Plan Review Notes
Plan Review Notes For Permit 03050107
Permit Number 03050107
Review Stop M
Sequence Number 1
Notes
Date Text
2003-05-24 00:00:00DENIED:MECHANICAL PERMIT 03050109
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW:
  
 1.PLAN SHEET M1.03 DUCTS PENETRATING
 WALLS WITH 1 HR RATING AT THE LOCATION
 OF THE MAIL RM, STORAGE RM & PUBLIC
 BATHROOMS.PLEASE INDICATE LOCATION OF
 THE FIRE DAMPERS.
  
 2.PLAN SHEET 2.01, LINT TRAP WITH FAN
 BOOSTER INDICATED ON PLAN.PLAN SHEET
 M6.21 INDICATES A SUB-DUCT.PLEASE
 CLARIFY WHICH WILL BE USED. PLEASE NOTE,
 SHOULD THE SUBDUCT METHOD BE USED CLEAN-
 OUTS & SPRINKLER SYSTEM REQUIRED IN THE
 2 HR SHAFT.SHOULD THE BOOSTER FAN
 METHOD BE USED PLEASE PROVIDE DETAIL
 OF "LINT TRAP".BOOSTER FAN MUST HAVE
 SOME TYPE OF NOTIFICATION IF IT FAILS.
  
 4.PLEASE PROVIDE ELEVATION AT WHICH
 THE MUFFLER EXHAUST FROM THE GENERATOR
 WILL TERMINATE.
  
 5.PLEASE PROVIDE OUTSIDE AIR CALCS
 FOR ALL AREAS COMMON AS WELL AS
 RESIDENTIAL.RESIDENTIAL CAN BE BY
 NATURAL MEANS AS PER 2001 FBC(M) 402.2
 OR MECHANICAL TABLE 403.3.
  
 6.A MINIMUM OF 4" CLEARANCE REQUIRED
 AROUND THE VERTICAL AHU AS PER 2001 FBC
 (M) 603.1.3.
  
 7.AS PER 2001 FBC 411.4.2, THE
 MECHANICAL SYSTEM SHALL BE CAPABLE OF
 PROVIDING AT LEAST 6 AIR CHANGES PER
 HOUR FOR EACH LEVEL.
  
 8.PLEASE PROVIDE CALCULATIONS FOR
 GARAGE, BOILER ROOM AND ALL EQUIPMENT
 AND MECHANICAL ROOMS.
  
 9.PLEASE NOTE, MASTER BATHROOMS WHERE
 THE TOILET ROOM IS SEPARATE FROM THE
 BATHING AREA, A FAN WILL BE REQUIRED
 IN THE SHOWER AREA AS WELL AS THE TOILET
 AREA AS PER 2001 FBC(M) 402.3.1.