Plan Review Notes
Plan Review Notes For Permit 03050107
Permit Number 03050107
Review Stop P
Sequence Number 3
Notes
Date Text
2004-02-10 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FHA-AMEND. 98 DESIGN MANUAL
  
 A) COMMENTS FROM THE FIRST AND SECOND
 REVIEW HAVE NOT BEEN ADDRESSED AND NO
 COMMENT RESPONSE NOTED. COMMENT NUMBERS
 FROM FIRST AND SECOND REVEIW WILL REMAIN
 THE SAME FOR CLAIRTY.
 2) PLEASE SUBMIT CALCULATIONS FOR MINI-
 MUM FIXTURE FACILITIES PER TABLE 403.1
 FOR THE BUSINESS/COMMON AREAS GROUND
 FLOOR LEVEL. INCLUDE MGR, ASST. MGR,
 CONFERENCE ROOMS, HEALTH CLUB, FIRE CON-
 TROL, SEC. DESK, VALET, MAIL ROOM, MAIN
 LOBBY, CARD ROOM, FITNESS CENTER, BAR,
 PANTRY, ECT. (NO RESPONSE NOTED)
 3) SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS. SHOW 1/2 AREA OF
 ALL VERTICAL WALLS INCLUDING PARAPETS &
 AREA OF ROOFS THAT DRAIN FROM ABOVE. IN-
 DICATE HOW THE INTERNAL ROOF AREAS,
 (WITHOUT SCUPPERS), ADD TO SCUPPER SIZE
 OF ADJACENT AREAS. SECTIONS 1106 & 1107
 AND ALL SUBSECTIONS. (NO RESPONSE NOTED)
 6) SHEETS A.51 THRU A.61 LAV. ELEVATIONS
 MAXIMUM 34" TO TOP. FHA DESIGN MANUAL
 PAGE 7.52. (NO RESPONSE NOTED - STILL AT
 36" TO TOP).
 8) SHTS A.51 THRU A.66 UNIT PLAN NOTES
 #7, SUBMIT CALCULATIONS FOR 20GA BACKING
 SHOW COMPLIANCE WITH SECTIONS 11-4.26.3,
 11-4.26.3(1), 11-4.26.3(2), 11-4.26.3(3)
 AND 11-4.26.34). (NO RESPONSE NOTED)
 9) SHEETS A.51 THRU A.66 SHOW OPENING
 SIZE FOR ALL WATER CLOSETS. MINIMUM 33".
 (18" OFF WALL WHERE LOCATED NEXT TO ONE,
 AND MINIMUM OF 18" OFF FIXTURE) - THE
 FOLLOWING UNITS DO NOT SHOW SIZE OPENING
 SHT A.52 UNIT A2, SHT A.53 UNIT A5 W/C
 TO BE 1'6" OFF WALL NOT 1'7", SHT A.56
 UNIT B1B, SHT A.57 UNIT B1E, SHT A.59
 UNIT B1E, SHT A.61 UNIT B3, SHT A.62
 UNIT B5, AND SHT A.63 UNIT C1.
 10) SHT P1.01 SHOW PIPE SIZES AND CLEAN-
 OUT LOCTIONS. TABLE 710.1(1) & SECTIONS
 708.3, 708.3.1, AND 708.3.5. (NO RESPON-
 SE NOTED. THE PIPE SIZE CAN BE LOCATED
 ON THE SANT. RISER DIAGRAM, BUT THE C/O
 LOCATIONS SHALL BE SHOWN PER CODE).
 *************FROM 2ND REVIEW************
 3B) SHT A.11 BAR SINK SHALL COMPLY WITH
 11.4.24 AND ALL SUBSECTIONS. PROVIDE A
 DETAIL. (RESPONSE STATES SHOWN ON SHEET
 A.68, BUT NO SHEET A.68 SUBMITTED).
 5B) SHEETS A.51 THRU A.66 SHOW CLEAR
 FLOOR SPACE FOR ALL ACCESSIBLE FIXTURES
 PER FHA DESIGN MANUAL PAGE 7.43. (RES-
 PONSE NOTED BUT ON SHT A.51 THE CLEAR
 FLOOR SPACE FOR THE LAV AND W/C ARE NOT
 ON PLANS. AND FOR SHTS A.52 THRU A.66
 THE CLEAR FLOOR SPACE FOR THE WATER
 CLOSETS ARE NOT ON PLANS).
 37B) 4 TIMES THE FEE FOR PLAN REVIEW
 SHALL NOW BE CHARGED PER FLORIDA STATUTE
 533.80(2)(B) - $133,200.00 IS DUE.
 ******NEW COMMENTS******
 1C) SHT A.55 UNITS B1 & B1.1 INDICATES
 TYPE 'B' BUT BATH #2 IS A TYPE 'A' LAY-
 OUT. PLEASE CLAIRFY.
 2C) SHTS A.56, A.57, A.58, A.59, A.60,
 A.61, A.62, AND A.63 ALL THESE UNITS
 SHOW TYPE 'B', BUT IN EACH SPACE BOTH
 BATHROOMS SHOW CLEAR FLOOR SPACE. WHICH
 BATHROOM WILL BE ADAPTABLE? PLEASE
 CLAIRFY.
 3C) SHTS A.51 THRU A.66 ALL UNITS THAT
 HAVE PARALLEL APPROACH TO LAVS, THE LAVS
 SHALL BE CENTERED ON THE 48" DIMENSION.
 4C) ORIGINAL PERMIT APPLICATION SHALL BE
 SUBMITTED TO ISSUE PERMIT.
  
 REVIEW BY KEN STEVENS