Plan Review Notes For Permit 03050107 |
Permit Number |
03050107 |
|
Review Stop |
E |
Sequence Number |
10 |
|
Notes |
Date |
Text |
2005-10-09 00:00:00 | ************* UNSAT *********** | | | | ** PLEASE ALSO SEE REVIEW DATED 10/9/05 | | WHICH SHEETS 2.01,2.02,2.03 AND 2.04 | | HAVE BEEN VOIDED. | | THE FOLLOWING NOTES ARE FOR SHEETS 1.10, | | 1.11,1.12,2.05,4.02 | | | | | | 1)NOTE: PLEASE VERIFY CIRCUITING FOR | | ELEVATOR EQUIPMENT RMS FOR RECEPTS AND | | LTS. | | 620.23 | | PLEASE SEE 1.10, | | PLEASE ALSO INDICATE FIXTURE TYPE BEING | | BATTERY BACK UP OR PLEASE ADD BATTERY | | BACK UP FIXTURE. | | | | 2)NOTE: PLEASE VERIFY FIXTURE TYPE SHOWN | | FOR STAIRWAYS. PLEASE SEE ORIGINAL | | FIXTURE SHCEDULE ON FILE DOES NOT | | CORRELATE WITH FIX TYPE "H">? | | PLEASE ALSO VERIFY IF EVERY OTHER ONE IS | | BATTERY BACK UP. | | PLEASE KNOW THIS WAS NOT A COMMENT ON | | ORIGINAL REVIEWS, HOWEVER FIRE MARSHALS | | OFFICE AND AHJ HAS DETERMIND A BATTERY | | BACK UP FIXTURE WILL BE REQUIRED TO | | MEET MIN FT CANDLES UNDER EMERGENCY | | EXITING. 7.9.2.2, NFPA-101 2000 | | | | | | | | 4)NOTE: PLEASE VEIFY LANSCAPE LIGHTING | | FIXTURE LOCATIONS. | | 120V TO BE A MIN OF 5' FROM WATERS EDGE. | | (GFI PROTECTED) | | LV LTS, MUST BE A MIN OF 10' FROM WATERS | | EDGE. 411.4 | | | | | | PLEASE SEE REDLINED PANELS ON 2.02, | | UNITS "B-6 AND B-4 | | 110.26, 30" MIN WIDTH. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE NAY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|