Plan Review Notes
Plan Review Notes For Permit 03050107
Permit Number 03050107
Review Stop E
Sequence Number 2
Notes
Date Text
2003-11-04 00:00:00******************** UNSAT *************
  
 PLEASE SEE NOTES FROM OTHER REVIEWERS
 THAT MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 1)NOTE: PLEASE SEE 700.16 FOR LIGHTING
 IN ELECTRICAL RMS AND THE LIKE.
  
 2)NOTE: PLEASE SEE NOTE FOR LIGHTNING
 PROTECTIONS SYSTEM REFERENCES NFPA 78,
 SHOULD READ 780. (MISPRINT).
  
 3)NOTE: PLEASE CLARIFY MEANS OF EGRESS
 LIGHING ON GRADE LEVEL ACCESS FROM
 GROUND FLR UNITS EXITING TO STREET.
 210.70 AND LS 101
  
 4)NOTE: PLEASE SEE THAT POOL PERMIT WILL
 BE REQ'D TO BE UNDER SEPARATE PERMIT
 ANDWILL REQUIRE A WIRING DIAGRAM FOR
 POOL EQUIPMENT AT THAT TIME.
  
 5)NOTE: PLEASE SEE PLANS FOR UNITS,
 STARTING AT E2.01. KEYNOTES MENTION FOR
 RECEPTS TO HAVE ARC FAULT PROETCTION,
 HOWEVER, PANEL SCHEDULES MENTION TO SEE
 NOTES AND THOSE NOTES MENTION LTS AND
 RECEPTS? PLEASE SEE 210.12.
 PLEASE SEE THE STATE ADOPTED THE 2002
 NEC ON 7/1/03.
  
 6)NOTE: PLEASE SEE THAT WHEN BATHROOMS
 ARE WIRED TO HAVE ALL LIGHTING AND GFI
 RECEPT ON ONE CIRCUIT AS PERMITTED UNDER
 210.11C3, NO OTHER AREAS INCLUDING
 ADDTIONAL BATH(S) MAY BE FED. PLEASE
 ADJUST ALL CIRCUITING ON PLANS AND
 PANEL SCHEDULES.
 PLEASE ALSO SEE 210.52D FOR A COUPLE OF
 MISSING GFI RECEPTS. (B-5)
  
 7)NOTE: PLEASE SEE 210.52 FOR RECEPT
 SPACING. PLEASE SEE 2' OF WALL SPACES
 IN MANY UNITS. ONE SET HAS MANY HIGH-
 -LIGHTED ON YELLOW.
  
 8)NOTE: PLEASE PROVIDE INFORMATION FOR
 FIRE PUMP OCP ETC PER 695.4B
 DISC MEANS? SIGNAGE/NOTES ETC. 230.2,
 230.72 ETC.
 PLEASE SEE THAT THIS INFORMATION IS
 REQ'D ON THESE PLANS. PLEASE ALSO NOTE
 IF ALL SUBMITTALS FOR GENERATOR SYSTEM
 IS NOT SUBMITTED WITH THIS PACKAGE THEN
 GENERATOR SYSTEM WILL BE REQ'D TO BE
 UNDER SEPARATE PERMITS AND ALL ADDTIONAL
 FEES WILL BE REQ'D AT THAT TIME ALSO.
  
 9)NOTE: PLEASE PROVIDE INFORMATION FOR
 MSBR, SHOWN AS HAVING 3 SPACES? AS THIS
 EQUIPMENT IS A MLO UNIT. PLEASE CLARIFY
  
 10)NOTE: PLEASE PROVIDE A NOTE ON ELEC-
 -TRICAL AND BLDG PLANS FOR REQUIREMENTS
 OF 110.26 AND TYPE OF HARDWARE REQ'D
 ON ELECTRICAL ROOM DOORS THAT MEET.
 110.26
  
 11)NOTE: PLEASE SHOW ALL CONTINUOUS LOAD
 -S AT 125% PER 215.3,230.42 ETC.
 INCLUDING LARGEST MOTOR LOADS.
  
 12)NOTE: PLEASE CLARIFY HOW BOTH PANEL
 "H" AND "HA" ARE SHOWN AS SEC 1O2.
  
 13)NOTE: PLEASE CLARIFY METHOD OF
 WATER HEATER?
  
 14)NOTE: PLEASE SEE FAC 61G15-23.002 AND
 PLEASE INCLUDE ALL INFORMATION SET FORTH
 AND REQUIRED PER THIS AND FS 471
 THIS IS REQ'D FOR ALL TRADES WEATHER OR
 NOT COMMENTED ON.
  
 15)NOTE: PLEASE SEE COPY OF FS 553.80(2)
 (B) ATTACHED. THIS IS REQ'D TO GO OUT
 ON ANY PROJECT OF REVIEW THAT HAS HAD
 ONE/OR ANY OF THE PREVIOUS COMMENTS THE
 SECOND TIME. THIS IS ONLY A NOTICE.
  
 PLEASE NOTE: A RESPONSE LETTER WILL
 USUALLY HELP THE PROCESS OF PLAN REVIEW
 AND BEING ABLE TO ISSUE PERMIT.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT NEW SHEETS INTO TWO COMPLETE SETS
 FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]