2004-04-10 00:00:00DENIED:
 REFERENCE RESPONSE #12:
 1.PLAN SHEET M6.03 VERTICAL HEAT PUMP
 DETAIL, PER 2001 FBC(M) 307.2.4, THE
 CODE IS VERY SPECIFIC DRAIN PANS ARE TO
 BE BE INSTALLED WHERE POSSIBLE, THE
 ALTERNATIVE IS A DRAIN PAN SECURED ALONG
 SIDE THE UNIT WITH A DRAIN LINE OR A
 LEVEL DETECTOR.THE LEVEL DETECTOR IS
 NOT TO BE INSTALLED IN THE PRIMARY DRAIN
 PAN AS INDICATED.
  
 REFERENCE RESPONSE #13:
 1.PLANS INDICATE CO SENSORS PLANS DO
 NOT INDICATE AT WHAT LEVEL (PPM) THE
 SENSORS ARE SET.PER 2001 FBC 411.4.2
 & 412.5 THE MECHANICAL SYSTEM IS TO
 PROVIDE A MINIMUM OF 6 AIR CHANGES PER
 HOUR & BE CONTINUOUSLY VENTILATED WITH
 SUPPLY AND EXHAUST.
  
 2.PLEASE NOTE, RE-LOCATION OF EXHAUST
 FANS FOR GARAGE VENTILATION.WILL THIS
 BE EFFECTIVE FOR REMOVAL OF CARBON
 MONOXIDE?PLEASE PROVIDE INFORMATION
 AS TO HOW THE CO SENSORS WILL BE
 TESTED.
  
 3.PLANS INDICATE OUTSIDE AIR FOR THE
 CONDO UNITS BY INFILTRATION.PER 2001
 FBC(M) 403.3, VENTILATION SYSTEMS FOR
 OTHER THAN ONE & TWO FAMILY DWELLING
 SHALL BE DESIGNED TO SUPPLY THE MINIMUM
 OF OUSTIDE AIR PER TABLE 403.3.
 PER 2001 FBC(M) 403.2.1 #1 VENTILATION
 AIR SHALL NOT BE RECIRCULATED FROM ONE
 OCCUPANCY TYPE TO ANOTHER.
  
 REFERENCE RESPONSE #11:
 1.PLAN SHEET M4.01 NOTE C, PLEASE
 CLARIFY, WHEN BUILDING GOES INTO ALARM,
 EXHAUST FIRE/SMOKE DAMPERS ON ALL FLOORS
 FOR THE CORRIDORS WILL OPEN & THE SUPPLY
 FIRE/SMOKE DAMPERS WILL CLOSE ON THE
 FLOOR OF INCIDENCE IS THIS CORRECT?
  
 2.FLOOR PLAN INDICATES OA 1 & 2 FOR
 OUTSIDE AIR TO CORRIDORS THE SCHEDULE
 INDICATES RTU'S.PLEASE CORRELATE
 RISERS WITH THE SCHEDULE.
  
 3.PLAN SHEET M1.03 THROUGH M1.09
 INDICATES "CEA" FOR THE CORRIDOR EXHAUST
 & EXHAUST SCHEDULE (M5.02) INDICATES
 "SEF". PLEASE CORRELATE RISERS WITH
 THE SCHEDULE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.