Plan Review Notes
Plan Review Notes For Permit 03050107
Permit Number 03050107
Review Stop ENG
Sequence Number 2
Notes
Date Text
2003-11-06 00:00:00FAILED:
 1. PLEASE NOTE THAT A SEPARATE PERMIT
 APPLICATION AND FEES FOR "UNDERGRPOUND
 UTILITIES AND SITE WORK" PERMIT IS
 REQUIRED, SUBMIT TWO SETS OF CIVIL PLANS
 ONLY SIGNED & SEALED, APPROVED & STAMPED
 BY THE PUBLIC UTILITIES AND ENGINEERING.
 2. PLEASE STATE THAT IF DRANAGE SYSTEM
 FOR THE ENTIRE SITE IS APPROVED BY
 STEVE SARLEY, DRANAGE ENGINEER.HOWEVER
 PERVIOUS AND IMPERVIOUS AREA CALC.
 AND TOTAL SITE AREA MUST BE SUBMITTED AT
 THE TIME OF ACTUAL PERMITTING.
 3. SHEET C-5 DOES NOT SHOW THE EXISTING
 INLETS AT CORNERS OF S. SAPODILLA AND
 GARDENIA, ARE THEY REMOVED,RELOCATED ?
 4. WORKING IN PUBLIC R.O.W REQUIRES
 PERMIT FROM CITY ENGINEER, RECHARD
 PITTMAN.M.O.T PLANS FOR WORKING IN
 PUBLIC R.O.W MUST ALSO BE APPROVED BY
 CITY ENGINEER PRIOR TO WORK BEGINS
 659-8040.
 5.INSTALLATION OF SHEET PILING IN PUBLIC
 R.O.W AS SHOWN, SHEET C-5 REQUIRES A
 FOOTING AND AERIAL FACADE EASEMENT
 AGREEMENT WITH PLANNING DEPARTMENT,
 659-8031.
 6. INSTALLATION OF 8' SAFETY FENCE ALL
 AROUND THE SITE DURING THE CONSTRUCTION
 IS REQUIRED.
 7. ACCESSIBLE CURB RAMPS AT ALL INTER-
 SECTION CORNERS MUST PROVIDED.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI