2003-11-18 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 FUEL GAS |
| FBC-2001 CHAPTER 1 |
| FBC-2001 CHAPTER 11 |
| FHA-98 DESIGN MANUAL |
| FLORIDA STATUTES |
| FLORIDA ADMINISTRATIVE CODE |
| CITY WPB CODE |
| |
| A) MANY COMMENTS FROM THE FIRST REVIEW |
| WERE NOT ADDRESSED AND NO COMMENT RES- |
| PONSE NOTED. COMMENT NUMBERS FROM FIRST |
| REVIEW WILL BE SHOWN FOR CLAIRITY. |
| 1) SHTS A.11 & A.12, ALL PUBLIC & COMMON |
| USE TOILET ROOMS SHALL COMPLY WITH SEC. |
| 11-4.22 AND ALL SUBSECTIONS. (CLEAR |
| FLOOR SPACE, HEIGHTS, GRAB BARS, ECT.). |
| 2) PLEASE SUBMIT CALCULATIONS FOR MINI- |
| MUM FIXTURE FACILITIES PER TABLE 403.1 |
| FOR THE BUSINESS/COMMON AREAS GROUND |
| FLOOR LEVEL, INCLUDE MGR, ASST. MGR, |
| CONFERENCE ROOMS, HEALTH CLUB, FIRE |
| CONTROL, SEC. DESK, VALET, MAIL ROOM, |
| MAIN LOBBY, CARD ROOM, FITNESS CENTER, |
| BAR, PANTRY, ECT. |
| 3) SUBMIT CALCULATIONS FOR PRIMARY AND |
| SECONDARY ROOF DRAINS. SHOW 1/2 AREA OF |
| ALL VERTICAL WALLS INCLUDING PARAPETS |
| AND AREA OF ROOFS THAT DRAIN FROM ABOVE |
| ON TO ROOF ADDED TO SQUARE FOOTAGE OF |
| ROOF. SHOW HOW EACH AREA WILL BE AFFECT- |
| ED BY VERTICAL WALLS AND ROOF DRAINING |
| FROM ABOVE, INDICATE HOW THE INTERNAL |
| ROOF AEAS, (WITHOUT SCUPPERS), ADD TO |
| SCUPPER SIZE OF ADJACENT AREAS. SECTIONS |
| 1106 & 1107 AND ALL SUBSECTIONS. |
| 4) SHT A.09, INDICATE LOCATION OF SECON- |
| DARY DRAINS FOR THE DECK AREA AROUND THE |
| POOL, AND DECK AREAS BELOW THE POOL DECK |
| AREA. |
| 6) SHTS A.51 THRU A.66, LAV ELEVATIONS |
| MAXIMUM 34" TO TOP. FHA DESIGN MANUAL |
| PAGE 7.52. |
| 7) SHTS A.51 THRU A.66, SPECIFICATION |
| "A" OR "B" SHALL BE NOTED ON PLANS FOR |
| BATHROOMS PER FHA DESIGN MANUAL PAGE |
| 7.35. |
| 8) SHTS A.51 THRU A.66, UNIT PLAN NOTES: |
| #7, SUBMIT CALCULATIONS FOR 20GA METAL |
| BACKING. SHOW COMPLIANCE WITH SECTIONS |
| AA-4.26.3, 11-4.26.3(1), 11-4.26.3(2), |
| 11-4.26.3(3), & 11-4.26.3(4). |
| 9) SHTS A.51 THRU A.66 SHOW OPENING SIZE |
| FOR ALL WATER CLOSETS. MINIMUM SIZE 33". |
| (18" OFF WALL WHERE LOCATED NEXT TO ONE, |
| AND MINIMUM OF 18" OFF FIXTURE). |
| 10) SHT P1.01 SHOW PIPE SIZES AND CLEAN- |
| OUT LOCATIONS. TABLE 710.1(1) & SECTIONS |
| 708.3, 708.3.1, 708.3.3, 708.3.5. |
| 23) SEPARATE GAS PERMIT REQUIRED. THE |
| FOLLOWING INFORMATION IS REQUIRED FOR A |
| PERMIT. |
| A. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2001 |
| FUEL GAS CODE. - NOT ALL SECTIONS INDIC- |
| ATE THE LENGTHS. |
| B. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED. |
| C. TYPE OF GAS, (LP OR NATURAL) |
| E. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES (A)(3). - RECHECK |
| DISTANCE. |
| F. SUBMIT CALCULATIONS FOR COMBUSTION |
| AIR (IF APPLICABLE) PER FBC-2001 FUEL |
| GAS CODE SECTION 304. |
| G. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2001 FUEL GAS CODE SEC 402.2 |
| J. CLEARLY SHOW THE LOCATION AND CAP- |
| ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| OR ASME), THE DISTANCE OF THE TANK FROM |
| THE BUILDING AND ADJACENT PROPERTY LINES |
