2003-06-05 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 FUEL GAS |
| FBC-2001 CHAPTER 11 |
| FBC-2001 BUILDING |
| FHA-AMEND. 98 DESIGN MANUAL |
| |
| 1) SHTS A.11 & A.12, ALL PUBLIC & COMMON |
| USE TOILET ROOMS SHALL COMPLY WITH SEC. |
| 11-4.22 AND ALL SUB SECTIONS. (5' TURN- |
| ING CIRCLE, CLEAR FLOOR SPACE ECT) SEC. |
| 11-4.1.3(11). (4 TOILET ROOMS #019) |
| 2) PLEASE SUBMIT CALCULATIONS FOR MINI- |
| MUM FIXTURE FACILITIES PER TABLE 403.1 |
| FOR THE BUSINESS/COMMON AREAS GROUND |
| FLOOR LEVEL. |
| 3) PLEASE SUBMIT CALCULATIONS FOR PRIM- |
| ARY AND SECONDARY ROOF DRAINS. PLEASE |
| SHOW 1/2 AREA OF ALL VERTICAL WALLS, AND |
| SHOW AREA OF ROOFS THAT DRAIN TO ROOF |
| DRAINS FROM ABOVE, AND SHOW HOW EACH |
| AREA WILL BE AFFECTED BY WALLS AND UPPER |
| ROOFS. INDICATE HOW THE INTERNAL ROOF |
| AREAS, (WITHOUT SCUPPERS), ADD TO SCUPP- |
| ER SIZE OF ADJACENT AREAS. SEC. 1106 & |
| 1107 AND ALL SUBSECTIONS. |
| 4) SHT A.09, PLEASE INDICATE LOCATION OF |
| SECONDARY DRAINS FOR DECK AREA AROUND |
| THE POOL, AND DECK AREAS BELOW THE POOL |
| DECK AREA. |
| 5) SHT A.09 PLEASE INDICATE WHERE THE |
| AREA FOR THE COOLING TOWERS WILL DRAIN |
| AND IF 1/2 AREA OF ALL VERTICAL WALLS |
| WILL BE ADDED TO THAT AREA. |
| 6) SHTS A.51 THRU A.66, LAV ELEVATIONS |
| MAXIMUM 34" TO TOP. FHA DESIGN MANUAL |
| PAGE 7.52. |
| 7) SHTS A.51 THRU A.66, SPECIFICATION |
| "A" OR "B" SHALL BE NOTED ON PLANS FOR |
| BATHROOMS PER FHA DESIGN MANUAL PAGE |
| 7.35. |
| 8) SHTS A.51 THRU A.66, UNIT PLAN NOTES: |
| #7, SUBMIT CALCULATIONS FOR 20GA METAL |
| BACKING. SHOW COMPLIANCE WITH SECTIONS |
| 11-4.26.3, 11-4.26.3(1), 11-4.26.3(2), |
| 11-4.26.3(3), & 11-4.26.3(4). SEE AT- |
| TACHED SHEET. |
| 9) SHTS A.51 THRU A.66 SHOW OPENING |
| SIZE FOR ALL WATER CLOSETS. MINIMUM SIZE |
| 33". (18" OFF WALL WHERE LOCATED NEXT TO |
| ONE, AND MINIMUM 18" OFF FIXTURE.) |
| 10) SHT P1.01 PLEASE SHOW PIPE SIZES AND |
| CLEANOUT LOCATIONS. TABLE 710.1(1) AND |
| SECTION 708.3, 708.3.1, 708.3.3, 708.3.5 |
| 11) PLEASE SUBMIT SETS OF PLANS WITH ALL |
| SHEETS INCLUDED. THE FOLLOWING SHEETS |
| REFERENCED ON SHT P1.01 WERE NOT FOUND. |
| P3.01, P3.03, P3.05, P3.06, P3.07, P3.08 |
| P3.09, P3.10, & P3.11. |
| 12) SHT P1.01 PLEASE SHOW PIPE SIZES AND |
| C/0'S REQUIRED BY SEC 104.2.1 AND SEC |
| 708.3. |
| 13) SHT P1.07 FLOOR DRAINS REQUIRED IN |
| TOILET ROOMS FOR POOL. SEC 424.1.6.1.3 |
| 14) SHT P2.01 UNIT A-2, WASH MACHINE |
| SHALL NOT DRAIN THROUGH WET VENT FOR |
| BATHROOM FIXTURES. SEC 909.1 |
| 15) SHT P205 NO PIPING LAYOUT IN STUDIO |
| UNITS 1, 2, & 3. PLEASE CLAIRFY. |
| 16) SUBMIT A SANITARY HORIZONTAL ISOMET- |
| RIC. PLEASE SHOW ALL PIPE SIZES, SLOP OF |
| PIPE, INDICATE WHERE RISERS TIE IN, FIX- |
| TURE UNITS AS THEY ACCUMULATE, AND CLEAN |
| OUTS. SEC 104.2.1 |
| 17) SUBMIT A STORM WATER ISOMETRIC. |
| PLEASE SHOW ALL PIPE SIZES, SLOP OF PIPE |
| INDICATE WHERE RISERS TIE IN, SQUARE |
| FOOTAGE AS IT ACCUMULATES, AND TERMIN- |
| ATION. SEC 104.2.1 |
| 18) SUBMIT A WATER AND SANT. RISER DIA- |
| GRAM FOR FOR TYPICAL UNITS AND COMMON |
| AREAS. SHOW ALL PIPE SIZES, LOCATION OF |
| WATER HAMMER ARRESTORS, ECT. SEC 104.2.1 |
| 19) SHT P4.01 SEPARATE PERMIT/PLANS RE- |
| QUIRED FOR POOL/POOL EQUIPMENT ROOM. |
| PLANS TO BE REVIEWED AND STAMPED BY THE |
| HEALTH DEPT. PRIOR TO SUBMITTING TO CITY |
| FOR REVIEW. |
| 20) SHT 4.02 PLUMBING GENERAL NOTES #16, |
| WATER HAMMER ARRESTORS SHALL BE LOCATED |
| AT THE ICE MAKER, AND DISHWASHER ALSO, |
| SEC 604.9. W.H.A'S SHALL BE LOCATED NEAR |
| THE FIXTURE, IN AN "EFFECTIVE RANGE" PER |
| PDI-WH 201 AND MANUF. INSTALL. INSTRUCT. |
| NOT AT TOP OF DROP, IN THE CEILING. |
| 21) SUBMIT A CONDENSATE ISOMETRIC FOR |
| REVIEW. PLEASE SHOW ALL PIPES SIZES AND |
| INDICATE TERMINATION POINT. CONDENSATE |
| SHALL RUN SEPARATELY OUT OF BLDG. AND |
| TIE INTO STORM LINE OR CATCH BASIN. A |
| RELIEF VENT IS REQUIRED AS CONDENSATE |
| LINE EXITS THE BLDG. |
| 22) SHT P4.01 DOMESTIC BOILER SYSTEM DE- |
| TAIL, SAFETY PAN ARE REQUIRED FOR THE |
| HEATERS AND THE STORAGE TANK. SEC 504.8 |
| PLEASE SHOW HOW PAN DRAIN LINES WILL BE |
| RUN. SUPPLY RISER DIAGRAM IF REQUIRED, |
| AND INDICATE SIZE OF PIPING, & MATERIAL |
| FOR PIPING. SEC 104.2.1 |
| 23) SEPARATE GAS PERMIT REQUIRED. THE |
| FOLLOWING INFORMATION IS REQUIRED FOR |
| PERMIT. |
| A. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2001 |
| FUEL GAS CODE. |
| B. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED. |
| PER FBC-2001 FUEL GAS CODE SEC 402.3 |
| C. TYPE OF GAS, (LP OR NATURAL) SEC402.3 |
| D. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2001 FUEL GAS CODE SECS. 401.8 |
| THRU 402.5.2 AND TABLES 402(1) THRU |
| 402(34). |
| E. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES (A)(3). |
| F. SUBMIT CALCULATIONS FOR COMBUSTION |
| AIR (IF APPLICABLE) PER FBC-2001 FUEL |
| GAS CODE SECTION 304. |
| G. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| H. SUBMIT A DETAIL SHOWING THE TYPE, |
| LOCATION, SIZE AND TERMINATION OF THE |
| GAS VENTS PER FBC-2001 FUEL GAS CODE |
| SECS. 502 THRU 506. |
| I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2001 FUEL GAS CODE SEC 402.2 |
| J. CLEARLY SHOW THE LOCATION AND CAP- |
| ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| OR ASME), THE DISTANCE OF THE TANK FROM |
| THE BUILDING AND ADJACENT PROPERTY LINES |
| THE DISTANCE OF THE TANK FROM ALL SOUR- |
| CES OF IGNITION, OTHER CONTAINERS, BUILD |
| INGS, AND THE LOCATION OF ANY BUILDING |
| OPENINGS BELOW THE RELIEF VALVE OF THE |
| TANK PER NFPA 58, TABLE 3-2.2.2. |
| K. CLEARLY INDICATE ON THE PLAN IF THE |
| LP TANK IS ABOVE OR BELOW GROUND, AND |
| SHOW REQUIRED PROTECTION OF THE TANK AND |
| APPURTENANCES PER NFPA 58. IF THE TANK |
| IS BELOW GROUND THE CONTAINER SHALL BE |
| SECURILY ANCHORED PER NFPA 58 SECTION |
| 3-2.2.7(H). |
| *********WHEN RESUBMITTING PLANS******** |
| PLEASE CLEARLY INDICATE THE REVISION AND |
| REMOVE AND REPLACE ANY PAGES AS NECESS- |
| ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| THE PLANS WHEN RESUBMITTING PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN |
| BE FOUND, WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| REVIEW BY KEN STEVENS |