Plan Review Notes For Permit 03050107 |
Permit Number |
03050107 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-05-13 00:00:00 | *********** UNSAT ****************** | | | | PLEASE COMPLETE PLANS FOR SUFFICIENT | | REVIEW. | | | | PLANS MISSING CIRCUIT #`S,MISSING ITEMS | | LOADS/WIRE/OCP ON PANEL SCHEDULES. | | | | PLEASE SUBMIT MORE INFORMATION FOR FIRE | | PUMP/CONTROLLER ETC. 695-4B,,,,, | | LOCATION OF DISC MEANS, SIGNAGE NOTES, | | ETC. 230-2/-230-72 | | | | PLEASE NOTE, FEEDER SCHEDULE IS SHOWN | | ON RISER, HOWEVER, (#) NOTES ARE NOT | | COMPLETED ON RISER? | | | | PLEASE SEE MISSING CIRCUITING FOR EF`S | | ETC. | | | | PLEASE SEE A COUPLE OF SD`S MISSING. | | TO BE INSIDE AND OUTSIDE ALL SLEEPING | | ROOMS. NFPA-72 8-1.4.2 | | | | PLEASE CLARIFY HOW ALL UNITS SHOW SAME | | LOAD AND UNITS ARE DIFFERENT SIZES?? | | | | | | | | | | PLEASE NOTE, MOST OF THE ABOVE PERTAIN | | TO ART 215-5 | | PLEASE ALSO NOTE, ONCE PLANS ARE | | COMPLETED, THERE MAY BE OTHER COMMENTS | | TO FOLLOW. | | PLEASE SUBMIT ALL OF THE ABOVE INFORMAT- | | -ION FOR REVIEW. PLEASE TAKE OUT ALL OLD | | /VOIDED SHEETS AND SUBMIT COMPLETE SETS | | FOR REVIEW. | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|