2003-11-21 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 ***SEE COMMENT #43***
  
 NOTE:
 MANY OF THE PREVIOUS BUILDING/STRUCTURAL
 PLAN REVIEW COMMENTS HAVE NOT BEEN
 ADDRESSED.
 CHAPTER 553.80(2)(B) FLORIDA STATUTES
 STATES THAT A LOCAL GOVERNMENT SHALL
 IMPOSE A FEE OF FOUR TIMES THE FEE FOR
 PLAN REVIEW, IF PLANS ARE REJECTED THREE
 OR MORE TIMES FOR REPEATED FAILURE TO
 CORRECT A CODE VIOLATION.
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 6/19/03:
  
 1) THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2) IMPACT FEES. THE PLANS SHALL BE TAKEN
 TO PALM BEACH COUNTY BUILDING DEPARTMENT
 FOR IMPACT FEE ASSESSMENT. THEY SHALL BE
 STAMPED AT THAT OFFICE AND A COPY OF THE
 PAID RECEIPT SUBMITTED TO THE CITY OF
 WEST PALM BEACH DEPT OF CONSTRUCTION
 SERVICES BEFORE A PERMIT CAN BE ISSUED.
  
 3) THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES
 BETWEEN THE LOTS WHICH COMBINE TO FORM
 'THE SITE'.SUBMIT A COPY OF THE 'UNITY
 OF TITLE' DOCUMENT SO THAT FBC TABLE 600
 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED
 NOT APPLICABLE.
  
 4) CONDOMINIUM V APARTMENTS.IF THE
 DWELLING UNITS ARE TO BE SOLD AS
 CONDOMINIUMS, NO CERTIFICATE OF
 OCCUPANCY CAN BE ISSUED UNTIL A
 'DECLARATION OF CONDOMINIUM' HAS BEEN
 SUBMITTED TO THE STATE FOR APPROVAL, AND
 THEN RECORDED WITH THE CLERK OF THE
 COUNTY COURT.A RECORDED COPY SHALL BE
 SUBMITTED TO THE CITY FOR RECORDS,
 ADDRESSING PURPOSES, AND NOTIFICATION OF
 PALM BEACH COUNTY PROPERTY APPRAISER'S
 OFFICE.
  
 5) FBC* 104.4.5 SPECIAL FOUNDATION
 PERMIT. THE BUILDING OFFICIAL MAY, AT
 HIS DISCRETION, ISSUE A SPECIAL PERMIT
 FOR THE FOUNDATION ONLY, UPON WRITTEN
 REQUEST BY THE OWNER AND CONTRACTOR. THE
 HOLDER OF SUCH SPECIAL PERMIT IS PROCEED
 ING AT HIS/HER OWN RISK AND WITHOUT
 ASSURANCE THAT A PERMIT FOR THE
 REMAINDER OF THE WORK WILL BE GRANTED
 AND THAT CORRECTIONS WILL NOT BE
 REQUIRED IN ORDER TO MEET THE PROVISIONS
 OF THE TECHNICAL CODES.
  
 6) FBC* 105.13.1SPECIAL INSPECTOR.A
 STRUCTURAL INSPECTION PLAN MUST BE
 SUBMITTED PRIOR TO THE ISSUANCE OF A
 BUILDING PERMIT FOR THE CONSTRUCTION OF
 A THRESHOLD BUILDING.A THRESHOLD
 BUILDING IS ANY BUILDING WHICH IS
 GREATER THAN THREE STORIES OR 50 FEET IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY
 OCCUPANCY WITH 5,000 SQFT AREA AND
 GREATER THAN 500 OCCUPANTS.THREE
 COPIES OF THE PLANS AND OTHER DOCUMENTS
 WILL BE REQUIRED FOR PERMITTING PURPOSES
  
 7) A SEPARATE PERMIT APPLICATION WILL BE
 REQUIRED FOR THE SWIMMING POOL.
  
 8) THIS COMMENT HAS NOT BEEN ADDRESSED.
 FBC* 1804.2.2SHEET S-0, FOUNDATIONS
 SUBMIT COPIES OF GFA INTERNATIONAL SOIL
 REPORT AS REFERENCED IN THE NOTES.
  
 9) THIS COMMENT HAS NOT BEEN ADDRESSED.
 FBC 13-103.1.1.1 AND 103.1.2SHEET 2
 OF THE SUBMITTED ENERGY CODE COMPLIANCE
 FORMS SHALL BE SIGNED BY THE OWNER (OR
 THE PROJECT ARCHITECT OR OTHER
 AUTHORIZED AGENT DESIGNATED BY THE
 OWNER) TO CERTIFY COMPLIANCE WITH THE
 CODE.ALSO THE ARCHITECT'S NAME AND
 REGISTRATION NUMBER SHALL BE ADDED ABOVE
 THAT OF THE MEP ENGINEER.
  
