Plan Review Notes
Plan Review Notes For Permit 03050107
Permit Number 03050107
Review Stop B
Sequence Number 113
Notes
Date Text
2006-08-27 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 REVISION SUBMITTED ON 8/18/06 FOR SHEET
 A.04.
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) FBC 704.2.4 AND 705.1.2EXIT ACCESS
 CORRIDOR.THE BUSINESS CENTER DOOR WAS
 SPECIFIED ON SHEET A.48 AS A MIN. 20
 MINUTE FIRE-RATED DOOR BECAUSE IT IS ON
 AN EXIT ACCESS CORRIDOR.THE DOOR SHALL
 NOT BE OMITTED.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6652ROBERT BROWN
 E-MAIL: [email protected]
  