS-LABELLED |
| ON SHEET A.04, A.11 & A.12 AS DOOR #22) |
| DO NOT HAVE AT LEAST ONE LEAF WITH A |
| CLEAR OPENING OF 32".AMEND THE PLANS. |
| |
| 49) FBC 11-4.3.2SHEET A.O4.THE |
| ACCESSIBLE RAMP TO THE PATH AROUND THE |
| LAWN AREA OF THE COURTYARD IS TOO REMOTE |
| FROM FITNESS, CONFERENCE ROOM AND CLUB |
| ROOM.AMEND THE PLAN. |
| |
| 50) SHEET A.29PRE-CAST CONCRETE |
| ARCHITECTURAL FEATURES/MOLDINGS. PROVIDE |
| ATTACHMENT DETAILS FOR THESE ITEMS. |
| |
| 51) FBC 11-413.8DOOR THRESHOLDS. SHEET |
| A.43 - DETAIL L AND SHEET A.44-DETAIL. |
| THE THRESHOLDS AT EXTERIOR SLIDING DOORS |
| SHALL NOT EXCEED 3/4" IN HEIGHT (SEE |
| ALSO FAIR HOUSING ACT DESIGN MANUAL |
| PAGE 4.14).AMEND THE PLANS. |
| |
| 52) FBC 412.5(3)SHEET M4.01,SMOKE |
| CONTROL NOTE C.THIS NOTE DOES NOT MAKE |
| SENSE.AMEND THE NOTE TO DEMONSTRATE |
| COMPLIANCE WITH FBC 412.5(3). |
| |
| 53) FBC 1005.6.9.9SHEET M4.01, STAIR |
| AND ELEVATOR PRESSURIZATION NOTES AND/OR |
| SHEET M3.01, CORRIDOR/STAIR RISER |
| DIAGRAMS SHALL STATE THE REQUIREMENT FOR |
| MIN. 2,500 CFM DISCHARGE THROUGH THE |
| RELIEF LOUVERS AND FOR A MAX. 0.35 WATER |
| COLUMN COMBINED PRESSURE IN THE STAIR- |
| WELLS. ANNOTATE THE PLANS TO DEMONSTRATE |
| COMPLIANCE. |
| |
| 54) TO EXPEDITE REVIEW OF A RESUBMITTAL |
| WHICH REQUIRES NEW PLANS IN ORDER TO |
| ADDRESS THE ABOVE COMMENTS, THE OLD |
| SHEETS SHALL BE REMOVED AND THE NEW |
| SHEETS INSERTED.ONE COPY OF EACH OLD |
| SHEET SHOULD BE STAPLED/CLIPPED TO THE |
| REMAINING OLD SHEETS FOR COMPARISON OF |
| REVISIONS WHEN REVIEWING THE RESUBMITTED |
| PLANS. |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |
| THE CODE REFERENCES GIVE ADDITIONAL INFO |
| TELEPHONE: (561) 805 6716ROBERT BROWN |
| E-MAIL: [email protected] |