Plan Review Notes
Plan Review Notes For Permit 03050107
Permit Number 03050107
Review Stop P
Sequence Number 2
Notes
Date Text
2003-11-18 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
 FLORIDA STATUTES
 FLORIDA ADMINISTRATIVE CODE
 CITY WPB CODE
  
 A) MANY COMMENTS FROM THE FIRST REVIEW
 WERE NOT ADDRESSED AND NO COMMENT RES-
 PONSE NOTED. COMMENT NUMBERS FROM FIRST
 REVIEW WILL BE SHOWN FOR CLAIRITY.
 1) SHTS A.11 & A.12, ALL PUBLIC & COMMON
 USE TOILET ROOMS SHALL COMPLY WITH SEC.
 11-4.22 AND ALL SUBSECTIONS. (CLEAR
 FLOOR SPACE, HEIGHTS, GRAB BARS, ECT.).
 2) PLEASE SUBMIT CALCULATIONS FOR MINI-
 MUM FIXTURE FACILITIES PER TABLE 403.1
 FOR THE BUSINESS/COMMON AREAS GROUND
 FLOOR LEVEL, INCLUDE MGR, ASST. MGR,
 CONFERENCE ROOMS, HEALTH CLUB, FIRE
 CONTROL, SEC. DESK, VALET, MAIL ROOM,
 MAIN LOBBY, CARD ROOM, FITNESS CENTER,
 BAR, PANTRY, ECT.
 3) SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS. SHOW 1/2 AREA OF
 ALL VERTICAL WALLS INCLUDING PARAPETS
 AND AREA OF ROOFS THAT DRAIN FROM ABOVE
 ON TO ROOF ADDED TO SQUARE FOOTAGE OF
 ROOF. SHOW HOW EACH AREA WILL BE AFFECT-
 ED BY VERTICAL WALLS AND ROOF DRAINING
 FROM ABOVE, INDICATE HOW THE INTERNAL
 ROOF AEAS, (WITHOUT SCUPPERS), ADD TO
 SCUPPER SIZE OF ADJACENT AREAS. SECTIONS
 1106 & 1107 AND ALL SUBSECTIONS.
 4) SHT A.09, INDICATE LOCATION OF SECON-
 DARY DRAINS FOR THE DECK AREA AROUND THE
 POOL, AND DECK AREAS BELOW THE POOL DECK
 AREA.
 6) SHTS A.51 THRU A.66, LAV ELEVATIONS
 MAXIMUM 34" TO TOP. FHA DESIGN MANUAL
 PAGE 7.52.
 7) SHTS A.51 THRU A.66, SPECIFICATION
 "A" OR "B" SHALL BE NOTED ON PLANS FOR
 BATHROOMS PER FHA DESIGN MANUAL PAGE
 7.35.
 8) SHTS A.51 THRU A.66, UNIT PLAN NOTES:
 #7, SUBMIT CALCULATIONS FOR 20GA METAL
 BACKING. SHOW COMPLIANCE WITH SECTIONS
 AA-4.26.3, 11-4.26.3(1), 11-4.26.3(2),
 11-4.26.3(3), & 11-4.26.3(4).
 9) SHTS A.51 THRU A.66 SHOW OPENING SIZE
 FOR ALL WATER CLOSETS. MINIMUM SIZE 33".
 (18" OFF WALL WHERE LOCATED NEXT TO ONE,
 AND MINIMUM OF 18" OFF FIXTURE).
 10) SHT P1.01 SHOW PIPE SIZES AND CLEAN-
 OUT LOCATIONS. TABLE 710.1(1) & SECTIONS
 708.3, 708.3.1, 708.3.3, 708.3.5.
 23) SEPARATE GAS PERMIT REQUIRED. THE
 FOLLOWING INFORMATION IS REQUIRED FOR A
 PERMIT.
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE. - NOT ALL SECTIONS INDIC-
 ATE THE LENGTHS.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 C. TYPE OF GAS, (LP OR NATURAL)
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3). - RECHECK
 DISTANCE.
 F. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304.
