Plan Review Notes
Plan Review Notes For Permit 03050107
Permit Number 03050107
Review Stop P
Sequence Number 12
Notes
Date Text
2005-06-13 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
  
  
 1. SHT P1.01 REVISION 7 NOT FOUND.
 PLEASE CLOUD AND NUMBER EACH REVISION.
 SECTION 104.2.1.
 2. SHT P1.02 REVISION 6 NOT FOUND.
 PLEASE CLOUD AND NUMBER EACH REVISION.
 SECTION 104.2.1.
 3. SHT P1.03 FOLLOWING TO NOT MEET CODE:
 A. TUB NOT VENTED UNIT B1.1 BATH #2
 B. INDICATE WHERE S/14 RISER CONNECTS
 TO THE BLDG. DRAIN. SECTION 104.2.1.
 C. UNIT STUDIO "S2" TOILET IS NOT
 VENTED. LAV SHOULD VENT THE BATHROOM
 FIXTURES AND KITCHEN SINK/WASH MACHINE
 SHALL DISCHARGE DOWNSTREAM OF THE WET
 VENT. SECTIONS 901.2.1 & 909.1.
 D. 2" PIPE FEEDING THE HOSE BIBB?
 PLEASE CLARIFY. SECTION 104.2.1.
 E. UNIT A2 UNABLE TO READ RISER
 DESIGNATION OVER A/C UNIT. SECTION
 104.2.1.
 F. REVISIONS 2, 3, & 4 NOT FOUND.
 PLEASE CLOUD AND NUMBER EACH REVISION.
 SECTION 104.2.1.
 4. SHT P1.04 REVISION #1 NOT FOUND.
 PLEASE CLOUD AND NUMBER ALL REVISIONS.
 SECTION 104.2.1. - SEE UNIT "B2" LAV
 CONNECTION TO BRANCH LINE NOT DIRECTING
 WASTE IN DIRECTIONS OF FLOW. SECTION
 706.3. (COL. LINE W.K)
 5. SHT P1.05 REVISION #1 NOT FOUND.
 PLEASE CLOUD AND NUMBER ALL REVISIONS.
 SECTION 104.2.1. - TWO NUMBER 46 RISERS
 BUT NO NUMBER 47. PLEASE CLARIFY.
 6. SHT P1.06 REVISION #1 NOT FOUND.
 PLEASE CLOUD AND NUMBER ALL REVISIONS.
 SECTION 104.2.1. - SHEET INDICATES
 "TYPICAL FLOOR PLAN - PLUMBING" FOR
 WHICH FLOORS? SECTION 104.2.1. - TWO #46
 SANT. RISERS AND NO #47 SANT. RISER.
 PLEASE CLARIFY.
 7. SHT P1.07 REVISION #1 NOT FOUND.
 PLEASE CLOUD AND NUMBER ALL REVISIONS.
 SECTION 104.2.1. - TWO #46 RISERS AND NO
 #47 RISER FOUND. PLEASE CLARIFY.
 8. SHT P1.08 REVISION #1 NOT FOUND.
 PLEASE CLOUD AND NUMBER ALL REVISIONS.
 SECTION 104.2.1. - SHOW ALL RISER
 DESIGNATION NUMBERS. SECTION 104.2.1.
 9. SHT P1.09 REVISION #1 NOT FOUND.
 PLEASE CLOUD AND NUMBER ALL REVISIONS.
 SECTION 104.2.1. - TWO NUMBER 46 SANT.
 RISERS AND NO #47 RISER FOUND. PLEASE
 CLARIFY.
 10. SHT P1.10 THE FOLLOWING SANT. RISERS
 SHOW UP ON THIS SHEET, BUT WERE NOT
 NOTED ON THE PREVIOUS SHEETS FROM THE
 GROUND FLOOR UP. S/16, S/33, S/51, &
 S/63 PLEASE CLARIFY.-INDICATE THE
 LOCATION OF VTR FOR SANT. RISER 74. -
 RISER S/63 DOES NOT REFLECT THE ROOF
 PLAN. THE FLOOR DRAIN IS NOT SHOWN ON
 RISER. PLEASE CORRELATE RISER WITH FLOOR
 PLAN. - FLOOR DRAIN BY S/64 NOT PIPED TO
 ANY SANT. RISER. PLEASE CLARIFY. SECTION
 104.2.1.
 11. SHT P3.01 SANT. RISER S/8 OFFSET
 VENT REQUIRED. SECTION 915 - VENT STACK
 SHALL CONNECT AT OR BELOW THE THE LOWEST
 HORIZONTAL BRANCH. SECTION 903.4. -
 STACK VENT SHALL RUN UNDIMINISHED IN
 SIZE AND AS DIRECTLY AS POSSIBLE FROM
 THE BUILDING DRAIN THROUGH TO THE OPEN
 AIR. SECTION 903.1.
 12 SHT P3.01 SANT. RISER S/1 A VENT
 STACK IS REQUIRED PER SECTION 903.2 -
 VENT STACK CONNECTION APPEARS TO BE A
 HORIZONTAL DRY VENT. THIS IS NOT
 APPROVED PER SECTIONS 905.3 & 905.4.
 13. SHT P3.01 SANT. RISER S/6-W/7, THE
 FITTING DOWNSTREAM OF STACKS PICKING UP
 THE W/M & TUB DOES NOT DIRECT THE WASTE
 IN THE DIRECTION OF FLOW AS REQUIRED IN
 SECTION 706.3.
