2003-11-04 00:00:00 | ******************** UNSAT ************* |
| |
| PLEASE SEE NOTES FROM OTHER REVIEWERS |
| THAT MAY HAVE AN AFFECT ON ELECTRICAL |
| PLANS. |
| |
| 1)NOTE: PLEASE SEE 700.16 FOR LIGHTING |
| IN ELECTRICAL RMS AND THE LIKE. |
| |
| 2)NOTE: PLEASE SEE NOTE FOR LIGHTNING |
| PROTECTIONS SYSTEM REFERENCES NFPA 78, |
| SHOULD READ 780. (MISPRINT). |
| |
| 3)NOTE: PLEASE CLARIFY MEANS OF EGRESS |
| LIGHING ON GRADE LEVEL ACCESS FROM |
| GROUND FLR UNITS EXITING TO STREET. |
| 210.70 AND LS 101 |
| |
| 4)NOTE: PLEASE SEE THAT POOL PERMIT WILL |
| BE REQ'D TO BE UNDER SEPARATE PERMIT |
| ANDWILL REQUIRE A WIRING DIAGRAM FOR |
| POOL EQUIPMENT AT THAT TIME. |
| |
| 5)NOTE: PLEASE SEE PLANS FOR UNITS, |
| STARTING AT E2.01. KEYNOTES MENTION FOR |
| RECEPTS TO HAVE ARC FAULT PROETCTION, |
| HOWEVER, PANEL SCHEDULES MENTION TO SEE |
| NOTES AND THOSE NOTES MENTION LTS AND |
| RECEPTS? PLEASE SEE 210.12. |
| PLEASE SEE THE STATE ADOPTED THE 2002 |
| NEC ON 7/1/03. |
| |
| 6)NOTE: PLEASE SEE THAT WHEN BATHROOMS |
| ARE WIRED TO HAVE ALL LIGHTING AND GFI |
| RECEPT ON ONE CIRCUIT AS PERMITTED UNDER |
| 210.11C3, NO OTHER AREAS INCLUDING |
| ADDTIONAL BATH(S) MAY BE FED. PLEASE |
| ADJUST ALL CIRCUITING ON PLANS AND |
| PANEL SCHEDULES. |
| PLEASE ALSO SEE 210.52D FOR A COUPLE OF |
| MISSING GFI RECEPTS. (B-5) |
| |
| 7)NOTE: PLEASE SEE 210.52 FOR RECEPT |
| SPACING. PLEASE SEE 2' OF WALL SPACES |
| IN MANY UNITS. ONE SET HAS MANY HIGH- |
| -LIGHTED ON YELLOW. |
| |
| 8)NOTE: PLEASE PROVIDE INFORMATION FOR |
| FIRE PUMP OCP ETC PER 695.4B |
| DISC MEANS? SIGNAGE/NOTES ETC. 230.2, |
| 230.72 ETC. |
| PLEASE SEE THAT THIS INFORMATION IS |
| REQ'D ON THESE PLANS. PLEASE ALSO NOTE |
| IF ALL SUBMITTALS FOR GENERATOR SYSTEM |
| IS NOT SUBMITTED WITH THIS PACKAGE THEN |
| GENERATOR SYSTEM WILL BE REQ'D TO BE |
| UNDER SEPARATE PERMITS AND ALL ADDTIONAL |
| FEES WILL BE REQ'D AT THAT TIME ALSO. |
| |
| 9)NOTE: PLEASE PROVIDE INFORMATION FOR |
| MSBR, SHOWN AS HAVING 3 SPACES? AS THIS |
| EQUIPMENT IS A MLO UNIT. PLEASE CLARIFY |
| |
| 10)NOTE: PLEASE PROVIDE A NOTE ON ELEC- |
| -TRICAL AND BLDG PLANS FOR REQUIREMENTS |
| OF 110.26 AND TYPE OF HARDWARE REQ'D |
| ON ELECTRICAL ROOM DOORS THAT MEET. |
| 110.26 |
| |
| 11)NOTE: PLEASE SHOW ALL CONTINUOUS LOAD |
| -S AT 125% PER 215.3,230.42 ETC. |
| INCLUDING LARGEST MOTOR LOADS. |
| |
| 12)NOTE: PLEASE CLARIFY HOW BOTH PANEL |
| "H" AND "HA" ARE SHOWN AS SEC 1O2. |
| |
| 13)NOTE: PLEASE CLARIFY METHOD OF |
| WATER HEATER? |
| |
| 14)NOTE: PLEASE SEE FAC 61G15-23.002 AND |
| PLEASE INCLUDE ALL INFORMATION SET FORTH |
| AND REQUIRED PER THIS AND FS 471 |
| THIS IS REQ'D FOR ALL TRADES WEATHER OR |
| NOT COMMENTED ON. |
| |
| 15)NOTE: PLEASE SEE COPY OF FS 553.80(2) |
| (B) ATTACHED. THIS IS REQ'D TO GO OUT |
| ON ANY PROJECT OF REVIEW THAT HAS HAD |
| ONE/OR ANY OF THE PREVIOUS COMMENTS THE |
| SECOND TIME. THIS IS ONLY A NOTICE. |
| |
| PLEASE NOTE: A RESPONSE LETTER WILL |
| USUALLY HELP THE PROCESS OF PLAN REVIEW |
| AND BEING ABLE TO ISSUE PERMIT. |
| |
| PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| INSERT NEW SHEETS INTO TWO COMPLETE SETS |
| FOR REVIEW AND STAMPING. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |