Plan Review Notes
Plan Review Notes For Permit 03050107
Permit Number 03050107
Review Stop B
Sequence Number 4
Notes
Date Text
2004-04-14 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 NOTE:
 CHAPTER 553.80(2)(B) FLORIDA STATUTES
 STATES THAT A LOCAL GOVERNMENT SHALL
 IMPOSE A FEE OF FOUR TIMES THE FEE FOR
 PLAN REVIEW, IF PLANS ARE REJECTED THREE
 OR MORE TIMES FOR REPEATED FAILURE TO
 CORRECT A CODE VIOLATION.
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 11/21/03:
  
 1) THE COMMENT RESPONSE, DATED 2/11/04,
 IS NOTED.
 THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2) THE COMMENT RESPONSE, DATED 2/11/04,
 IS NOTED.
 IMPACT FEES. THE PLANS SHALL BE TAKEN
 TO PALM BEACH COUNTY BUILDING DEPARTMENT
 FOR IMPACT FEE ASSESSMENT. THEY SHALL BE
 STAMPED AT THAT OFFICE AND A COPY OF THE
 PAID RECEIPT SUBMITTED TO THE CITY OF
 WEST PALM BEACH DEPT OF CONSTRUCTION
 SERVICES BEFORE A PERMIT CAN BE ISSUED.
  
 3) UNITY OF TITLE. THE COMMENT RESPONSE,
 DATED 2/11/04, IS NOTED BUT THE COMMENT
 HAS NOT BEEN PROPERLY ADDRESSED.PALM
 BEACH COUNTY PROPERTY APPRAISERS OFFICE
 (HTTP://WWW.CO.PALM-BEACH.FL.US/PAPA/)
 SHOWS THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES
 BETWEEN THREE LOTS (PCN: 74-43-43-21-01-
 033-0011, 74-43-43-21-01-033-0012 AND
 74-43-43-21-10-074-0010)WHICH FORM THE
 'THE SITE'.SUBMIT A COPY OF THE 'UNITY
 OF TITLE' DOCUMENT SO THAT FBC TABLE 600
 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED
 NOT APPLICABLE.
  
 4) DECLARATION OF CONDOMINIUM BEFORE
 C.O. ISSUE.THE COMMENT RESPONSE, DATED
 2/11/04, IS NOTED.
  
 6)FBC* 105.13.1SPECIAL INSPECTOR.
 THIS COMMENT HAS NOT BEEN PROPERLY
 ADDRESSED.THE SUBMITTED 'SPECIAL
 INSPECTOR AGREEMENT' IS MISSING THE LAST
 PAGE, WHICH IS TO BE SIGNED BY THE
 CONTRACTOR AND ARCHITECT/ENGINEER.THE
 AGREEMENT SHALL ALSO BE SIGNED BY THE
 OWNER AND THE JOB INSPECTOR IN THE SPACE
 ALLOCATED.ALL SIGNATURES ARE TO BE
 NOTARIZED ORIGINALS.ALSO, ON SHEET S-0
 THE DRAWING LIST UNDER THE HEADING
 'THRESHOLD BUILDING INSPECTION PLAN
 SHALL INCLUDE ALL RELEVANT ARCHITECTURAL
 SHEETS SUCH AS A.68, A.69, A.70, A.71.
  
 7) SEPARATE SWIMMING POOL PERMIT APPLIC.
 THE COMMENT RESPONSE, DATED 2/11/04, IS
 NOTED.
  
 9) FBC 104.2.2ENERGY CODE COMPLIANCE
 FORMS.THE COMMENT RESPONSE, DATED
 2/11/04, IS NOTED. SHEET 2 OF THE
 SUBMITTED FORM SHALL HAVE THE ORIGINAL
 SEAL AND WET SIGNATURE OF ENGINEER THAT
 PREPARED IT (STEVEN FELLER P.E.).ALSO,
 SHEET 1 SHALL INCLUDE THE PERMIT NUMBER
 (03050107), ADDRESS (403 SAPODILLA AVE),
 ZIP (33401).THREE COPIES ARE REQUIRED.
  
 11) PRODUCT APPROVALS.THIS COMMENT HAS
 NOT BEEN PROPERLY ADDRESSED.NO PRODUCT
 APPROVALS HAVE BEEN SUBMITTED FOR THE
 ROOFING PRODUCTS.THE SUBMITTED MIAMI
 WALL SYSTEMS INC PRODUCT APPROVAL NOA'S
 FOR THE SINGLE HUNG WINDOWS AND SLIDING
 GLASS DOORS DO NOT INCLUDE THE DRAWING
 SHEETS WHICH FORM PART OF THE APPROVAL.
 THE SUBMITTED FLEMING DOOR PRODUCTS LTD
 OUTSWING COMMERCIAL STEEL DOOR PRODUCT
 APPROVAL NOA# 02-0523.06 INCLUDES
 DRAWINGS WHICH DO NOT INCLUDE THE
 REQUIRED MIAMI-DADE PRODUCT CONTROL
 DIVISION APPROVAL STAMP.ALSO, SUBMIT
 THREE COPIES OF COMPLETE PRODUCT
 APPROVALS FOR ALL OF THE PROPOSED
 WINDOW, STOREFRONT, EXTERIOR DOOR AND
 ROOF PRODUCTS.
  
 12) FBC* 104.2.1.2BUILDING DATA.THIS
 COMMENT HAS NOT BEEN PROPERLY ADDRESSED.
 SHEET A.01 SHOWS A NEW HEADING 'BUILDING
 AREA' BUT NO BUILDING AREA INFO, EXCEPT
 THE AREAS OF THE RESIDENTIAL UNIT TYPES,
 HAS BEEN ADDED.ADD THE BUILDING AREA
 INFO.
 NOTE:THE STATED VALUATION FOR PERMIT
 APPLICATION FEE CALCULATION HAS NOT YET
 BEEN REVIEWED DUE TO THE LACK OF THIS
 INFORMATION.ADDITIONAL FEES MAY BE
 DUE (SEE FBC* 104.6.5).
  
 13) FBC 1606.1.1WIND LOAD. THE COMMENT
 RESPONSE, DATED 2/11/04, IS NOTED.
 SUBMIT COPIES OF THE RWDI WIND TUNNEL
 TEST REPORT REFERENCED ON SHEET S-0
 UNDER THE TITLE 'WIND LOADS'.ADD A
 TITLE AND KEY TO SHEETS A.68, A.69,
 A.70 AND A.71 TO CLARIFY WHETHER THAT
 INFORMATION REPRESENTS COMPONENT AND
 CLADDING WIND PRESSURES IN PSF.
  
 18) FBC 412.6SHEETS A.02 AND A.03,
 PARKING LEVEL PLANS. IF DOOR #7 IS BEING
 PROVIDED IN FRONT OF EACH ELEVATOR, IN
 LIEU OF ELEVATOR LOBBIES, HOW IS THE
 REQUIREMENT FOR A SMOKE DETECTOR IN EACH
 ELEVATOR LOBBY (REF: FBC 412.6.3) GOING
 TO BE MET?AMEND THE PLANS (INCL.
 SHEETS LS.1 AND LS.2)
  
 34) FBC 411.2.3PARKING GARAGE LOADING.
 THE 2/11/04 COMMENT RESPONSE AND REVISED
 ARCHITECTURAL SHEET A.03 REFER TO THE
 STRUCTURAL PLANS FOR PARKING GARAGE
 IMPACT LOADING.NO REFERNCE TO THIS
 LOADING COULD BE FOUND ON THE STRUCTURAL
 PLANS.PLEASE CLARIFY.
  
 41) FBC 1010.1SHEETS LS.2 AND A.04.
 ROUTE TO EXIT DISCHARGE FROM STAIR #4.
 SHEET LS.2 SHOWS TWO STAIRS WHILE
 SHEET A.04 & A.15 SHOW ONE.ALSO, SHOW
 DIMENSIONS FOR THE WIDTH OF THE STAIRS
 AND ASSOCIATED GATE, AND PROVIDE TREAD/
 RISER DETAILS FOR THE STAIRS.
  
 42) SHEET S-17, UPPER LEVEL ROOF PLAN.
 AS THE RWDI WIND TUNNEL TEST REPORT HAS
 NOT BEEN SUBMITTED (SEE COMMENT 13) THE
 UPLIFTS ON THE ROOF TRUSSES CANNOT BE
 VERIFIED AT THIS TIME.
  
