2003-10-30 00:00:00 | 1) STAIR # 4 DOOR ON PAGE A.02 SWINGS |
| IN THE WRONG DIRECTION. DOOR SWINGS |
| OUT, SHOULD SWING IN. B-2 LEVEL. |
| |
| 2) SAME CONDITION, SAME LOCATION OCCURS |
| ON PAGE A.03. B-1 LEVEL. |
| |
| 3) PLEASE EXPLAIN EXITING RATIONALE |
| FROM THE BUILDING. PLEASE INDICATE |
| WHICH STAIRS LEAD DIRECTLY TO THE |
| EXTERIOR AT GROUND LEVEL. |
| |
| 4) COURTYARD AREA DISPLAYS STAIRS ABSENT |
| OF HANDRAILS. |
| |
| 5) PLEASE EXPLAIN HOW EXITING OCCURS |
| NEAR THE BIKE STORAGE AREA. IT APPEARS |
| THRU THE LOADING DOCK. PLEASE EXPLAIN |
| RATIONALE. |
| |
| 6) STAIR # 1 APPEARS TO DISCHARGE ONTO |
| THE LOADING DOCK. PLEASE EXPLAIN. |
| |
| 7) KNOX-BOX NOT REQUIRED IN FIRE |
| COMMAND ROOM. KNOX-BOXES ARE REQUIRED |
| TO GAIN ACCESS FROM THE EXTERIOR OF |
| THE BUILDING. THEY ARE NOTED ON THE |
| DRAWINGS. |
| |
| 8) ALL PREVIOUSLY PLAN REVIEW COMMENTS |
| NOTED ON JUNE 6, 2003 HAVE NOT BEEN |
| ADEQUATELY ADDRESSED. |
| |
| 9) PLEASE EXPLAIN "SMOKE DETECTOR NOTE |
| ON FA1.10 CONNECT DELUGE SYSTEM TO |
| FIRE ALARM PANEL AS REQUIRED". |
| |
| 10) FIRE ALARM EQUIPMENT NOTED IN |
| STAIR # 2. PLEASE REVIEW CODE SECTIONS |
| FOR ITEMS ALLOWED IN STAIRWELL. |
| |
| 11) ALL FIRE ALARM SYSTEMS THAT |
| SUPERVISE AUTOMATIC FIRE SPRINKLER |
| SYSTEMS AS OF AUGUST 1, 2003, MUST BE |
| UL LISTED FOR CENTRAL STATION SERVICE. |
| |
| 12) FPS.02 DISPLAYS THREE FIRE |
| DEPARTMENT CONNECTIONS. ONLY TWO ARE |
| NEEDED. |
| |
| 13) NOTE # 29 ON FP3.01 IS INCORRECT. |
| STANDPIPES ERECTED DURING CONSTRUCTION |
| ARE REQUIRED WHEN CONSTRUCTION REACHES |
| 30 FEET NOT 50 FEET. |
| |
| 14) ALL SPRINKLERS SHALL BE QUICK |
| RESPONSE TYPE. |
| |
| 15) TACTILE SIGNAGE REQUIRED AT ALL |
| STAIRWELLS. |
| |
| 16) HOW IS THE 4" PIPING FOR THE |
| STANDPIPE SYSTEM THAT RUNS BELOW |
| THE POOL DECK GOING TO BE INSPECTED |
| OR MAINTAINED IN THE FUTURE. |
| |
| 17) SMOKE CONTROL NOTES SHALL MENTION |
| ANTICIPATED STACK EFFECT. |
| |
| 18) PLEASE EXPLAIN MAGNETIC LOCKS TIED |
| TO FIRE ALARM SYSTEM. LOCKING |
| DEVICES ON EXIT DOORS TO COMPLY WITH |
| ACCESS CONTROLLED EGRESS WITH ALL |
| CODE PARAMETERS BEING MET. |
| |
| 19) NO REVISIONS COULD BE LOCATED |
| ON THE DRAWINGS. |
| |
| 20) PLEASE PROVIDE PRODUCT APPROVALS |
| FOR INSULATION PLANNED FOR AROUND |
| TRASH CHUTE. |
| |
| 21) PLEASE PROVIDE STRENGTH REQUIREMENTS |
| FOR HANDRAILS. |
| |
| 22) ALL CONCRETE STAIRS ON RECREATION |
| DECK SHALL BE EQUIPPED WITH HANDRAILS |
| ON BOTH SIDES. |
| |
| 23) HANDRAILS ARE REQUIRED FOR STAIRS |
| ON UPPER PLAZA. |
| |
| 24) PROVIDE CONSTRUCTION DATA. |
| |
| 25) BUILDING ADDRESS REQUIRED. |
| |
| MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| 835-2910 |