2003-05-24 00:00:00 | DENIED:MECHANICAL PERMIT 03050109 |
| PLEASE PROVIDE THE FOLLOWING INFORMATION |
| FOR REVIEW: |
| |
| 1.PLAN SHEET M1.03 DUCTS PENETRATING |
| WALLS WITH 1 HR RATING AT THE LOCATION |
| OF THE MAIL RM, STORAGE RM & PUBLIC |
| BATHROOMS.PLEASE INDICATE LOCATION OF |
| THE FIRE DAMPERS. |
| |
| 2.PLAN SHEET 2.01, LINT TRAP WITH FAN |
| BOOSTER INDICATED ON PLAN.PLAN SHEET |
| M6.21 INDICATES A SUB-DUCT.PLEASE |
| CLARIFY WHICH WILL BE USED. PLEASE NOTE, |
| SHOULD THE SUBDUCT METHOD BE USED CLEAN- |
| OUTS & SPRINKLER SYSTEM REQUIRED IN THE |
| 2 HR SHAFT.SHOULD THE BOOSTER FAN |
| METHOD BE USED PLEASE PROVIDE DETAIL |
| OF "LINT TRAP".BOOSTER FAN MUST HAVE |
| SOME TYPE OF NOTIFICATION IF IT FAILS. |
| |
| 4.PLEASE PROVIDE ELEVATION AT WHICH |
| THE MUFFLER EXHAUST FROM THE GENERATOR |
| WILL TERMINATE. |
| |
| 5.PLEASE PROVIDE OUTSIDE AIR CALCS |
| FOR ALL AREAS COMMON AS WELL AS |
| RESIDENTIAL.RESIDENTIAL CAN BE BY |
| NATURAL MEANS AS PER 2001 FBC(M) 402.2 |
| OR MECHANICAL TABLE 403.3. |
| |
| 6.A MINIMUM OF 4" CLEARANCE REQUIRED |
| AROUND THE VERTICAL AHU AS PER 2001 FBC |
| (M) 603.1.3. |
| |
| 7.AS PER 2001 FBC 411.4.2, THE |
| MECHANICAL SYSTEM SHALL BE CAPABLE OF |
| PROVIDING AT LEAST 6 AIR CHANGES PER |
| HOUR FOR EACH LEVEL. |
| |
| 8.PLEASE PROVIDE CALCULATIONS FOR |
| GARAGE, BOILER ROOM AND ALL EQUIPMENT |
| AND MECHANICAL ROOMS. |
| |
| 9.PLEASE NOTE, MASTER BATHROOMS WHERE |
| THE TOILET ROOM IS SEPARATE FROM THE |
| BATHING AREA, A FAN WILL BE REQUIRED |
| IN THE SHOWER AREA AS WELL AS THE TOILET |
| AREA AS PER 2001 FBC(M) 402.3.1. |