 45) 61G1-16.004FL. ADMIN. CODE.PLANS
 PREPARED BY A REGISTERED ARCHITECT SHALL
 INCLUDE THE PRINTED NAME OF THE
 ARCHITECT SEALING THE PLANS.THE
 PRINTED NAME AND LICENSE NUMBER ARE FOR
 GUILLERMO J. ENCINOSA BUT THE PLANS ARE
 SIGNED AND SEALED BY STUART COHEN.THE
 PRINTED NAME AND LICENSE NUMBER OF THE
 ARCHITECT MUST MATCH THE SIGNATURE AND
 SEAL ON THE PLANS.
  
 46) FBC 1003.3EGRESS CAPACITY.AMEND
 THE LIFE SAFETY PLANS LS.1 TO LS.5 (LS.2
 IN PARTICULAR) TO SHOW THE CALCULATED
 NUMBER OF OCCUPANT USING EACH EXIT.
  
 47) FBC 1012.1EXTERIOR DOOR (#78) TO
 SOUTH EAST PLAZA.THE WIDTH OF THE EXIT
 ROUTE IS RESTRICTED.AMENT SHEETS A.04,
 A.30 AND LS.2 TO SHOW THIS DOOR AS
 OUTSWING WITH THE HINGES ON THE WEST
 SIDE SUCH THAT THE WIDTH IS NO LONGER
 RESTRICTED BY THE PLANTING.
  
 48) FBC 11-4.13.4SHEET A.48, DOUBLE
 LEAF DOORWAYS 21, 27 & 31 (MIS-LABELLED
 ON SHEET A.04, A.11 & A.12 AS DOOR #22)
 DO NOT HAVE AT LEAST ONE LEAF WITH A
 CLEAR OPENING OF 32".AMEND THE PLANS.
  
 49) FBC 11-4.3.2SHEET A.O4.THE
 ACCESSIBLE RAMP TO THE PATH AROUND THE
 LAWN AREA OF THE COURTYARD IS TOO REMOTE
 FROM FITNESS, CONFERENCE ROOM AND CLUB
 ROOM.AMEND THE PLAN.
  
 50) SHEET A.29PRE-CAST CONCRETE
 ARCHITECTURAL FEATURES/MOLDINGS. PROVIDE
 ATTACHMENT DETAILS FOR THESE ITEMS.
  
 51) FBC 11-413.8DOOR THRESHOLDS. SHEET
 A.43 - DETAIL L AND SHEET A.44-DETAIL.
 THE THRESHOLDS AT EXTERIOR SLIDING DOORS
 SHALL NOT EXCEED 3/4" IN HEIGHT (SEE
 ALSO FAIR HOUSING ACT DESIGN MANUAL
 PAGE 4.14).AMEND THE PLANS.
  
 52) FBC 412.5(3)SHEET M4.01,SMOKE
 CONTROL NOTE C.THIS NOTE DOES NOT MAKE
 SENSE.AMEND THE NOTE TO DEMONSTRATE
 COMPLIANCE WITH FBC 412.5(3).
  
 53) FBC 1005.6.9.9SHEET M4.01, STAIR
 AND ELEVATOR PRESSURIZATION NOTES AND/OR
 SHEET M3.01, CORRIDOR/STAIR RISER
 DIAGRAMS SHALL STATE THE REQUIREMENT FOR
 MIN. 2,500 CFM DISCHARGE THROUGH THE
 RELIEF LOUVERS AND FOR A MAX. 0.35 WATER
 COLUMN COMBINED PRESSURE IN THE STAIR-
 WELLS. ANNOTATE THE PLANS TO DEMONSTRATE
 COMPLIANCE.
  
 54) TO EXPEDITE REVIEW OF A RESUBMITTAL
 WHICH REQUIRES NEW PLANS IN ORDER TO
 ADDRESS THE ABOVE COMMENTS, THE OLD
 SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHOULD BE STAPLED/CLIPPED TO THE
 REMAINING OLD SHEETS FOR COMPARISON OF
 REVISIONS WHEN REVIEWING THE RESUBMITTED
 PLANS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]