Date |
Text |
2004-04-10 00:00:00 | DENIED: |
| REFERENCE RESPONSE #12: |
| 1.PLAN SHEET M6.03 VERTICAL HEAT PUMP |
| DETAIL, PER 2001 FBC(M) 307.2.4, THE |
| CODE IS VERY SPECIFIC DRAIN PANS ARE TO |
| BE BE INSTALLED WHERE POSSIBLE, THE |
| ALTERNATIVE IS A DRAIN PAN SECURED ALONG |
| SIDE THE UNIT WITH A DRAIN LINE OR A |
| LEVEL DETECTOR.THE LEVEL DETECTOR IS |
| NOT TO BE INSTALLED IN THE PRIMARY DRAIN |
| PAN AS INDICATED. |
| |
| REFERENCE RESPONSE #13: |
| 1.PLANS INDICATE CO SENSORS PLANS DO |
| NOT INDICATE AT WHAT LEVEL (PPM) THE |
| SENSORS ARE SET.PER 2001 FBC 411.4.2 |
| & 412.5 THE MECHANICAL SYSTEM IS TO |
| PROVIDE A MINIMUM OF 6 AIR CHANGES PER |
| HOUR & BE CONTINUOUSLY VENTILATED WITH |
| SUPPLY AND EXHAUST. |
| |
| 2.PLEASE NOTE, RE-LOCATION OF EXHAUST |
| FANS FOR GARAGE VENTILATION.WILL THIS |
| BE EFFECTIVE FOR REMOVAL OF CARBON |
| MONOXIDE?PLEASE PROVIDE INFORMATION |
| AS TO HOW THE CO SENSORS WILL BE |
| TESTED. |
| |
| 3.PLANS INDICATE OUTSIDE AIR FOR THE |
| CONDO UNITS BY INFILTRATION.PER 2001 |
| FBC(M) 403.3, VENTILATION SYSTEMS FOR |
| OTHER THAN ONE & TWO FAMILY DWELLING |
| SHALL BE DESIGNED TO SUPPLY THE MINIMUM |
| OF OUSTIDE AIR PER TABLE 403.3. |
| PER 2001 FBC(M) 403.2.1 #1 VENTILATION |
| AIR SHALL NOT BE RECIRCULATED FROM ONE |
| OCCUPANCY TYPE TO ANOTHER. |
| |
| REFERENCE RESPONSE #11: |
| 1.PLAN SHEET M4.01 NOTE C, PLEASE |
| CLARIFY, WHEN BUILDING GOES INTO ALARM, |
| EXHAUST FIRE/SMOKE DAMPERS ON ALL FLOORS |
| FOR THE CORRIDORS WILL OPEN & THE SUPPLY |
| FIRE/SMOKE DAMPERS WILL CLOSE ON THE |
| FLOOR OF INCIDENCE IS THIS CORRECT? |
| |
| 2.FLOOR PLAN INDICATES OA 1 & 2 FOR |
| OUTSIDE AIR TO CORRIDORS THE SCHEDULE |
| INDICATES RTU'S.PLEASE CORRELATE |
| RISERS WITH THE SCHEDULE. |
| |
| 3.PLAN SHEET M1.03 THROUGH M1.09 |
| INDICATES "CEA" FOR THE CORRIDOR EXHAUST |
| & EXHAUST SCHEDULE (M5.02) INDICATES |
| "SEF". PLEASE CORRELATE RISERS WITH |
| THE SCHEDULE. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE |
| CONTACT PATTY KRAUSS AT (561) 805-6719. |