Plan Review Notes
Plan Review Notes For Permit 03050107
Permit Number 03050107
Review Stop P
Sequence Number 1
Notes
Date Text
2003-06-05 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 11
 FBC-2001 BUILDING
 FHA-AMEND. 98 DESIGN MANUAL
  
 1) SHTS A.11 & A.12, ALL PUBLIC & COMMON
 USE TOILET ROOMS SHALL COMPLY WITH SEC.
 11-4.22 AND ALL SUB SECTIONS. (5' TURN-
 ING CIRCLE, CLEAR FLOOR SPACE ECT) SEC.
 11-4.1.3(11). (4 TOILET ROOMS #019)
 2) PLEASE SUBMIT CALCULATIONS FOR MINI-
 MUM FIXTURE FACILITIES PER TABLE 403.1
 FOR THE BUSINESS/COMMON AREAS GROUND
 FLOOR LEVEL.
 3) PLEASE SUBMIT CALCULATIONS FOR PRIM-
 ARY AND SECONDARY ROOF DRAINS. PLEASE
 SHOW 1/2 AREA OF ALL VERTICAL WALLS, AND
 SHOW AREA OF ROOFS THAT DRAIN TO ROOF
 DRAINS FROM ABOVE, AND SHOW HOW EACH
 AREA WILL BE AFFECTED BY WALLS AND UPPER
 ROOFS. INDICATE HOW THE INTERNAL ROOF
 AREAS, (WITHOUT SCUPPERS), ADD TO SCUPP-
 ER SIZE OF ADJACENT AREAS. SEC. 1106 &
 1107 AND ALL SUBSECTIONS.
 4) SHT A.09, PLEASE INDICATE LOCATION OF
 SECONDARY DRAINS FOR DECK AREA AROUND
 THE POOL, AND DECK AREAS BELOW THE POOL
 DECK AREA.
 5) SHT A.09 PLEASE INDICATE WHERE THE
 AREA FOR THE COOLING TOWERS WILL DRAIN
 AND IF 1/2 AREA OF ALL VERTICAL WALLS
 WILL BE ADDED TO THAT AREA.
 6) SHTS A.51 THRU A.66, LAV ELEVATIONS
 MAXIMUM 34" TO TOP. FHA DESIGN MANUAL
 PAGE 7.52.
 7) SHTS A.51 THRU A.66, SPECIFICATION
 "A" OR "B" SHALL BE NOTED ON PLANS FOR
 BATHROOMS PER FHA DESIGN MANUAL PAGE
 7.35.
 8) SHTS A.51 THRU A.66, UNIT PLAN NOTES:
 #7, SUBMIT CALCULATIONS FOR 20GA METAL
 BACKING. SHOW COMPLIANCE WITH SECTIONS
 11-4.26.3, 11-4.26.3(1), 11-4.26.3(2),
 11-4.26.3(3), & 11-4.26.3(4). SEE AT-
 TACHED SHEET.
 9) SHTS A.51 THRU A.66 SHOW OPENING
 SIZE FOR ALL WATER CLOSETS. MINIMUM SIZE
 33". (18" OFF WALL WHERE LOCATED NEXT TO
 ONE, AND MINIMUM 18" OFF FIXTURE.)
 10) SHT P1.01 PLEASE SHOW PIPE SIZES AND
 CLEANOUT LOCATIONS. TABLE 710.1(1) AND
 SECTION 708.3, 708.3.1, 708.3.3, 708.3.5
 11) PLEASE SUBMIT SETS OF PLANS WITH ALL
 SHEETS INCLUDED. THE FOLLOWING SHEETS
 REFERENCED ON SHT P1.01 WERE NOT FOUND.
 P3.01, P3.03, P3.05, P3.06, P3.07, P3.08
 P3.09, P3.10, & P3.11.
 12) SHT P1.01 PLEASE SHOW PIPE SIZES AND
 C/0'S REQUIRED BY SEC 104.2.1 AND SEC
 708.3.
 13) SHT P1.07 FLOOR DRAINS REQUIRED IN
 TOILET ROOMS FOR POOL. SEC 424.1.6.1.3
 14) SHT P2.01 UNIT A-2, WASH MACHINE
 SHALL NOT DRAIN THROUGH WET VENT FOR
 BATHROOM FIXTURES. SEC 909.1
 15) SHT P205 NO PIPING LAYOUT IN STUDIO
 UNITS 1, 2, & 3. PLEASE CLAIRFY.
 16) SUBMIT A SANITARY HORIZONTAL ISOMET-
 RIC. PLEASE SHOW ALL PIPE SIZES, SLOP OF
 PIPE, INDICATE WHERE RISERS TIE IN, FIX-
 TURE UNITS AS THEY ACCUMULATE, AND CLEAN
 OUTS. SEC 104.2.1
 17) SUBMIT A STORM WATER ISOMETRIC.
 PLEASE SHOW ALL PIPE SIZES, SLOP OF PIPE
 INDICATE WHERE RISERS TIE IN, SQUARE
 FOOTAGE AS IT ACCUMULATES, AND TERMIN-
 ATION. SEC 104.2.1
 18) SUBMIT A WATER AND SANT. RISER DIA-
 GRAM FOR FOR TYPICAL UNITS AND COMMON
 AREAS. SHOW ALL PIPE SIZES, LOCATION OF
 WATER HAMMER ARRESTORS, ECT. SEC 104.2.1
 19) SHT P4.01 SEPARATE PERMIT/PLANS RE-
 QUIRED FOR POOL/POOL EQUIPMENT ROOM.
 PLANS TO BE REVIEWED AND STAMPED BY THE
 HEALTH DEPT. PRIOR TO SUBMITTING TO CITY
 FOR REVIEW.
 20) SHT 4.02 PLUMBING GENERAL NOTES #16,
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 AT THE ICE MAKER, AND DISHWASHER ALSO,
 SEC 604.9. W.H.A'S SHALL BE LOCATED NEAR
 THE FIXTURE, IN AN "EFFECTIVE RANGE" PER
 PDI-WH 201 AND MANUF. INSTALL. INSTRUCT.
 NOT AT TOP OF DROP, IN THE CEILING.
 21) SUBMIT A CONDENSATE ISOMETRIC FOR
 REVIEW. PLEASE SHOW ALL PIPES SIZES AND
 INDICATE TERMINATION POINT. CONDENSATE
 SHALL RUN SEPARATELY OUT OF BLDG. AND
 TIE INTO STORM LINE OR CATCH BASIN. A
 RELIEF VENT IS REQUIRED AS CONDENSATE
 LINE EXITS THE BLDG.
 22) SHT P4.01 DOMESTIC BOILER SYSTEM DE-
 TAIL, SAFETY PAN ARE REQUIRED FOR THE
 HEATERS AND THE STORAGE TANK. SEC 504.8
 PLEASE SHOW HOW PAN DRAIN LINES WILL BE
 RUN. SUPPLY RISER DIAGRAM IF REQUIRED,
 AND INDICATE SIZE OF PIPING, & MATERIAL
 FOR PIPING. SEC 104.2.1
 23) SEPARATE GAS PERMIT REQUIRED. THE
 FOLLOWING INFORMATION IS REQUIRED FOR
 PERMIT.
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 PER FBC-2001 FUEL GAS CODE SEC 402.3
 C. TYPE OF GAS, (LP OR NATURAL) SEC402.3
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 F. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304.
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 H. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2001 FUEL GAS CODE
 SECS. 502 THRU 506.
 I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 J. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 K. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 *********WHEN RESUBMITTING PLANS********
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692