Plan Review Notes
Plan Review Notes For Permit 03050107
Permit Number 03050107
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2003-10-30 00:00:001) STAIR # 4 DOOR ON PAGE A.02 SWINGS
 IN THE WRONG DIRECTION. DOOR SWINGS
 OUT, SHOULD SWING IN. B-2 LEVEL.
  
 2) SAME CONDITION, SAME LOCATION OCCURS
 ON PAGE A.03. B-1 LEVEL.
  
 3) PLEASE EXPLAIN EXITING RATIONALE
 FROM THE BUILDING. PLEASE INDICATE
 WHICH STAIRS LEAD DIRECTLY TO THE
 EXTERIOR AT GROUND LEVEL.
  
 4) COURTYARD AREA DISPLAYS STAIRS ABSENT
 OF HANDRAILS.
  
 5) PLEASE EXPLAIN HOW EXITING OCCURS
 NEAR THE BIKE STORAGE AREA. IT APPEARS
 THRU THE LOADING DOCK. PLEASE EXPLAIN
 RATIONALE.
  
 6) STAIR # 1 APPEARS TO DISCHARGE ONTO
 THE LOADING DOCK. PLEASE EXPLAIN.
  
 7) KNOX-BOX NOT REQUIRED IN FIRE
 COMMAND ROOM. KNOX-BOXES ARE REQUIRED
 TO GAIN ACCESS FROM THE EXTERIOR OF
 THE BUILDING. THEY ARE NOTED ON THE
 DRAWINGS.
  
 8) ALL PREVIOUSLY PLAN REVIEW COMMENTS
 NOTED ON JUNE 6, 2003 HAVE NOT BEEN
 ADEQUATELY ADDRESSED.
  
 9) PLEASE EXPLAIN "SMOKE DETECTOR NOTE
 ON FA1.10 CONNECT DELUGE SYSTEM TO
 FIRE ALARM PANEL AS REQUIRED".
  
 10) FIRE ALARM EQUIPMENT NOTED IN
 STAIR # 2. PLEASE REVIEW CODE SECTIONS
 FOR ITEMS ALLOWED IN STAIRWELL.
  
 11) ALL FIRE ALARM SYSTEMS THAT
 SUPERVISE AUTOMATIC FIRE SPRINKLER
 SYSTEMS AS OF AUGUST 1, 2003, MUST BE
 UL LISTED FOR CENTRAL STATION SERVICE.
  
 12) FPS.02 DISPLAYS THREE FIRE
 DEPARTMENT CONNECTIONS. ONLY TWO ARE
 NEEDED.
  
 13) NOTE # 29 ON FP3.01 IS INCORRECT.
 STANDPIPES ERECTED DURING CONSTRUCTION
 ARE REQUIRED WHEN CONSTRUCTION REACHES
 30 FEET NOT 50 FEET.
  
 14) ALL SPRINKLERS SHALL BE QUICK
 RESPONSE TYPE.
  
 15) TACTILE SIGNAGE REQUIRED AT ALL
 STAIRWELLS.
  
 16) HOW IS THE 4" PIPING FOR THE
 STANDPIPE SYSTEM THAT RUNS BELOW
 THE POOL DECK GOING TO BE INSPECTED
 OR MAINTAINED IN THE FUTURE.
  
 17) SMOKE CONTROL NOTES SHALL MENTION
 ANTICIPATED STACK EFFECT.
  
 18) PLEASE EXPLAIN MAGNETIC LOCKS TIED
 TO FIRE ALARM SYSTEM. LOCKING
 DEVICES ON EXIT DOORS TO COMPLY WITH
 ACCESS CONTROLLED EGRESS WITH ALL
 CODE PARAMETERS BEING MET.
  
 19) NO REVISIONS COULD BE LOCATED
 ON THE DRAWINGS.
  
 20) PLEASE PROVIDE PRODUCT APPROVALS
 FOR INSULATION PLANNED FOR AROUND
 TRASH CHUTE.
  
 21) PLEASE PROVIDE STRENGTH REQUIREMENTS
 FOR HANDRAILS.
  
 22) ALL CONCRETE STAIRS ON RECREATION
 DECK SHALL BE EQUIPPED WITH HANDRAILS
 ON BOTH SIDES.
  
 23) HANDRAILS ARE REQUIRED FOR STAIRS
 ON UPPER PLAZA.
  
 24) PROVIDE CONSTRUCTION DATA.
  
 25) BUILDING ADDRESS REQUIRED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910