Plan Review Notes
Plan Review Notes For Permit 03050107
Permit Number 03050107
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2004-02-10 00:00:001) PLEASE EXPLAIN HOW STAIRS ON THE
 LOADING DOCK CAN ACCOMODATE THE
 OCCUPANT LOAD FROM STAIR # 1. ALSO
 HOW WILL EXIT DISCHARGE BE MAINTAINED
 FROM THE EXIT DOOR OF STAIR # 1 THROUGH
 THE LOADING DOCK.
  
 2) PLEASE EXPLAIN COMMENT PERMIT
 RESPONSE # 9. PLEASE CLARIFY.
  
 3) FIRE ALARM NOTE ON PAGE FA1.03 IS
 INCORRECT. THE FIRE ALARM SYSTEM
 SHALL BE LISTED FOR CENTRAL STATION
 SERVICE. PLEASE REVISE.
  
 4) ITEMS # 15 AND # 16 SHALL BE
 INDICATED ON THE PLANS. PLEASE REVISE.
  
 5) NOTE # 18 PERMIT COMMENT RESPONSE
 NEEDS FURTHER CLARIFICATION. ANY
 ELECTRONIC LOCKS ON EXIT DOORS SHALL
 COMPLY WITH ACCESS CONTROL OR
 DELAYED EGRESS. PLEASE REVIEW
 APPLICABLE CODE SECTIONS AND ANNOTE
 PLANS.
  
 6) HANDRAILS SHALL BE PROVIDED ON ALL
 NEW STAIRS. ALSO HANDRAILS ARE REQUIRED
 WITHIN 30" OF ALL REQUIRED WIDTHS USED
 FOR EXITING.
  
 7) EXIT SIGN MISSING AT EXTERIOR DOOR
 OF STAIR # 3.
  
 8) ONLY ONE FIRE HYDRANT SHOWN ON C-5.
 PLEASE CLARIFY.
  
 9) NOTE # 29, NO PERMIT RESPONSE
 PROVIDED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910