 14. SHT P3.01A SANT. RISER S/76
 INDICATES FLOORS 3 THRU 7 TWICE, BUT NO
 FLOOR 8. PLEASE CLARIFY. SECTION
 104.2.1.
 15. SHT P301A SANT. RISER S/19 DOES NOT
 REFLECT THE FLOOR PLAN. SHOWER MISSING
 FROM RISER AND TUB SHOWN IN DIFFERENT
 LOCATION. PLEASE CORRELATE FLOOR PLAN &
 RISER DIAGRAM. SECTION 104.2.1.
 16. SHT P3.01A FLOOR DRAIN NEAR SANT.
 RISER S/69 REQUIRES A RELIEF VENT FOR
 THE AIR ADMITTANCE VALVE. SECTION
 917.3.2.
 17. SHT P3.01C AIR ADMITTANCE VALVE NOT
 APPROVED FOR LIFT STATION. ONLY APPROVED
 FOR NEGATIVE PRESSURE. PLEASE SUBMIT
 MANUFACTURE SPECIFICATION AND
 INSTALLATION SHEETS FOR VALVE INDICATING
 APPROVAL FOR INSTALLATION FOR THIS TYPE
 OF APPLICATION.SECTION 303.2
 18. SHT P3.01C FLOOR SINK FOR INDIRECT
 WASTE FROM 3" FSP THE AIR ADMITTANCE
 VALVE REQUIRES A RELIEF VENT. SECTION
 917.3.2.
 19. SHT P3.01C BUILDING DRAIN LINES DO
 NOT REFLECT THE FLOOR PLAN DOWNSTREAM OF
 RISERS I, J, & K. ALSO THE PIPE SIZING
 FOR I, J, & K DO NOT REFLECT WHAT IS
 STATED IN KEY NOTES #10 WHICH IS 4".
 20. SHT P3.01C INDICATE IF FLOOR DRAIN
 PIPING TO THE LIFT STATION. IT APPEARS
 TO BE ON THE FLOOR ABOVE. PLEASE
 CLARIFY. SECTION 104.2.1. - ALSO ALL
 THREE FLOOR DRAINS TO LIFT STATIONS ARE
 NOT VENTED. SECTION 901.2.1.
 21. SHT P3.02 SANT. RISER S/30, TUB NOT
 VENTED AT THE BASE OF SANT. RISER.
 SECTION 901.2.1.
 22. SHT P3.02 TOILET ROOM DOWNSTREAM OF
 RISERS 2/37-S/67 DOES NOT REFLECT THE
 FLOOR PLAN. LAV NOT SHOWN. CORRELATE
 FLOOR PLAN AND RISER. SECTION 104.2.1. -
 REVISIONS 2 & 3 NOT FOUND. PLEASE CLOUD
 AND NUMBER EACH REVISION.
 23. SHT P3.02 SANT. RISER DIAGRAM, A
 VENT STACK IS REQUIRED, AND AN OFFSET
 VENT IS REQUIRED. SECTIONS 903.3 & 915.
 24. SHT P3.02A BATHROOM DOWNSTREAM OF
 RISER S/53, THE LAV IS MISSING ON THE
 RISER DIAGRAM. THE LAV SHOULD VENT THE
 BATHROOM GROUP AND THE KITCHEN SHOULD
 CONNECT TO THE LINE WITH THE WASH
 MACHINE AND SHOULD NOT DRAIN THROUGHT
 THE HORIZONTAL WET VENT OF THE BATHROOM
 FIXTURES. SECTION 909.1. - THIS IS A NEW
 SHEET AND SHOWS 4 DIFFERENT REVISIONS.
 PLEASE CLARIFY.
 25. SHT P3.03 SANT. RISER S/44 DOES NOT
 REFLECT THE FLOOR PLAN. WASH MACHINE IS
 MISSING. SECTION 104.2.1. - REVISIONS 2
 & 3 NOT FOUND. PLEASE CLOUD AND NUMBER
 EACH REVISION. SECTION 104.2.1.
 26. SHT P3.04 SANT. RISER S/58 DOES NOT
 REFLECT THE FLOOR PLAN, AND THE FIXTURES
 ARE MISLABLED AS LAVS. KITCHEN SINK
 MISSING 2ND FLOOR. SECTION 104.2.1. -
 REVISIONS 2 & 3 NOT FOUND. PLEASE CLOUD
 AND NUMBER EACH REVISION. SECTION
 104.2.1.
 27. SHT P3.09 REVISIONS 5 & 6 NOT FOUND.
 PLEASE CLOUD AND NUMBER EACH REVISIONS.
 SECTION 104.2.1.
 28. SHT P3.11 NATURAL GAS ISOMETRIC:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 28. SHT P3.12 REVISIONS 2 & 3 NOT FOUND.
 PLEASE CLOUD AND NUMBER ALL REVISIONS.
 SECTION 104.2.1.
 29. SHT P4.01 REVISION #2 NOT FOUND.
 PLEASE CLOUD AND NUMBER EACH REVISIONS.
 SECTION 104.2.1.
 30. THE FOLLOWING SHEETS WERE APPROVED
 AND ONE HAS BEEN ATTACHED TO FILE SET.
 P.1.11, P2.01. [2.02, P2.03, P2.04,
 P3.01B, P3.05, P3.06, & P4.02.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]