Notes
Date Text
2003-11-19 00:00:00DENIED:
 PLEASE PROVIDE TRANSMITTAL LETTER WITH
 RESPONSES TO COMMENTS TO HELP EXPEDITE
 PLANS IN A MORE TIMELY MANNER.
  
 1.PLAN SHEET A.45B DETAIL G, DRYER
 VENT TO BE NON-SCREENED WITH A BACKDRAFT
 DAMPER AND SHALL NOT PASS THRU PLENUMS
 PER 2001 FBC(M) 504.4.
  
 2.PLAN SHEET M1.03 CLARIFY MAKE-UP AIR
 NEXT TO STAIRWELL PRESSURE RELIEF
 (EXHAUST).
  
 3.M1.03-INDICATES FLAMEBAR DUCT IN
 STAIRWELL. PER 2001 FBC 1006.1.3.1, NO
 DUCT PENETRATIONS THROUGH A STAIRWELL
 EXCEPT FOR STAIRWELL PRESSURIZATION.
 PLEASE PROVIDE SUBMITTAL FOR THE
 FLAMEBAR DUCT.
  
 4.M1.03-PROVIDE MANUFACTURER SUBMITTAL
 DATA ON THE GENERATOR WILL THERE BE A
 FILL TANK OR STORAGE?
  
 5.SUPPLY DUCT FROM HP-G-1 APPEARS TO
 PENETRATE A RATED WALL AT THE ELEVATOR
 LOBBY AREA.FIRE DAMPERS ARE NOT
 REQUIRED AS LONG AS ALL THE CONDITIONS
 OF 607.1.3.
  
 6.FLOORS 2 THRU 8 SUPPLY DUCT FROM
 HP-C-1 REQUIRE A FIRE DAMPER AT THE
 PENETRATION THRU THE WALL TO THE
 CORRIDOR.
  
 7.M1.03 THRU M1.09 INDICATE DOORS WITH
 UNDERCUTS AND LOUVERS ARE THESE FIRE
 RATED CORRIDORS?PLEASE CLARIFY.
  
 8.M1.03 FIRE/SMOKE DAMPERS MISSING
 FROM HP-G-5 WHERE DUCT PASSES THRU RATED
 WALLS.PLEASE CLARIFY.
  
 9.M2.01 & OTHERS INDICATE EXHAUST ON
 TERMINATING ONTO THE TERRANCE PLEASE
 NOTE PER 2001 FBC(M) 401.5.2, EXHAUST
 OPENINGS SHALL BE LOCATED SO AS NOT
 CREATE A NUISANCE. EXHAUST AIR SHALL NOT
 DIRECTED ONTO WALKWAYS.
  
 10. M2.01 NOTE ON PLAN INDICATES SPECFIC
 DRYERS TO BE INSTALLED FOR INCREASED
 VENTING CAPABILITY.PLEASE PROVIDE
 MANUFACTURER SPECS FOR DRYER.DRYERS
 TO BE INSTALLED FOR FINAL INSPECTION.
  
 11. M.401 SMOKE CONTROL - PRESSURIZATION
 OF CORRIDOR PLEASE CLARIFY HOW THIS
 COMPLYS WITH 2001 FBC 412.5.WHERE WILL
 THE SMOKE ON THE FLOOR OF INCIDENT BE
 MIDIGATED TO?
  
 12. AUXILIARY DRAIN PANS REQUIRED PER
 2001 FBC(M) 307.2.3.
  
 13. PROVIDE OUTSIDE AIR CALCULATIONS FOR
 ALL AREAS COMMON AND RESIDENTIAL PER
 2001 FBC(M) 403.3.
  
 14. PROVIDE CALCULATIONS FOR COMBUSTION
 AIR IN THE BOILER ROOM.PROVIDE MIMINUM
 AIR REQUIREMENTS FOR ALL THE MECHANICAL
 ROOMS.INDICATE CALCULATIONS ON PLAN.
  
 15. PLEASE NOTE EXHAUST CONTAINING
 NOXIOUS FUMES, DUST PARTICALS OR SMOKE
 SHALL BE LOCATED A MINIMUM OF 10 FT
 FROM ANY FRESH AIR INTAKE (INCLUDING
 DOORS AND WINDOWS).
  
 16. PLEASE INDICATE IF ANY OF THE
 APPLIANCES ARE GAS.
  
 17. PLEASE NOTE AS PER FS 471.025 AND
 FAC 61G15-23.003, ALL PLANS SHALL BE
 SIGNED (NOT INITIALED), SEALED AND DATED
 BY THE ENGINEER OF RECORD.PLEASE
 REVISE PLANS TO COMPLY.
  