2003-06-19 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 805 6716 |
| E-MAIL: [email protected] |
| |
| FBC = FLORIDA BUILDING CODE 2001 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| |
| 1) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, THE PLANS STAMPED BY THEM |
| AND A COPY OF THE RECEIPT SUBMITTED TO |
| THE CITY OF WEST PALM BEACH CONSTRUCTION |
| SERVICES DEPARTMENT BEFORE A BUILDING |
| PERMIT CAN BE ISSUED. |
| |
| 3) THE BUILDING STRUCTURE TRANSGRESSES |
| LEGAL BOUNDARY LINES BETWEEN THE LOTS |
| WHICH COMBINE TO FORM 'THE SITE'. SUBMIT |
| A COPY OF THE UNITIVE TITLE DOCUMENT SO |
| THAT FBC TABLE 600 BOUNDARY LINE |
| REQUIREMENTS MAY BE DEEMED NOT |
| APPLICABLE. |
| |
| 4) CONDOMINIUM V APARTMENTS.IF THE |
| DWELLING UNITS ARE TO BE SOLD AS |
| CONDOMINIUMS, NO CERTIFICATE OF |
| OCCUPANCY CAN BE ISSUED UNTIL A |
| 'DECLARATION OF CONDOMINIUM' HAS BEEN |
| SUBMITTED TO THE STATE FOR APPROVAL, AND |
| THEN RECORDED WITH THE CLERK OF THE |
| COUNTY COURT.A RECORDED COPY SHALL BE |
| SUBMITTED TO THE CITY FOR RECORDS, |
| ADDRESSING PURPOSES, AND NOTIFICATION OF |
| PALM BEACH COUNTY PROPERTY APPRAISER'S |
| OFFICE. |
| |
| 5) FBC* 104.4.5 SPECIAL FOUNDATION |
| PERMIT. THE BUILDING OFFICIAL MAY, AT |
| HIS DISCRETION, ISSUE A SPECIAL PERMIT |
| FOR THE FOUNDATION ONLY, UPON WRITTEN |
| REQUEST BY THE OWNER AND CONTRACTOR. THE |
| HOLDER OF SUCH SPECIAL PERMIT IS PROCEED |
| ING AT HIS/HER OWN RISK AND WITHOUT |
| ASSURANCE THAT A PERMIT FOR THE |
| REMAINDER OF THE WORK WILL BE GRANTED |
| AND THAT CORRECTIONS WILL NOT BE |
| REQUIRED IN ORDER TO MEET THE PROVISIONS |
| OF THE TECHNICAL CODES. |
| |
| 6) FBC* 105.13.1SPECIAL INSPECTOR.A |
| STRUCTURAL INSPECTION PLAN MUST BE |
| SUBMITTED PRIOR TO THE ISSUANCE OF A |
| BUILDING PERMIT FOR THE CONSTRUCTION OF |
| A THRESHOLD BUILDING.A THRESHOLD |
| BUILDING IS ANY BUILDING WHICH IS |
| GREATER THAN THREE STORIES OR 50 FEET IN |
| HEIGHT, OR WHICH HAS AN ASSEMBLY |
| OCCUPANCY WITH 5,000 SQFT AREA AND |
| GREATER THAN 500 OCCUPANTS.THREE |
| COPIES OF THE PLANS AND OTHER DOCUMENTS |
| WILL BE REQUIRED FOR PERMITTING. |
| |
| 7) A SEPARATE PERMIT APPLICATION WILL BE |
| REQUIRED FOR THE SWIMMING POOL. |
| |
| 8) FBC* 1804.2.2SHEET S-0, FOUNDATIONS |
| SUBMIT COPIES OF GFA INTERNATIONAL SOIL |
| REPORT AS REFERENCED IN THE NOTES. |
| |
| 9) FBC 13-103.1.1.1 AND 103.1.2SHEET 2 |
| OF THE SUBMITTED ENERGY CODE COMPLIANCE |
| FORMS SHALL BE SIGNED BY THE OWNER (OR |
| THE PROJECT ARCHITECT, OR OTHER |
| AUTHORIZED AGENT DESIGNATED BY THE |
| OWNER) TO CERTIFY COMPLIANCE WITH THE |
| CODE.ALSO THE ARCHITECT'S NAME AND |
| REGISTRATIONNUMBER SHALL BE ADDED |
| ABOVE THAT OF THE MEP ENGINEER. |
| |
| 10) FBC* F102.2.4FIRE DISTRICT.THE |
| ROOF COVERING SHALL CONFORM TO CLASS A |
| AND B AS DEFINED IN FBC 1505.AMEND THE |
| PLANS TO DEMONSTRATE COMPLIANCE. |
| |
| 11) SUBMIT PRODUCT APPROVALS FOR THE |
| WINDOWS, STOREFRONTS, EXTERIOR DOORS AND |
| ROOFING PRODUCTS. |
| |
| 12) FBC* 104.2.1.2BUILDING DATA.THE |
| BUILDING AREAS, CONSTRUCTION TYPE AND |
| OTHER CODE/BUILDING DESIGN CRITERIA |
| SHALL BE STATED ON THE PLANS.(NOTE: TO |
| COMPLY WITH TABLE 500 FOR A SPRINKLERED, |
| TWO STOREY, ENCLOSED PARKING GARAGE |
| >60,000 SQ FT, TYPE I CONSTRUCTION IS |
| REQUIRED) |
| |
| 13) FBC 1606.1.7WIND LOAD.THE PLANS |
| SHALL STATE THE BASIC WIND SPEED, WIND |
| IMPORTANCE FACTOR, WIND EXPOSURE |
| CATEGORY, INTERNAL PRESSURE COEFFICIENT, |
| AND EXTERIOR COMPONENT AND CLADDING |
| DESIGN WIND PRESSURES. |
| |
| 14) FBC* 104.2.1SHEETS A.22 & A.23. |
| THE SOUTH AND NORTH ELEVATIONS DO NOT |
| APPEAR TO REPRESENT FENESTRATION AND |
| OTHER ARCHITECTURAL FEATURES SHOWN ON |
| THE PLANS.FOR EXAMPLE, THE NUMBER OF |
| WINDOWS ON THE ELEVATIONS IS DIFFERENT |
| TO THE PLANS.PLEASE AMEND/CLARIFY. |
| |
| 15) FBC* 104.2.1SHEET A.02PARKING |
| LEVELS B-1 & B-2. STAIR 4 IS INCORRECTLY |
| LABELLED AS 'STAIR 2'.AMEND THE PLAN. |
| |
| 16) FBC* 104.2.1SHEET A.35.THE STAIR |
| 2 PLANS ARE MIS-LABELLED AS 'STAIR 3'. |
| |
| 17) FBC 705.1.2SHEETS LS.1 TO LS.4 |
| AMEND THE LEGEND TO INDICATE THE |
| REQUIRED ONE HOUR RATING FOR THE |
| ELEVATOR LOBBIES AND TWO HOUR RATING FOR |
| THE WALL TYPE SHOWN AROUND THE STAIR |
| SHAFTS, TRASH CHUTE ETC. |
| |
| 18) FBC 412.6SHEET A.02, PARKING LEVEL |
| PLAN.AMEND THE PLAN TO CLARIFY THE |
| THE PURPOSE, CONSTRUCTION AND |
| FIRE-RATING OF THE WALL/DOOR THAT HAS |
| BEEN PROVIDED, IN FRONT OF ELEVATORS |
| 1 TO 3, IN LIEU OF ELEVATOR LOBBIES. |
| |
| 19) FBC 411.4.2SHEET A.02, ENCLOSED |
| PARKING GARAGES, MECHANICAL VENTILATION |
| AND SMOKE EVACUATION.THE REFERENCE TO |
| 'STACKED FANS' IS NOTED.ANNOTATE THE |
| PLANS TO CLARIFY THE PROVISION OF |
| DEDICATED MECHANICAL VENTILATION AT EACH |
| LEVEL OF THE PARKING GARAGE. |
| |
| 20) FBC 411.2.6SHEETS A.02 & A.48THE |
| PUMP ROOM SHALL BE SEPARATED FROM THE |
| PARKING GARAGE BY 1-HOUR FIRE RESISTANT |
| CONSTRUCTION. |
| |
| 21) FBC 1012.1.2SHEET A.04, GROUND |
| LEVEL PLAN.THE STAIR #2 DOOR SHALL |
| OPEN IN THE DIRECTION OF EGRESS.AMEND |
| THE PLAN. |
| |
| 22) FBC 1010.3SHEET A.04, GROUND LEVEL |
| PLAN, MAIN LOBBY.THE EXIT DISCHARGE |
| FROM STAIR #2 IS THROUGH THE MAIN LOBBY |
| WHICH MUST THEREFOR SATISFY THE |
| REQUIREMENTS OF THE EXCEPTION UNDER |
| FBC 1010.3.RECOMMENDATION: PROVIDE TWO |
| 1-1/2 HOUR CROSS-CORRIDOR DOORS, ONE |
| BETWEEN THE STUDIO 'S2' KITCHEN WALL AND |
| THE UNIT 'C1' POWDER ROOM WALL OPPOSITE |
| AND ONE BETWEEN THE RECEPTION |
| ADMINISTRATION AREA AND ELEVATOR #2. |
| THIS WOULD LIMIT THE SIZE OF THE EXIT |
| DISCHARGE AREA AND SO LIMIT THE |
| POTENTIAL RISK OF FIRE/SMOKE INGRESS |
| INTO THE EXIT DISCHARGE. |
| |
| 23) FBC TABLES 704.2.4 & 705.1.2SHEETS |
| A.04 & A.48. THE RECEPTION ADMINISTRAT'N |
| OFFICE, CONFERENCE RM, BUSINESS CENTER, |
| FIRE COMMAND CENTER, CLUB ROOM AND |
| HEALTH CLUB ARE IN THE EXIT ACCESS |
| CORRIDOR AND SHALL BE AT LEAST 30-MINUTE |
| FIRE-RATED WITH 20-MINUTE FIRE-RATED |
| DOORS (DOOR #'S 16, 17, 18, 20, 26 & 27) |
| |
| 24) SHEET A.04 & A.48THE CA/TV ROOM |
| DOOR IS SHOWN AS DOOR REF #30.SHOULD |
| THIS BE #38 (SEE DOOR SCHEDULE)? |
| |
| 25) FBC TABLE 704.1SHEET A.13 & A.14 |
| GROUND LEVEL (PARTIAL) PLAN.THE WALL |
| BETWEEN THE CONFERENCE ROOM AND |
| UNIT 'A6' IS SHOWN AS TYPE 13, WHICH IS |
| NOT A FIRE-RATED WALL TYPE.AMEND THE |
| PLAN TO SHOW A MINIMUM OF 1-HOUR FIRE- |
| RATING FOR THIS WALL. |
| |
| 26) FBC 11-4.13.6SHEET A.11, GROUND |
| LEVEL PLANS, MANEUVERING CLEARANCES AT |
| DOORS.THE MEN'S AND WOMEN'S TOILET |
| ROOM DOORS FROM CORRIDOR 027 SHALL HAVE |
| A MINIMUM OF 18" CLEARANCE BETWEEN THE |
| LEADING EDGE OF THE DOOR AND THE |
| ADJACENT PERPENDICULAR WALL ON THE PULL |
| SIDE OF THE DOOR.AMEND THE PLANS |
| |
| 27) FBC 11-4.13.6 MANEUVERING CLEARANCES |
| AT DOORS.THE CONFERENCE ROOM LOBBY, |
| BUSINESS CENTER, CLUB ROOM AND HEALTH |
| CLUB ENTRANCE DOORS FROM CORRIDOR 027 |
| (SHEET A.13, GROUND LEVEL) SHALL HAVE A |
| MINIMUM 12" CLEARANCE BETWEEN THE |
| LEADING EDGE OF THE DOOR AND THE |
| ADJACENT RECESSED WALL ON THE PUSH SIDE |
| OF THE DOOR IF IT HAS BOTH A CLOSER AND |
| A LATCH.AMEND THE PLANS.THIS COMMENT |
| ALSO APPLIES TO ALL RESIDENTIAL UNIT |
| RECESSED ENTRANCE DOORS (FOR EXAMPLE |
| GROUND FLOOR UNITS 'A2' AND 'A4'), IF |
| THEY HAVE BOTH A CLOSER AND A LATCH. |
| |
| 28) FBC 1012.1.4SHEET A.36THE STOREY |
| EXIT DOORS INTO STAIR #3 AT EACH LEVEL |
| SHALL LEAVE UNOBSTRUCTED AT LEAST ONE |
| HALF OF THE REQUIRED WIDTH OF THE |
| LANDING.AMEND THE PLAN. |
| |
| 29) FBC 1007.5.5SHEET A.34, STAIR #1 |
| PLANS.THE HANDRAILS SHALL EXTEND AT |
| LEAST 12" HORIZONTALLY BEYOND THE TOP |
| RISER OF EACH FLIGHT.THE STAIR #1 |
| PLANS SHOW ONLY 11", AMEND THE PLANS. |
| |
| 30) FBC 1015.4GUARDRAIL STRENGTH.THE |
| PLANS SHALL BE AMENDED TO STATE THE |
| STRENGTH REQUIREMENTS SET OUT IN |
| FBC 1608.2. |
| |
| 31) FBC 1015.3SHEET A.34, A.35 & A.36 |
| THE PLANS SHALL STATE THE REQUIREMENT |
| FOR THE BOTTOM RAIL OF THE GUARDING TO |
| BE POSITIONED SUCH THAT A 6" DIAMETER |
| SPHERE CANNOT PASS THROUGH THE |
| TRIANGULAR OPENING THAT IT FORMS WITH |
| THE TREAD AND THE RISER. |
| |
| 32) FBC 1015.3SHEET A.44, DETAIL J. |
| THE GUARDRAIL DETAIL SHALL MAKE |
| REFERENCE TO THE REQUIREMENTS FOR THE |
| SPACING BETWEEN PICKETS TO REJECT THE |
| PASSAGE OF A 4" DIAMETER SPHERE, AND FOR |
| THE BOTTOM RAIL POSITIONING TO REJECT |
| THE PASSAGE OF A 2" DIAMETER SPHERE. |
| |
| 33) FBC* 104.2.1SHEET A.44, DETAIL M, |
| SLIDING GLASS DOOR THRESHOLD. THE DETAIL |
| SHALL MAKE REFERENCE TO A PRODUCT |
| APPROVAL FOR ANCHOR SPECIFICATION. |
| |
| 34) FBC 411.2.3AUTOMOBILE PARKING |
| GARAGE, GUARDING.THE INTERIOR PARKING |
| GARAGE WALLS ADJACENT THE VEHICLE RAMP, |
| STAIR 2 AND 4, AND THE FRONT WALL OF THE |
| ELEVATOR SHAFTS SHALL BE DESIGNED TO |
| WITHSTAND IMPACT LOADING IN ACCORDANCE |
| WITH FBC 1608.2.3.PROVIDE STRUCTURAL |
| DETAILS OF THE WALLS AT THESE LOCATIONS. |
| |
| 35) FBC 2405.2THE SHOWER ENCLOSURE |
| GLAZING IS IN A 'HAZARDOUS LOCATION' AND |
| REQUIRED TO BE SAFETY GLASS SATISFYING |
| THE REQUIREMENTS OF THE CONSUMER PRODUCT |
| SAFETY COMMISSION 16, CODE OF FEDERAL |
| REGULATIONS, PART 1201 (CPSC 16-CFR, |
| PART 1201).AMEND THE PLANS TO |
| DEMONSTRATE COMPLIANCE. |
| |
| 36) FBC* 104.2.1THE SUBMITTED |
| STRUCTURAL PLANS DO NOT PROVIDE A |
| COMPLETE DESCRIPTION OF THE STRUCTURE. |
| SUBMIT FURTHER STRUCTURAL DETAILS. |
| |
| 37) FBC 11-4.16.4SHEET A.67, GRAB BARS |
| AT WATER CLOSETS.THE SIDE GRAB BAR |
| SHALL BE A MINIMUM OF 3'6" LONG SUCH |
| THAT IT EXTENDS TO NO LESS THAN 54" FROM |
| THE REAR WALL (REF: FIGURE 29(B)).THE |
| DIMENSIONS ARE SHOWN INCORRECTLY ON ONE |
| OF THE TWO DETAILS.AMEND THE PLANS. |
| |
| 38) FBC 11-4.16.2SHEET A.67, CLEAR |
| FLOOR SPACE AT WATER CLOSETS.THE |
| LAVATORY SHALL BE AT LEAST 18" FROM THE |
| CENTER-LINE OF THE W.C. AND 36" FROM THE |
| SIDE WALL (REF: FIGURE 28).AMEND THE |
| PLANS. |
| |
| 39) FBC 11-4.15.2SHEET A.67, SPOUT |
| HEIGHT AND KNEE CLEARANCE.THE HEIGHT |
| FROM FINISHED FLOOR TO THE SPOUT (NOT |
| THE TOP OF THE FOUNTAIN TRAY) SHALL BE A |
| MAXIMUM OF 36" (REF: FIGURE 27(A)).THE |
| DIMENSIONS ARE SHOWN INCORRECTLY ON ONE |
| OF THE TWO DETAILS.AMEND THE PLANS. |
| |
| 40) IF NEW PLAN SHEETS ARE REQUIRED, IN |
| ORDER TO ADDRESS THE ABOVE COMMENTS, THE |
| OLD SHEETS SHALL BE REMOVED AND THE NEW |
| SHEETS INSERTED.ONE COPY OF EACH OLD |
| SHEET SHALL BE INCLUDED WITH THE |
| RESUBMITTAL FOR COMPARISON OF REVISIONS. |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |