2005-06-13 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 FUEL GAS |
| FBC-2001 CHAPTER 1 |
| |
| |
| 1. SHT P1.01 REVISION 7 NOT FOUND. |
| PLEASE CLOUD AND NUMBER EACH REVISION. |
| SECTION 104.2.1. |
| 2. SHT P1.02 REVISION 6 NOT FOUND. |
| PLEASE CLOUD AND NUMBER EACH REVISION. |
| SECTION 104.2.1. |
| 3. SHT P1.03 FOLLOWING TO NOT MEET CODE: |
| A. TUB NOT VENTED UNIT B1.1 BATH #2 |
| B. INDICATE WHERE S/14 RISER CONNECTS |
| TO THE BLDG. DRAIN. SECTION 104.2.1. |
| C. UNIT STUDIO "S2" TOILET IS NOT |
| VENTED. LAV SHOULD VENT THE BATHROOM |
| FIXTURES AND KITCHEN SINK/WASH MACHINE |
| SHALL DISCHARGE DOWNSTREAM OF THE WET |
| VENT. SECTIONS 901.2.1 & 909.1. |
| D. 2" PIPE FEEDING THE HOSE BIBB? |
| PLEASE CLARIFY. SECTION 104.2.1. |
| E. UNIT A2 UNABLE TO READ RISER |
| DESIGNATION OVER A/C UNIT. SECTION |
| 104.2.1. |
| F. REVISIONS 2, 3, & 4 NOT FOUND. |
| PLEASE CLOUD AND NUMBER EACH REVISION. |
| SECTION 104.2.1. |
| 4. SHT P1.04 REVISION #1 NOT FOUND. |
| PLEASE CLOUD AND NUMBER ALL REVISIONS. |
| SECTION 104.2.1. - SEE UNIT "B2" LAV |
| CONNECTION TO BRANCH LINE NOT DIRECTING |
| WASTE IN DIRECTIONS OF FLOW. SECTION |
| 706.3. (COL. LINE W.K) |
| 5. SHT P1.05 REVISION #1 NOT FOUND. |
| PLEASE CLOUD AND NUMBER ALL REVISIONS. |
| SECTION 104.2.1. - TWO NUMBER 46 RISERS |
| BUT NO NUMBER 47. PLEASE CLARIFY. |
| 6. SHT P1.06 REVISION #1 NOT FOUND. |
| PLEASE CLOUD AND NUMBER ALL REVISIONS. |
| SECTION 104.2.1. - SHEET INDICATES |
| "TYPICAL FLOOR PLAN - PLUMBING" FOR |
| WHICH FLOORS? SECTION 104.2.1. - TWO #46 |
| SANT. RISERS AND NO #47 SANT. RISER. |
| PLEASE CLARIFY. |
| 7. SHT P1.07 REVISION #1 NOT FOUND. |
| PLEASE CLOUD AND NUMBER ALL REVISIONS. |
| SECTION 104.2.1. - TWO #46 RISERS AND NO |
| #47 RISER FOUND. PLEASE CLARIFY. |
| 8. SHT P1.08 REVISION #1 NOT FOUND. |
| PLEASE CLOUD AND NUMBER ALL REVISIONS. |
| SECTION 104.2.1. - SHOW ALL RISER |
| DESIGNATION NUMBERS. SECTION 104.2.1. |
| 9. SHT P1.09 REVISION #1 NOT FOUND. |
| PLEASE CLOUD AND NUMBER ALL REVISIONS. |
| SECTION 104.2.1. - TWO NUMBER 46 SANT. |
| RISERS AND NO #47 RISER FOUND. PLEASE |
| CLARIFY. |
| 10. SHT P1.10 THE FOLLOWING SANT. RISERS |
| SHOW UP ON THIS SHEET, BUT WERE NOT |
| NOTED ON THE PREVIOUS SHEETS FROM THE |
| GROUND FLOOR UP. S/16, S/33, S/51, & |
| S/63 PLEASE CLARIFY.-INDICATE THE |
| LOCATION OF VTR FOR SANT. RISER 74. - |
| RISER S/63 DOES NOT REFLECT THE ROOF |
| PLAN. THE FLOOR DRAIN IS NOT SHOWN ON |
| RISER. PLEASE CORRELATE RISER WITH FLOOR |
| PLAN. - FLOOR DRAIN BY S/64 NOT PIPED TO |
| ANY SANT. RISER. PLEASE CLARIFY. SECTION |
| 104.2.1. |
| 11. SHT P3.01 SANT. RISER S/8 OFFSET |
| VENT REQUIRED. SECTION 915 - VENT STACK |
| SHALL CONNECT AT OR BELOW THE THE LOWEST |
| HORIZONTAL BRANCH. SECTION 903.4. - |
| STACK VENT SHALL RUN UNDIMINISHED IN |
| SIZE AND AS DIRECTLY AS POSSIBLE FROM |
| THE BUILDING DRAIN THROUGH TO THE OPEN |
| AIR. SECTION 903.1. |
| 12 SHT P3.01 SANT. RISER S/1 A VENT |
| STACK IS REQUIRED PER SECTION 903.2 - |
| VENT STACK CONNECTION APPEARS TO BE A |
| HORIZONTAL DRY VENT. THIS IS NOT |
| APPROVED PER SECTIONS 905.3 & 905.4. |
| 13. SHT P3.01 SANT. RISER S/6-W/7, THE |
| FITTING DOWNSTREAM OF STACKS PICKING UP |
| THE W/M & TUB DOES NOT DIRECT THE WASTE |
| IN THE DIRECTION OF FLOW AS REQUIRED IN |
| SECTION 706.3. |
| 14. SHT P3.01A SANT. RISER S/76 |
| INDICATES FLOORS 3 THRU 7 TWICE, BUT NO |
| FLOOR 8. PLEASE CLARIFY. SECTION |
| 104.2.1. |
| 15. SHT P301A SANT. RISER S/19 DOES NOT |
| REFLECT THE FLOOR PLAN. SHOWER MISSING |
| FROM RISER AND TUB SHOWN IN DIFFERENT |
| LOCATION. PLEASE CORRELATE FLOOR PLAN & |
| RISER DIAGRAM. SECTION 104.2.1. |
| 16. SHT P3.01A FLOOR DRAIN NEAR SANT. |
| RISER S/69 REQUIRES A RELIEF VENT FOR |
| THE AIR ADMITTANCE VALVE. SECTION |
| 917.3.2. |
| 17. SHT P3.01C AIR ADMITTANCE VALVE NOT |
| APPROVED FOR LIFT STATION. ONLY APPROVED |
| FOR NEGATIVE PRESSURE. PLEASE SUBMIT |
| MANUFACTURE SPECIFICATION AND |
| INSTALLATION SHEETS FOR VALVE INDICATING |
| APPROVAL FOR INSTALLATION FOR THIS TYPE |
| OF APPLICATION.SECTION 303.2 |
| 18. SHT P3.01C FLOOR SINK FOR INDIRECT |
| WASTE FROM 3" FSP THE AIR ADMITTANCE |
| VALVE REQUIRES A RELIEF VENT. SECTION |
| 917.3.2. |
| 19. SHT P3.01C BUILDING DRAIN LINES DO |
| NOT REFLECT THE FLOOR PLAN DOWNSTREAM OF |
| RISERS I, J, & K. ALSO THE PIPE SIZING |
| FOR I, J, & K DO NOT REFLECT WHAT IS |
| STATED IN KEY NOTES #10 WHICH IS 4". |
| 20. SHT P3.01C INDICATE IF FLOOR DRAIN |
| PIPING TO THE LIFT STATION. IT APPEARS |
| TO BE ON THE FLOOR ABOVE. PLEASE |
| CLARIFY. SECTION 104.2.1. - ALSO ALL |
| THREE FLOOR DRAINS TO LIFT STATIONS ARE |
| NOT VENTED. SECTION 901.2.1. |
| 21. SHT P3.02 SANT. RISER S/30, TUB NOT |
| VENTED AT THE BASE OF SANT. RISER. |
| SECTION 901.2.1. |
| 22. SHT P3.02 TOILET ROOM DOWNSTREAM OF |
| RISERS 2/37-S/67 DOES NOT REFLECT THE |
| FLOOR PLAN. LAV NOT SHOWN. CORRELATE |
| FLOOR PLAN AND RISER. SECTION 104.2.1. - |
| REVISIONS 2 & 3 NOT FOUND. PLEASE CLOUD |
| AND NUMBER EACH REVISION. |
| 23. SHT P3.02 SANT. RISER DIAGRAM, A |
| VENT STACK IS REQUIRED, AND AN OFFSET |
| VENT IS REQUIRED. SECTIONS 903.3 & 915. |
| 24. SHT P3.02A BATHROOM DOWNSTREAM OF |
| RISER S/53, THE LAV IS MISSING ON THE |
| RISER DIAGRAM. THE LAV SHOULD VENT THE |
| BATHROOM GROUP AND THE KITCHEN SHOULD |
| CONNECT TO THE LINE WITH THE WASH |
| MACHINE AND SHOULD NOT DRAIN THROUGHT |
| THE HORIZONTAL WET VENT OF THE BATHROOM |
| FIXTURES. SECTION 909.1. - THIS IS A NEW |
| SHEET AND SHOWS 4 DIFFERENT REVISIONS. |
| PLEASE CLARIFY. |
| 25. SHT P3.03 SANT. RISER S/44 DOES NOT |
| REFLECT THE FLOOR PLAN. WASH MACHINE IS |
| MISSING. SECTION 104.2.1. - REVISIONS 2 |
| & 3 NOT FOUND. PLEASE CLOUD AND NUMBER |
| EACH REVISION. SECTION 104.2.1. |
| 26. SHT P3.04 SANT. RISER S/58 DOES NOT |
| REFLECT THE FLOOR PLAN, AND THE FIXTURES |
| ARE MISLABLED AS LAVS. KITCHEN SINK |
| MISSING 2ND FLOOR. SECTION 104.2.1. - |
| REVISIONS 2 & 3 NOT FOUND. PLEASE CLOUD |
| AND NUMBER EACH REVISION. SECTION |
| 104.2.1. |
| 27. SHT P3.09 REVISIONS 5 & 6 NOT FOUND. |
| PLEASE CLOUD AND NUMBER EACH REVISIONS. |
| SECTION 104.2.1. |
| 28. SHT P3.11 NATURAL GAS ISOMETRIC: |
| A. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2001 |
| FUEL GAS CODE. |
| 28. SHT P3.12 REVISIONS 2 & 3 NOT FOUND. |
| PLEASE CLOUD AND NUMBER ALL REVISIONS. |
| SECTION 104.2.1. |
| 29. SHT P4.01 REVISION #2 NOT FOUND. |
| PLEASE CLOUD AND NUMBER EACH REVISIONS. |
| SECTION 104.2.1. |
| 30. THE FOLLOWING SHEETS WERE APPROVED |
| AND ONE HAS BEEN ATTACHED TO FILE SET. |
| P.1.11, P2.01. [2.02, P2.03, P2.04, |
| P3.01B, P3.05, P3.06, & P4.02. |
| |
| REVIEW BY KEN STEVENS |