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 J. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 K. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 *********WHEN RESUBMITTING PLANS********
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 ****************************************
 NEW COMMENTS
 1B) SHT A.12 WALLS IN MEN'S & WOMEN'S
 TOILET ROOMS APPEAR TO BE IN TURNING
 CIRCLE AND IN HDCP STALLS. PLEASE REMOVE
 2B) SUBMIT A DETAIL FOR ACCESSIBLE
 TOILET ROOMS PER 11-4.16, 11-4.19, AND
 11-4.22 AND ALL SUBSECTIONS.
 3B) SHT A.11 BAR SINK SHALL COMPLY WITH
 11-4.24 AND ALL SUBSECTIONS. PROVIDE A
 DETAIL.
 4B) SHT A.45 OVERFLOW SCUPPER DETAIL.
 SCUPPER SHALL BE PLACED IN WALLS OR
 PARAPETS WITH THE INLET FLOW LINE NOT
 LESS THAN 2 INCHES ABOVE THE ROOF SUR-
 FACE, EXCLUDING SUMPS, OR MORE THAN 4
 INCHES ABOVE THE ROOF SURFACE AND SHALL
 BE LOCATED AS CLOSE AS PRACTICAL TO REQ-
 UIRED VERTICAL LEADERS.
 5B) SHTS A.51 THRU A.66 SHOW CLEAR FLOOR
 SPACE FOR ALL ACCESSIBLE FIXTURES PER
 FHA DESIGN MANUAL PAGE 7.43
 6B) SHTS A.51 THRU A.66 UNIT PLAN NOTES:
 #6 STATE 1996 FHA - UPDATE TO READ AMEND
 ED 1998 FHA.
 7B) SHT P1.01 KEY NOTES: #8 & STORM
 DRAIN, 3" FIRE STAND PIPE DRAIN NOT APP-
 ROVED TO STORM. DRAIN SHALL CONNECT TO
 SANITARY VIA INDIRECT WASTE. CITY CODE
 SECTION 90-233(A).
 8B) SHTS P1.01 & P1.02 MORE INFORMATION
 REQUIRED FOR PAD RISER. SEE #'S 14 & 37
 KEY NOTES.
 9B) SHT P1.02 FLOOR DRAINS FOR FIRE AND
 DOMESTIC PUMP ROOMS SHALL CONNECT TO
 SANITARY, NOT STORM. CITY CODE 90-233(A)
 10B) 61G15-23.002(1) SIGNATURE REQUIRED
 ON SEAL. PER FBPE INITALS ARE NOT TO BE
 ACCEPTED. THE SIGNATURE THAT WAS SIGNED
 ON THE ENGINEERS LICENSE SHALL BE RE-
 QUIRED ON EACH SHEET.
 11B) SHT P1.04 RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN FOR UNIT 1.
 SECTION 104.2.1
 12B) SUBMIT RISER DIAGRAMS FOR RELIEF
 VALVE DISCHARGE LINE (P&T) FOR W/HEATERS
 THE DISCHARGE LINE FOR RELIEF VALVE
 SHALL NOT HAVE ANY TRAPPED SECTIONS AND
 SHALL HAVE A VISIBLE AIR GAP OR AIR GAP
 FITTING IN THE SAME ROOM AS THE WATER
 HEATER. SEC 504.7.1
 13B) SHT P3.01 12" @ 3085 DFU'S AND 12"
 @ 3419 DFU'S NOT APPROVED PER TABLE
 710.1(1).
 14B) SHT P3.03 RISER S/19, 3" REQUIRED
 TO SHOWER. TABLE 909.3
 15B) BACKFLOW PROTECTION REQUIRED FOR
 TRASH CHUTE RING. SECTION 608.13 SUBMIT
 DETAIL.
 16B) SHT P3.05 KEY NOTES: #22, CLAIRFY
 15TH FLOOR. #17 NOT FOUND. (2) # 19'S
 17B) SHT P3.05 SUBMIT CALCULATIONS FOR
 WATER PRESSURE AT BOTTOM OF DROPS FOR
 UNITS TO DETERMINE OF A PRESSURE REGULA-
 TOR IS REQUIRED.
 18B) SHT P3.06 FILTER FOR ICE MACHINE
 SHALL COMPLY WITH NSF STANDARD FOR WATER
 FILTERS. SUBMIT MANUFACTURE SPECIFICAT-
 ION SHEETS. SECTION 303.4
 19B) SHT P3.06 WATER HAMMER ARRESTORS
 REQUIRED AND ICE MACHINE AND DISHWASHER.
 SECTION 604.9
 20B) SHT P3.09 STORM DRAIN COLLECTION
 ISOMETRIC, DOWNSTREAM OF RWL'S 24 & 25
 SHOWS 6"(5280 SF). MINIMUM 8" PIPE REQD.
 21B) SHT P3.09 STORM DRAIN COLLECTION
 ISO., DOWNSTREAM OF (A) SHOWS 6" (2840
 SF) THEN SHOWS 4" PLEASE REVISE. 704.2.
 22B) SHT P3.09 STORM DRAIN COLLECTION
 ISO., PLANTER DRAINS SHOW 40SF PLUS 200
 SF, BUT ONLY ADDS UP TO 80SF. AND AFTER
 6" DD (3300SF) PLUS (240SF) SHOWS (3380
 SF) BUT SHOULD READ (3540SF) PLEASE RE-
 VISE. - INDICATE SF FOR FORCE MAIN FROM
 BELOW. - ALSO DOWNSTREAM OF PD (1040SF)
 SHOWS (900 SF) REVISE.
 23B) PROVIDE INFORMATION FOR FSP DRAIN.
 WHAT TYPE OF DRAIN IS THIS AND WHAT DOES
 IT DRAIN?
 24B) SHT P3.10 PROVIDE MANUF. SPECC.
 SHEETS ON STORM DRAIN LIFT STATION.
 25B) SHT P3.10 FIRE STAND PIPE DRAIN
 SHALL NOT DRAIN TO STORM. CONNECT TO
 SANITARY SYSTTEM.
 26B) SHT P3.11 PROVIDE CUT PIECE MEAS-
 URMENTS FROM METER TO FIRST GAS RISER &
 MEASURMENTS FOR ALL CUT PIECES IN BOILER
 ROOM.
 27B) SHT P3.11 GAS ISOMETRIC, INDICATE
 WHY GAS LINE TO POOL EQUIPMENT ROOM IS
 SLEEVED. PIPING SHALL NOT BE INSTALLED
 IN SOLID FLOOR SLABS. SECTION 404.6
 28B) SHT P3.11 NFPA-54 HAS NOT BEEN
 ADOPTED. SIZE PIPE PER FBC-2001 FUEL GAS
 DELETE REFERENCE.
 29B) SHT P3.12 CONDENSATE COLLECTION ISO
 MINIMUM 2" PIPE UNDERGROUND. SECTION
 710.3
 30B) SHT P3.12 COND. COLLECTION ISO., A
 RELIEF VENT IS REQUIRED AS CONDENSATE
 EXITS THE BLDG.
 31B) SHTS P1.03, THRUP1.09, & P2.01
 UNIT "A", RISER S/70 RISER NOT FOUND AND
 RISER S/18 DOES NOT REFLECT THE FLOOR
 PLAN. SHT P3.04
 32B) SHT P3.03 RISER S/19 TABLE 909.3
 3" REQUIRED TO SHOWER.
 33B) SHTS P1.03 THRU P1.09 & P2.01 UNIT
 "A" MOD, RISER S/71 NOT FOUND AND RISER
 S/53 DOES NOT REFLECT THE FLOOR PLAN.
 SHT P3.04.
 34B) SHT P3.04 RISER S/59 DOES NOT RE-
 FLECT THE FLOOR PLAN.
 35B) SHT P3.04 RISER S/62 DOES NOT RE-
 FLECT THE FLOOR PLAN.
 36B) SUBMIT MANUF. SPEC. SHEET FOR SIM-
 PLEX AND TRIPLES PUMP SYSTEMS.
 37B) SEE ATTACHED SHEET CONCERNING
 FS 533.80(2)(B) DESIGN PROFESSIONAL DOC-
 UMENTS.
 *********WHEN RESUBMITTING PLANS********
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026