 10) FBC* F102.2.4FIRE DISTRICT.THE
 ROOF COVERING SHALL CONFORM TO CLASS A
 OR B AS DEFINED IN FBC 1505.AMEND THE
 PLANS TO DEMONSTRATE COMPLIANCE.
  
 11) THIS COMMENT HAS NOT BEEN ADDRESSED.
 SUBMIT PRODUCT APPROVALS FOR THE
 WINDOWS, STOREFRONTS, EXTERIOR DOORS AND
 ROOFING PRODUCTS.
  
 12) THIS COMMENT HAS NOT BEEN ADDRESSED.
 FBC* 104.2.1.2BUILDING DATA.THE
 BUILDING AREAS, CONSTRUCTION TYPE AND
 OTHER CODE/BUILDING DESIGN CRITERIA
 SHALL BE STATED ON THE PLANS(NOTE: TO
 COMPLY WITH TABLE 500 FOR A SPINKLERED,
 TWO STOREY ENCLOSED PARKING GARAGE
 >60,000 SQ FT, TYPE I CONSTRUCTION IS
 REQUIRED)
  
 13) FBC 1606.1.7WIND LOAD.THIS
 COMMENT HAS NOT BEEN PROPERLY ADDRESSED.
 IT IS NOTED THAT SHEET S-0 INCLUDES
 INFORMATION UNDER THE TITLE 'WIND LOADS'
 BUT THE WIND IMPORTANCE FACTOR, INTERIOR
 PRESSURE COEFFICIENT, EXTERIOR COMPONENT
 AND CLADDING WIND PRESSURES MUST ALSO BE
 ADDED.
  
 14) FBC* 104.2.1SHEET A.23.THE NORTH
 ELEVATION DOES NOT SHOW THE FIRST FLOOR
 DOOR #15 (BETWEEN GRIDS T.3 & T.4) TO
 THE VALET.AMEND/CLARIFY.
  
 17) FBC 705.1.2SHEETS LS.1 TO LS.4.
 THIS COMMENT HAS NOT BEEN PROPERLY
 ADDRESSED.AMEND THE LEGEND TO INDICATE
 THE REQUIRED ONE HOUR FIRE RATING FOR
 THE ELEVATOR LOBBIES AND TWO HOUR RATING
 FOR THE WALL TYPE SHOWN AROUND THE STAIR
 SHAFTS, TRASH CHUTE ETC.
  
 18) THIS COMMENT HAS NOT BEEN ADDRESSED.
 FBC 412.6SHEET A.02, PARKING LEVEL
 PLAN.AMEND THE PLAN TO CLARIFY THE
 PURPOSED (I.E. IN LIEU OF ELEVATOR
 LOBBY), CONSTRUCTION AND FIRE-RATING OF
 THE WALL/DOOR THAT HAS BEEN PROVIDED IN
 FRONT OF ELEVATORS 1 TO 3.
  
 20) THIS COMMENT HAS NOT BEEN ADDRESSED.
 FBC 411.2.6SHEETS A.03 & A.48.THE
 PUMP ROOM SHALL BE SEPARATED FROM THE
 PARKING GARAGE BY 1-HOUR FIRE
 RESISTANT CONSTRUCTION.AMEND THE PLANS
  
 23) THIS COMMENT HAS NOT BEEN ADDRESSED.
 FBC TABLES 704.2.4 & 705.1.2SHEETS
 A.04 & A.48.THE MANAGER'S OFFICE
 SUITE, THE CONFERENCE ROOM, CLUB ROOM,
 PANTRY AND FITNESS CENTER ARE ON THE
 EXIT ACCESS CORRIDOR AND SHALL BE AT
 LEAST 30-MINUTE FIRE-RATED WITH
 20-MINUTE FIRE-RATED DOORS (DOOR #'S 16,
 27, 32 AND THE PANTRY DOOR WHICH IS
 INCORRECTLY LABELLED AS DOOR #58). AMEND
 THE PLANS.
  
