Date |
Text |
2003-06-06 00:00:00 | 1) WET FIRE HYDRANTS ARE REQUIRED PRIOR |
| TO, DURING, AND AFTER CONSTRUCTION. |
| |
| 2) TEMPORARY STANDPIPES ARE REQUIRED |
| WHEN CONSTRUCTION REACHES THREE STORIES |
| OR THIRTY FEET IN HEIGHT. |
| |
| 3) EXIT STAIRS ARE REQUIRED DURING |
| CONSTRUCTION. |
| |
| 4) ALL CONSTRUCTION WORK IS TO COMPLY |
| WITH NFPA 241. |
| |
| 5) DOOR AT STAIR # 2 SWINGS OUTWARD |
| INSTEAD OF INWARD. |
| |
| 6) BOTH STAIRS ON L.S.1 ARE LABELED |
| STAIR # 2. |
| |
| 7) PLEASE INDICATE ALL DEVICES AND |
| EQUIPMENT THAT WILL BE CONTAINED |
| IN THE FIRE COMMAND ROOM. PLEASE SEE |
| FBC 412.4.1. |
| |
| 8) PLEASE PROVIDE MORE DETAILS ON |
| SECRUITY LOCKS PLANNED FOR EXIT |
| DOORS. |
| |
| 9) ALL STAIRS AND RAMPS ARE REQUIRED |
| TO HAVE HANDRAILS ON BOTH SIDES. |
| |
| 10) STAIR # 2 AT GROUND LEVEL SWINGS |
| INWARD INSTEAD OF OUTWARD. |
| |
| 11) PLEASE PROVIDE PRESCRIPTIVE STRENGTH |
| REQUIREMENTS FOR ALUMINUM AND RAILINGS. |
| |
| 12) LOCATION MAY BE LOCATED IN THE |
| CITY FIRE LIMITS. CERTAIN RESTRICTIONS |
| MAY APPLY. |
| |
| 13) BUILDING ADDRESS REQUIRED ON PROPER |
| ELEVATION. |
| |
| 14) A TWO HOUR FIRE SEPARATION IS |
| REQUIRED BETWEEN THE PARKING GARAGE |
| AND THE BUILDING. |
| |
| 15) PROVIDE INFORMATION ON INSULATION |
| PLANNED FOR THE TRASH CHUTE. |
| |
| 16) WHY ARE STAIR # 2 AND STAIR # 3 |
| POSITIONED SO CLOSE TOGETHER. |
| |
| 17) INDICATE TYPE OF CONSTRUCTION. |
| |
| 18) INDICATE CODE DATA. |
| |
| 19) VICINITY SPELLED WRONG ON PLANS. |
| |
| 20) WHY IS THE FIRE PUMP ROOM LOCATED |
| ON PARKING LEVEL B-2. |
| |
| 21) NO EMERGENCY LIGHT NOTED IN FIRE |
| PUMP ROOM. |
| |
| 22) ELECTRICAL CONDUITS NOTED IN STAIR |
| # 2. THE STAIR CANNOT BE USED AS A CHASE |
| FOR EQUIPMENT. |
| |
| 23) WHY IS THERE NO EXIT SIGN NEAR |
| EXTERIOR DOORS NEAR THE MAIL ROOM. |
| |
| 24) SMOKE DETECTOR MISSING FROM BEDROOM |
| UNIT B-4. |
| |
| 25) SMOKE DETECTOR MISSING FROM BEDROOM |
| UNIT B-3. |
| |
| 26) FOUR FDC'S SHOWN. THIS OFFICE ONLY |
| REQUIRES TWO OF THEM. |
| |
| 27) FSP # 2 IS LOCATED IN THE ELEVATOR |
| LOBBY. IT SHOULD BE RELOCATED FROM |
| THIS LOCALE. |
| |
| 28) CIVIL DRAWINGS SHOW A 6" FIRE LINE. |
| THIS LINE IS TWO SMALL. |
| |
| 29) TAMPER SWITCHES REQUIRED ON FIRE |
| LINE BACKFLOW DEVICE. |
| |
| 30) PLEASE CLEARLY ILLUSTRATE EXISTING |
| FIRE HYDRANT LOCATIONS ON SITE PLAN. |
| |
| MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| 835-2910 |
| 659-8096,EXT.8497 |