2004-02-10 00:00:00 | 1) PLEASE EXPLAIN HOW STAIRS ON THE |
| LOADING DOCK CAN ACCOMODATE THE |
| OCCUPANT LOAD FROM STAIR # 1. ALSO |
| HOW WILL EXIT DISCHARGE BE MAINTAINED |
| FROM THE EXIT DOOR OF STAIR # 1 THROUGH |
| THE LOADING DOCK. |
| |
| 2) PLEASE EXPLAIN COMMENT PERMIT |
| RESPONSE # 9. PLEASE CLARIFY. |
| |
| 3) FIRE ALARM NOTE ON PAGE FA1.03 IS |
| INCORRECT. THE FIRE ALARM SYSTEM |
| SHALL BE LISTED FOR CENTRAL STATION |
| SERVICE. PLEASE REVISE. |
| |
| 4) ITEMS # 15 AND # 16 SHALL BE |
| INDICATED ON THE PLANS. PLEASE REVISE. |
| |
| 5) NOTE # 18 PERMIT COMMENT RESPONSE |
| NEEDS FURTHER CLARIFICATION. ANY |
| ELECTRONIC LOCKS ON EXIT DOORS SHALL |
| COMPLY WITH ACCESS CONTROL OR |
| DELAYED EGRESS. PLEASE REVIEW |
| APPLICABLE CODE SECTIONS AND ANNOTE |
| PLANS. |
| |
| 6) HANDRAILS SHALL BE PROVIDED ON ALL |
| NEW STAIRS. ALSO HANDRAILS ARE REQUIRED |
| WITHIN 30" OF ALL REQUIRED WIDTHS USED |
| FOR EXITING. |
| |
| 7) EXIT SIGN MISSING AT EXTERIOR DOOR |
| OF STAIR # 3. |
| |
| 8) ONLY ONE FIRE HYDRANT SHOWN ON C-5. |
| PLEASE CLARIFY. |
| |
| 9) NOTE # 29, NO PERMIT RESPONSE |
| PROVIDED. |
| |
| MIKE CARSILLO, ASSISTANT FIRE MARSHAL |