 26) FBC 11-4-13.6 SHEET A.12 & 13 GROUND
 LEVEL PLANS, MANEUVERING CLEARANCES AT
 DOORS. THE DOORS TO THE CARD ROOM (024),
 CONFERENCE ROOM (016) AND CONFERENCE
 WAITNG ROOM (016), SHALL HAVE A MINIMUM
 OF 18" CLEARANCE BETWEEN THE STRIKE EDGE
 OF THE DOOR AND THE ADJACENT WALL ON THE
 PULL SIDE OF THE DOOR (REF FIG.25A).
 AMEND THE PLANS.THIS COMMENT ALSO
 APPLIES TO THE RESIDENTIAL UNIT ENTRANCE
 DOORS (FOR EXAMPLE GROUND LEVEL UNITS
 A5, A5 MOD, B2.1, B4 AND B6)
  
 28) THIS COMMENT HAS NOT BEEN ADDRESSED.
 FBC 1012.1.4SHEET A.36.THE STOREY
 EXIT DOORS INTO STAIR #3 AT EACH LEVEL
 SHALL LEAVE, UNOBSTRUCTED, AT LEAST ONE
 HALF OF THE REQUIRED LANDING WIDTH.
 AMEND THE PLANS.
  
 29) THIS COMMENT HAS NOT BEEN ADDRESSED.
 FBC 1007.5.5SHEET A.34, STAIR #1 PLANS
 THE HANDRAILS SHALL EXTEND AT LEAST 12"
 HORIZONTALLY BEYOND THE TOP RISER OF
 EACH FLIGHT.THE STAIR #1 PLANS SHOW
 ONLY 11".AMEND THE PLANS.
  
 30) FBC 1015.4GUARDRAIL STRENGTH.THE
 PLANS SHALL BE AMENDED TO STATE THE
 STRENGTH REQUIREMENTS SET OUT IN
 FBC 1608.2
  
 33) THIS COMMENT HAS NOT BEEN ADDRESSED.
 FBC *104.2.1SHEET A.44, DETAIL M,
 SLIDING GLASS DOOR THRESHOLD.THE
 DETAIL SHALL MAKE REFERENCE TO 'THE DOOR
 PRODUCT APPROVAL' FOR ANCHOR
 SPECIFICATION.AMEND THE DETAIL.
  
 34) THIS COMMENT HAS NOT BEEN ADDRESSED.
 FBC 411.2.3AUTOMOBILE PARKING GARAGE,
 GUARDING.THE INTERIOR PARKING GARAGE
 WALLS ADJACENT THE VEHICLE RAMP, STAIR 2
 AND 4, AND THE FRONT WALL OF THE
 ELEVATOR SHAFTS (SEE SHEET S-3) SHALL BE
 DESIGNED TO WITHSTAND IMPACT LOADING IN
 ACCORDANCE WITH FBC 1608.2.3.PROVIDE
 STRUCTURAL DETAILS OF THE WALLS AT THESE
 LOCATIONS.
  
 35) FBC 2405.2THE SHOWER ENCLOSURE
 GLAZING IS IN A 'HAZARDOUS LOCATION' AND
 REQUIRED TO BE SAFETY GLASS SATISFYING
 THE REQUIREMENTS OF THE CONSUMER PRODUCT
 SAFETY COMMISSION 16, CODE OF FEDERAL
 REGULATIONS, PART 1201 (CPSC 16-CFR,
 PART 1201).AMEND THE PLANS TO
 DEMONSTRATE COMPLIANCE.
  
 39) THIS COMMENT HAS NOT BEEN ADDRESSED.
 FBC 11-4.15.2SHEET A.67,DRINKING
 FOUNTAIN SPOUT HEIGHT AND KNEE CLEARANCE
 THE HEIGHT FROM FINISHED FLOOR TO THE
 SPOUT (NOT THE TOP OF THE FOUNTAIN TRAY)
 SHALL BE 36" (REF: FIG. 27A).THE
 DIMENSIONS ARE SHOWN INCORRECTLY ON ONE
 OF THE TWO DETAILS.AMEND THE PLANS.
  
 41) FBC 1010.1SHEET LS.2WHAT IS THE
 ROUTE TO EXIT DISCHARGE FROM STAIR #4?
 AMEND THE PLANS TO CLARIFY.
  
 42) SHEET S-17, UPPER LEVEL ROOF PLAN
 MAKES A NUMBER OF REFERENCES TO HUGHES
 ANCHORS.THAT COMPANY NO LONGER
 SUPPLIES ANCHORS.AMEND THE PLANS TO
 SPECIFY VALID ANCHORS AND STATE THE
 NUMBER AND SIZE FASTENERS.
  
 43) MANY OF THE COMMENTS FROM THE
 PREVIOUS REVIEW HAVE NOT BEEN ADDRESSED.
 A FULL REVIEW HAS NOT BEEN CARRIED OUT
 BECAUSE NO COMMENT RESPONSE LETTERS, OLD
 PLANS OR REVISION CLOUDS/MARKERS WERE
 INCLUDED WITH THE RE-SUBMITTAL.TO
 EXPEDITE THE REVIEW, THE RE-SUBMITTAL
 SHALL INCLUDE AT LEAST ONE OF THE ABOVE
 MEANS OF DESCRIBING THE REVISIONS MADE.
  
 44) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.