| THE DISTANCE OF THE TANK FROM ALL SOUR- |
| CES OF IGNITION, OTHER CONTAINERS, BUILD |
| INGS, AND THE LOCATION OF ANY BUILDING |
| OPENINGS BELOW THE RELIEF VALVE OF THE |
| TANK PER NFPA 58, TABLE 3-2.2.2. |
| K. CLEARLY INDICATE ON THE PLAN IF THE |
| LP TANK IS ABOVE OR BELOW GROUND, AND |
| SHOW REQUIRED PROTECTION OF THE TANK AND |
| APPURTENANCES PER NFPA 58. IF THE TANK |
| IS BELOW GROUND THE CONTAINER SHALL BE |
| SECURILY ANCHORED PER NFPA 58 SECTION |
| 3-2.2.7(H). |
| *********WHEN RESUBMITTING PLANS******** |
| PLEASE CLEARLY INDICATE THE REVISION AND |
| REMOVE AND REPLACE ANY PAGES AS NECESS- |
| ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| THE PLANS WHEN RESUBMITTING PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN |
| BE FOUND, WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| **************************************** |
| NEW COMMENTS |
| 1B) SHT A.12 WALLS IN MEN'S & WOMEN'S |
| TOILET ROOMS APPEAR TO BE IN TURNING |
| CIRCLE AND IN HDCP STALLS. PLEASE REMOVE |
| 2B) SUBMIT A DETAIL FOR ACCESSIBLE |
| TOILET ROOMS PER 11-4.16, 11-4.19, AND |
| 11-4.22 AND ALL SUBSECTIONS. |
| 3B) SHT A.11 BAR SINK SHALL COMPLY WITH |
| 11-4.24 AND ALL SUBSECTIONS. PROVIDE A |
| DETAIL. |
| 4B) SHT A.45 OVERFLOW SCUPPER DETAIL. |
| SCUPPER SHALL BE PLACED IN WALLS OR |
| PARAPETS WITH THE INLET FLOW LINE NOT |
| LESS THAN 2 INCHES ABOVE THE ROOF SUR- |
| FACE, EXCLUDING SUMPS, OR MORE THAN 4 |
| INCHES ABOVE THE ROOF SURFACE AND SHALL |
| BE LOCATED AS CLOSE AS PRACTICAL TO REQ- |
| UIRED VERTICAL LEADERS. |
| 5B) SHTS A.51 THRU A.66 SHOW CLEAR FLOOR |
| SPACE FOR ALL ACCESSIBLE FIXTURES PER |
| FHA DESIGN MANUAL PAGE 7.43 |
| 6B) SHTS A.51 THRU A.66 UNIT PLAN NOTES: |
| #6 STATE 1996 FHA - UPDATE TO READ AMEND |
| ED 1998 FHA. |
| 7B) SHT P1.01 KEY NOTES: #8 & STORM |
| DRAIN, 3" FIRE STAND PIPE DRAIN NOT APP- |
| ROVED TO STORM. DRAIN SHALL CONNECT TO |
| SANITARY VIA INDIRECT WASTE. CITY CODE |
| SECTION 90-233(A). |
| 8B) SHTS P1.01 & P1.02 MORE INFORMATION |
| REQUIRED FOR PAD RISER. SEE #'S 14 & 37 |
| KEY NOTES. |
| 9B) SHT P1.02 FLOOR DRAINS FOR FIRE AND |
| DOMESTIC PUMP ROOMS SHALL CONNECT TO |
| SANITARY, NOT STORM. CITY CODE 90-233(A) |
| 10B) 61G15-23.002(1) SIGNATURE REQUIRED |
| ON SEAL. PER FBPE INITALS ARE NOT TO BE |
| ACCEPTED. THE SIGNATURE THAT WAS SIGNED |
| ON THE ENGINEERS LICENSE SHALL BE RE- |
| QUIRED ON EACH SHEET. |
| 11B) SHT P1.04 RISER DIAGRAM DOES NOT |
| REFLECT THE FLOOR PLAN FOR UNIT 1. |
| SECTION 104.2.1 |
| 12B) SUBMIT RISER DIAGRAMS FOR RELIEF |
| VALVE DISCHARGE LINE (P&T) FOR W/HEATERS |
| THE DISCHARGE LINE FOR RELIEF VALVE |
| SHALL NOT HAVE ANY TRAPPED SECTIONS AND |
| SHALL HAVE A VISIBLE AIR GAP OR AIR GAP |
| FITTING IN THE SAME ROOM AS THE WATER |
| HEATER. SEC 504.7.1 |
| 13B) SHT P3.01 12" @ 3085 DFU'S AND 12" |
| @ 3419 DFU'S NOT APPROVED PER TABLE |
| 710.1(1). |
| 14B) SHT P3.03 RISER S/19, 3" REQUIRED |
| TO SHOWER. TABLE 909.3 |
| 15B) BACKFLOW PROTECTION REQUIRED FOR |
| TRASH CHUTE RING. SECTION 608.13 SUBMIT |
