Date |
Text |
2005-12-24 00:00:00 | ********** UNSAT ********** |
| |
| ** PLEASE SEE REVISONS FOR SOME UNITS |
| WHICH WERE STAMPED ON 10/9/05 HAVE SINCE |
| BEEN VOIDED. |
| |
| ** PLEASE SEE NOTE # 3 FROM SECOND |
| REVIEW ON 10/9/05 HAS BEEN RECENDED. |
| DOOR LOCATED TO SEPARATE BATHRM FROM |
| BEDRM FOR UNITS3 |
| |
| ** PLEASE SEE THE FOLLOWING NOTES, |
| PLEASE CORRELATE ALL UNITS AND SUBMIT |
| REVISIONS FOR ALL UNITS. |
| |
| |
| 1)NOTE: PLEASE SEE 210.52C1, C3, C4 FOR |
| KITCHEN GFI RECEPT SPACING. PLEASE SEE |
| SOME UNITS CONTAIN ADDED RECEPTS FOR |
| AREA OF 12' OR MORE WALL SPACE AND |
| PENINSULAR, HOWEVER SOME UNITS DO NOT |
| SHOW THESE. |
| PLEASE SEE ONLY ONE UNIT INDICATES A |
| NOTE WITH RESPECT TO 12" OR MORE OF |
| SPACE REQUIRING THE ADDITIONAL GFI. |
| PLEASE SEE SOME UNITS SEEM TO CLEARLY |
| INDICATE 12" OR MORE. |
| |
| 2)NOTE: PLEASE SEE WALL RECEPT MISSING |
| IN B1C1 KIT WALL. |
| 210.52 |
| |
| 3)NOTE: PLEASE SEE MANY UNITS HAVE BEEN |
| REVISED TO LOCATE THE RECEPT FOR THE LV |
| CONTROL PANEL ABOVE DOOR AND PLANS |
| INCLUDE A NOTE FOR THIS ALSO, HOWEVER |
| PLEASE SEE SOME UNITS WERE NOT CHANGED, |
| PLEASE SEE MOST ALL UNITS STILL INDICATE |
| A RECEPT IN PANEL AND SOME UNITS EVEN |
| MOVED THE RECEPT ABOVE DOOR IN |
| LAUNDRY/UTILITY RM? PLEASE KNOW, IF |
| THESE PANELS ARE IN THE UTILITY ROOM |
| THIS MOVING OF RECEPT ABOVE DOOR IS NOT |
| REQUIRED. |
| PLEASE ALSO CLARIFY WHY THERE IS A NOTE |
| WHICH MENTIONS FOR GROUND FLR UNITS |
| ONLY?? |
| THIS WOULD BE REQUIRED IN ALL UNITS. |
| |
| 110.26.240.24 ETC |
| |
| PLEASE CALL TO GO OVER COMMENTS. |
| WIRING TO UNITS SHOULD BE LIMITED UNTIL |
| PLANS ARE CORRECTED AND CLEARED. |
| |
| A NOTICE WILL BE SENT TO THE CHEIF |
| ELECTRICAL INSPECTOR AND ELECTRICAL |
| INSPECTOR TO NOTIFY OF CORRECTIONS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |