2005-08-02 00:00:00 | REVISION DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 1 |
| |
| 1. SHT P1.02 REVISION #6 NOT FOUND, AND |
| OTHER REVISIONS TO SHEET NOT CLOUDED OR |
| NUMBERED. (CONDENSATE DRAIN LINES, STORM |
| DRAIN LINES, BACKWATER VALVE ECT.). - |
| NUMBER 44, BACKFLOW PREVENTION REQUIRED |
| ON NEW IRRIGATION LINE. SECTION 608.13.2 |
| 2. SHT P1.09 REVISION #1 NOT FOUND. |
| REVISIONS REQUIRED FOR ALL RISER |
| DIAGRAMS CHANGED ON THIS REVISION. - |
| CONDENSATE AND STORM LINES DELETED FROM |
| PLANS. - WILL THESE BE SHOWN ON ANOTHER |
| SHEET? PLEASE CLARIFY SECTION 104.2.1. |
| 3. SHT P1.09 INDICATE HOW THE LISTING |
| FOR FIRE RATINGS FOR SEPARATION WALLS |
| WILL BE MAINTAINED WITH THE LAUNDRY |
| BOXES IN TENANT SEPARATION WALLS BETWEEN |
| UNITS B1A.1/B1A.1, B1.2/B1.2, & |
| B1C.2/B1C.2. ALSO UNIT B2.2 AND THE EXIT |
| CORRIDOR. |
| 4. SHT P1.09 UNABLE TO READ INFORMATION |
| AT W/H-A/C CLOSETS AT UNITS B1C.2 AND |
| B1D. SECTION 104.2.1. |
| 5. SHT P1.10 REVISION #2 NOT FOUND AND |
| MANY REVISIONS NOT CLOUDED OR NUMBERED. |
| SECTION 104.2.1. |
| 5. P3.01C NEW SHEET WITH REVISIONS? |
| PLEASE CLARIFY. WHAT IS THE INTENT OF |
| THIS SHEET? THIS SHEET DOES NOT REFLECT |
| THE INFORMATION OF THE PREVIOUS SHEET |
| SHOWING THE SANITARY COLLECTION SYSTEM. |
| ONLY SHOWS ONE CHANGE CLOUDED AND |
| NUMBERED. ALL RISER DESIGNATIONS ARE |
| CHANGED AND AS SUCH WILL HAVE TO BE |
| CHANGED ON ALL SHEETS FOR ALL FLOORS TO |
| REFLECT THIS CHANGE. BUILDING DRAIN |
| LAYOUT IS CHANGED WITHOUT CLOUDS OR |
| REVISION NUMBERS. IF THIS REVISION IS A |
| REVISION TO SHEET P3.01, (WHICH IT |
| APPEARS TO BE), SIMPLY REVISE SHE P3.01. |
| A NEW SHEET NUMBER IS NOT REQUIRED AND |
| ONLY CAUSES CONFUSION BECAUSE TWO |
| COLLECTION ISOMETRICS WILL BE SHOWN FOR |
| ONE SYSTEM. SECTION 104.2.1. |
| 6. SHT P3.01C STUDOR VENT WILL REQUIRE A |
| RELEIF VENT PER SECTION 917.3.2. - |
| STUDOR VENTS AT THE LIFT STATIONS ARE |
| NOT APPROVED. - INFORMATION ON P3.01C |
| WILL DELETE RISER "A" IF THIS SHEET |
| SUPERCEEDS SHEET P3.01. PLEASE CLARIFY. |
| SECTION 104.2.1. |
| 7. REVISIONS 5, 6, & 7 ARE NOT FOUND. |
| PLEASE CLARIFY. SECTION 104.2.1. MANY |
| CHANGES FOUND ON NEW SHEET ARE NOT |
| CLOUDED OR NUMBERED/. NO REVIEW OF SHEET |
| UNTILL ALL CHANGES TO SHEET FOLLOWING |
| THE SHEET SIGNED/SEALED 12-17-04 ARE |
| CLOUDED AND NUMBERED. |
| |