| DETAIL. |
| 16B) SHT P3.05 KEY NOTES: #22, CLAIRFY |
| 15TH FLOOR. #17 NOT FOUND. (2) # 19'S |
| 17B) SHT P3.05 SUBMIT CALCULATIONS FOR |
| WATER PRESSURE AT BOTTOM OF DROPS FOR |
| UNITS TO DETERMINE OF A PRESSURE REGULA- |
| TOR IS REQUIRED. |
| 18B) SHT P3.06 FILTER FOR ICE MACHINE |
| SHALL COMPLY WITH NSF STANDARD FOR WATER |
| FILTERS. SUBMIT MANUFACTURE SPECIFICAT- |
| ION SHEETS. SECTION 303.4 |
| 19B) SHT P3.06 WATER HAMMER ARRESTORS |
| REQUIRED AND ICE MACHINE AND DISHWASHER. |
| SECTION 604.9 |
| 20B) SHT P3.09 STORM DRAIN COLLECTION |
| ISOMETRIC, DOWNSTREAM OF RWL'S 24 & 25 |
| SHOWS 6"(5280 SF). MINIMUM 8" PIPE REQD. |
| 21B) SHT P3.09 STORM DRAIN COLLECTION |
| ISO., DOWNSTREAM OF (A) SHOWS 6" (2840 |
| SF) THEN SHOWS 4" PLEASE REVISE. 704.2. |
| 22B) SHT P3.09 STORM DRAIN COLLECTION |
| ISO., PLANTER DRAINS SHOW 40SF PLUS 200 |
| SF, BUT ONLY ADDS UP TO 80SF. AND AFTER |
| 6" DD (3300SF) PLUS (240SF) SHOWS (3380 |
| SF) BUT SHOULD READ (3540SF) PLEASE RE- |
| VISE. - INDICATE SF FOR FORCE MAIN FROM |
| BELOW. - ALSO DOWNSTREAM OF PD (1040SF) |
| SHOWS (900 SF) REVISE. |
| 23B) PROVIDE INFORMATION FOR FSP DRAIN. |
| WHAT TYPE OF DRAIN IS THIS AND WHAT DOES |
| IT DRAIN? |
| 24B) SHT P3.10 PROVIDE MANUF. SPECC. |
| SHEETS ON STORM DRAIN LIFT STATION. |
| 25B) SHT P3.10 FIRE STAND PIPE DRAIN |
| SHALL NOT DRAIN TO STORM. CONNECT TO |
| SANITARY SYSTTEM. |
| 26B) SHT P3.11 PROVIDE CUT PIECE MEAS- |
| URMENTS FROM METER TO FIRST GAS RISER & |
| MEASURMENTS FOR ALL CUT PIECES IN BOILER |
| ROOM. |
| 27B) SHT P3.11 GAS ISOMETRIC, INDICATE |
| WHY GAS LINE TO POOL EQUIPMENT ROOM IS |
| SLEEVED. PIPING SHALL NOT BE INSTALLED |
| IN SOLID FLOOR SLABS. SECTION 404.6 |
| 28B) SHT P3.11 NFPA-54 HAS NOT BEEN |
| ADOPTED. SIZE PIPE PER FBC-2001 FUEL GAS |
| DELETE REFERENCE. |
| 29B) SHT P3.12 CONDENSATE COLLECTION ISO |
| MINIMUM 2" PIPE UNDERGROUND. SECTION |
| 710.3 |
| 30B) SHT P3.12 COND. COLLECTION ISO., A |
| RELIEF VENT IS REQUIRED AS CONDENSATE |
| EXITS THE BLDG. |
| 31B) SHTS P1.03, THRUP1.09, & P2.01 |
| UNIT "A", RISER S/70 RISER NOT FOUND AND |
| RISER S/18 DOES NOT REFLECT THE FLOOR |
| PLAN. SHT P3.04 |
| 32B) SHT P3.03 RISER S/19 TABLE 909.3 |
| 3" REQUIRED TO SHOWER. |
| 33B) SHTS P1.03 THRU P1.09 & P2.01 UNIT |
| "A" MOD, RISER S/71 NOT FOUND AND RISER |
| S/53 DOES NOT REFLECT THE FLOOR PLAN. |
| SHT P3.04. |
| 34B) SHT P3.04 RISER S/59 DOES NOT RE- |
| FLECT THE FLOOR PLAN. |
| 35B) SHT P3.04 RISER S/62 DOES NOT RE- |
| FLECT THE FLOOR PLAN. |
| 36B) SUBMIT MANUF. SPEC. SHEET FOR SIM- |
| PLEX AND TRIPLES PUMP SYSTEMS. |
| 37B) SEE ATTACHED SHEET CONCERNING |
| FS 533.80(2)(B) DESIGN PROFESSIONAL DOC- |
| UMENTS. |
| *********WHEN RESUBMITTING PLANS******** |
| PLEASE CLEARLY INDICATE THE REVISION AND |
| REMOVE AND REPLACE ANY PAGES AS NECESS- |
| ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| THE PLANS WHEN RESUBMITTING PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN |
| BE FOUND, WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |