Plan Review Notes
Plan Review Notes For Permit 03050107
Permit Number 03050107
Review Stop B
Sequence Number 1
Notes
Date Text
2003-06-19 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, THE PLANS STAMPED BY THEM
 AND A COPY OF THE RECEIPT SUBMITTED TO
 THE CITY OF WEST PALM BEACH CONSTRUCTION
 SERVICES DEPARTMENT BEFORE A BUILDING
 PERMIT CAN BE ISSUED.
  
 3) THE BUILDING STRUCTURE TRANSGRESSES
 LEGAL BOUNDARY LINES BETWEEN THE LOTS
 WHICH COMBINE TO FORM 'THE SITE'. SUBMIT
 A COPY OF THE UNITIVE TITLE DOCUMENT SO
 THAT FBC TABLE 600 BOUNDARY LINE
 REQUIREMENTS MAY BE DEEMED NOT
 APPLICABLE.
  
 4) CONDOMINIUM V APARTMENTS.IF THE
 DWELLING UNITS ARE TO BE SOLD AS
 CONDOMINIUMS, NO CERTIFICATE OF
 OCCUPANCY CAN BE ISSUED UNTIL A
 'DECLARATION OF CONDOMINIUM' HAS BEEN
 SUBMITTED TO THE STATE FOR APPROVAL, AND
 THEN RECORDED WITH THE CLERK OF THE
 COUNTY COURT.A RECORDED COPY SHALL BE
 SUBMITTED TO THE CITY FOR RECORDS,
 ADDRESSING PURPOSES, AND NOTIFICATION OF
 PALM BEACH COUNTY PROPERTY APPRAISER'S
 OFFICE.
  
 5) FBC* 104.4.5 SPECIAL FOUNDATION
 PERMIT. THE BUILDING OFFICIAL MAY, AT
 HIS DISCRETION, ISSUE A SPECIAL PERMIT
 FOR THE FOUNDATION ONLY, UPON WRITTEN
 REQUEST BY THE OWNER AND CONTRACTOR. THE
 HOLDER OF SUCH SPECIAL PERMIT IS PROCEED
 ING AT HIS/HER OWN RISK AND WITHOUT
 ASSURANCE THAT A PERMIT FOR THE
 REMAINDER OF THE WORK WILL BE GRANTED
 AND THAT CORRECTIONS WILL NOT BE
 REQUIRED IN ORDER TO MEET THE PROVISIONS
 OF THE TECHNICAL CODES.
  
 6) FBC* 105.13.1SPECIAL INSPECTOR.A
 STRUCTURAL INSPECTION PLAN MUST BE
 SUBMITTED PRIOR TO THE ISSUANCE OF A
 BUILDING PERMIT FOR THE CONSTRUCTION OF
 A THRESHOLD BUILDING.A THRESHOLD
 BUILDING IS ANY BUILDING WHICH IS
 GREATER THAN THREE STORIES OR 50 FEET IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY
 OCCUPANCY WITH 5,000 SQFT AREA AND
 GREATER THAN 500 OCCUPANTS.THREE
 COPIES OF THE PLANS AND OTHER DOCUMENTS
 WILL BE REQUIRED FOR PERMITTING.
  
 7) A SEPARATE PERMIT APPLICATION WILL BE
 REQUIRED FOR THE SWIMMING POOL.
  
 8) FBC* 1804.2.2SHEET S-0, FOUNDATIONS
 SUBMIT COPIES OF GFA INTERNATIONAL SOIL
 REPORT AS REFERENCED IN THE NOTES.
  
 9) FBC 13-103.1.1.1 AND 103.1.2SHEET 2
 OF THE SUBMITTED ENERGY CODE COMPLIANCE
 FORMS SHALL BE SIGNED BY THE OWNER (OR
 THE PROJECT ARCHITECT, OR OTHER
 AUTHORIZED AGENT DESIGNATED BY THE
 OWNER) TO CERTIFY COMPLIANCE WITH THE
 CODE.ALSO THE ARCHITECT'S NAME AND
 REGISTRATIONNUMBER SHALL BE ADDED
 ABOVE THAT OF THE MEP ENGINEER.
  
 10) FBC* F102.2.4FIRE DISTRICT.THE
 ROOF COVERING SHALL CONFORM TO CLASS A
 AND B AS DEFINED IN FBC 1505.AMEND THE
 PLANS TO DEMONSTRATE COMPLIANCE.
  
 11) SUBMIT PRODUCT APPROVALS FOR THE
 WINDOWS, STOREFRONTS, EXTERIOR DOORS AND
 ROOFING PRODUCTS.
  
 12) FBC* 104.2.1.2BUILDING DATA.THE
 BUILDING AREAS, CONSTRUCTION TYPE AND
 OTHER CODE/BUILDING DESIGN CRITERIA
 SHALL BE STATED ON THE PLANS.(NOTE: TO
 COMPLY WITH TABLE 500 FOR A SPRINKLERED,
 TWO STOREY, ENCLOSED PARKING GARAGE
 >60,000 SQ FT, TYPE I CONSTRUCTION IS
 REQUIRED)
  
 13) FBC 1606.1.7WIND LOAD.THE PLANS
 SHALL STATE THE BASIC WIND SPEED, WIND
 IMPORTANCE FACTOR, WIND EXPOSURE
 CATEGORY, INTERNAL PRESSURE COEFFICIENT,
 AND EXTERIOR COMPONENT AND CLADDING
 DESIGN WIND PRESSURES.
  
 14) FBC* 104.2.1SHEETS A.22 & A.23.
 THE SOUTH AND NORTH ELEVATIONS DO NOT
 APPEAR TO REPRESENT FENESTRATION AND
 OTHER ARCHITECTURAL FEATURES SHOWN ON
 THE PLANS.FOR EXAMPLE, THE NUMBER OF
 WINDOWS ON THE ELEVATIONS IS DIFFERENT
 TO THE PLANS.PLEASE AMEND/CLARIFY.
  
 15) FBC* 104.2.1SHEET A.02PARKING
 LEVELS B-1 & B-2. STAIR 4 IS INCORRECTLY
 LABELLED AS 'STAIR 2'.AMEND THE PLAN.
  
 16) FBC* 104.2.1SHEET A.35.THE STAIR
 2 PLANS ARE MIS-LABELLED AS 'STAIR 3'.
  
 17) FBC 705.1.2SHEETS LS.1 TO LS.4
 AMEND THE LEGEND TO INDICATE THE
 REQUIRED ONE HOUR RATING FOR THE
 ELEVATOR LOBBIES AND TWO HOUR RATING FOR
 THE WALL TYPE SHOWN AROUND THE STAIR
 SHAFTS, TRASH CHUTE ETC.
  
 18) FBC 412.6SHEET A.02, PARKING LEVEL
 PLAN.AMEND THE PLAN TO CLARIFY THE
 THE PURPOSE, CONSTRUCTION AND
 FIRE-RATING OF THE WALL/DOOR THAT HAS
 BEEN PROVIDED, IN FRONT OF ELEVATORS
 1 TO 3, IN LIEU OF ELEVATOR LOBBIES.
  
 19) FBC 411.4.2SHEET A.02, ENCLOSED
 PARKING GARAGES, MECHANICAL VENTILATION
 AND SMOKE EVACUATION.THE REFERENCE TO
 'STACKED FANS' IS NOTED.ANNOTATE THE
 PLANS TO CLARIFY THE PROVISION OF
 DEDICATED MECHANICAL VENTILATION AT EACH
 LEVEL OF THE PARKING GARAGE.
  
 20) FBC 411.2.6SHEETS A.02 & A.48THE
 PUMP ROOM SHALL BE SEPARATED FROM THE
 PARKING GARAGE BY 1-HOUR FIRE RESISTANT
 CONSTRUCTION.
  
 21) FBC 1012.1.2SHEET A.04, GROUND
 LEVEL PLAN.THE STAIR #2 DOOR SHALL
 OPEN IN THE DIRECTION OF EGRESS.AMEND
 THE PLAN.
  
 22) FBC 1010.3SHEET A.04, GROUND LEVEL
 PLAN, MAIN LOBBY.THE EXIT DISCHARGE
 FROM STAIR #2 IS THROUGH THE MAIN LOBBY
 WHICH MUST THEREFOR SATISFY THE
 REQUIREMENTS OF THE EXCEPTION UNDER
 FBC 1010.3.RECOMMENDATION: PROVIDE TWO
 1-1/2 HOUR CROSS-CORRIDOR DOORS, ONE
 BETWEEN THE STUDIO 'S2' KITCHEN WALL AND
 THE UNIT 'C1' POWDER ROOM WALL OPPOSITE
 AND ONE BETWEEN THE RECEPTION
 ADMINISTRATION AREA AND ELEVATOR #2.
 THIS WOULD LIMIT THE SIZE OF THE EXIT
 DISCHARGE AREA AND SO LIMIT THE
 POTENTIAL RISK OF FIRE/SMOKE INGRESS
 INTO THE EXIT DISCHARGE.
  
 23) FBC TABLES 704.2.4 & 705.1.2SHEETS
 A.04 & A.48. THE RECEPTION ADMINISTRAT'N
 OFFICE, CONFERENCE RM, BUSINESS CENTER,
 FIRE COMMAND CENTER, CLUB ROOM AND
 HEALTH CLUB ARE IN THE EXIT ACCESS
 CORRIDOR AND SHALL BE AT LEAST 30-MINUTE
 FIRE-RATED WITH 20-MINUTE FIRE-RATED
 DOORS (DOOR #'S 16, 17, 18, 20, 26 & 27)
  
 24) SHEET A.04 & A.48THE CA/TV ROOM
 DOOR IS SHOWN AS DOOR REF #30.SHOULD
 THIS BE #38 (SEE DOOR SCHEDULE)?
  
 25) FBC TABLE 704.1SHEET A.13 & A.14
 GROUND LEVEL (PARTIAL) PLAN.THE WALL
 BETWEEN THE CONFERENCE ROOM AND
 UNIT 'A6' IS SHOWN AS TYPE 13, WHICH IS
 NOT A FIRE-RATED WALL TYPE.AMEND THE
 PLAN TO SHOW A MINIMUM OF 1-HOUR FIRE-
 RATING FOR THIS WALL.
  
 26) FBC 11-4.13.6SHEET A.11, GROUND
 LEVEL PLANS, MANEUVERING CLEARANCES AT
 DOORS.THE MEN'S AND WOMEN'S TOILET
 ROOM DOORS FROM CORRIDOR 027 SHALL HAVE
 A MINIMUM OF 18" CLEARANCE BETWEEN THE
 LEADING EDGE OF THE DOOR AND THE
 ADJACENT PERPENDICULAR WALL ON THE PULL
 SIDE OF THE DOOR.AMEND THE PLANS
  
 27) FBC 11-4.13.6 MANEUVERING CLEARANCES
 AT DOORS.THE CONFERENCE ROOM LOBBY,
 BUSINESS CENTER, CLUB ROOM AND HEALTH
 CLUB ENTRANCE DOORS FROM CORRIDOR 027
 (SHEET A.13, GROUND LEVEL) SHALL HAVE A
 MINIMUM 12" CLEARANCE BETWEEN THE
 LEADING EDGE OF THE DOOR AND THE
 ADJACENT RECESSED WALL ON THE PUSH SIDE
 OF THE DOOR IF IT HAS BOTH A CLOSER AND
 A LATCH.AMEND THE PLANS.THIS COMMENT
 ALSO APPLIES TO ALL RESIDENTIAL UNIT
 RECESSED ENTRANCE DOORS (FOR EXAMPLE
 GROUND FLOOR UNITS 'A2' AND 'A4'), IF
 THEY HAVE BOTH A CLOSER AND A LATCH.
  
 28) FBC 1012.1.4SHEET A.36THE STOREY
 EXIT DOORS INTO STAIR #3 AT EACH LEVEL
 SHALL LEAVE UNOBSTRUCTED AT LEAST ONE
 HALF OF THE REQUIRED WIDTH OF THE
 LANDING.AMEND THE PLAN.
  
 29) FBC 1007.5.5SHEET A.34, STAIR #1
 PLANS.THE HANDRAILS SHALL EXTEND AT
 LEAST 12" HORIZONTALLY BEYOND THE TOP
 RISER OF EACH FLIGHT.THE STAIR #1
 PLANS SHOW ONLY 11", AMEND THE PLANS.
  
 30) FBC 1015.4GUARDRAIL STRENGTH.THE
 PLANS SHALL BE AMENDED TO STATE THE
 STRENGTH REQUIREMENTS SET OUT IN
 FBC 1608.2.
  
 31) FBC 1015.3SHEET A.34, A.35 & A.36
 THE PLANS SHALL STATE THE REQUIREMENT
 FOR THE BOTTOM RAIL OF THE GUARDING TO
 BE POSITIONED SUCH THAT A 6" DIAMETER
 SPHERE CANNOT PASS THROUGH THE
 TRIANGULAR OPENING THAT IT FORMS WITH
 THE TREAD AND THE RISER.
  
 32) FBC 1015.3SHEET A.44, DETAIL J.
 THE GUARDRAIL DETAIL SHALL MAKE
 REFERENCE TO THE REQUIREMENTS FOR THE
 SPACING BETWEEN PICKETS TO REJECT THE
 PASSAGE OF A 4" DIAMETER SPHERE, AND FOR
 THE BOTTOM RAIL POSITIONING TO REJECT
 THE PASSAGE OF A 2" DIAMETER SPHERE.
  
 33) FBC* 104.2.1SHEET A.44, DETAIL M,
 SLIDING GLASS DOOR THRESHOLD. THE DETAIL
 SHALL MAKE REFERENCE TO A PRODUCT
 APPROVAL FOR ANCHOR SPECIFICATION.
  
 34) FBC 411.2.3AUTOMOBILE PARKING
 GARAGE, GUARDING.THE INTERIOR PARKING
 GARAGE WALLS ADJACENT THE VEHICLE RAMP,
 STAIR 2 AND 4, AND THE FRONT WALL OF THE
 ELEVATOR SHAFTS SHALL BE DESIGNED TO
 WITHSTAND IMPACT LOADING IN ACCORDANCE
 WITH FBC 1608.2.3.PROVIDE STRUCTURAL
 DETAILS OF THE WALLS AT THESE LOCATIONS.
  
 35) FBC 2405.2THE SHOWER ENCLOSURE
 GLAZING IS IN A 'HAZARDOUS LOCATION' AND
 REQUIRED TO BE SAFETY GLASS SATISFYING
 THE REQUIREMENTS OF THE CONSUMER PRODUCT
 SAFETY COMMISSION 16, CODE OF FEDERAL
 REGULATIONS, PART 1201 (CPSC 16-CFR,
 PART 1201).AMEND THE PLANS TO
 DEMONSTRATE COMPLIANCE.
  
 36) FBC* 104.2.1THE SUBMITTED
 STRUCTURAL PLANS DO NOT PROVIDE A
 COMPLETE DESCRIPTION OF THE STRUCTURE.
 SUBMIT FURTHER STRUCTURAL DETAILS.
  
 37) FBC 11-4.16.4SHEET A.67, GRAB BARS
 AT WATER CLOSETS.THE SIDE GRAB BAR
 SHALL BE A MINIMUM OF 3'6" LONG SUCH
 THAT IT EXTENDS TO NO LESS THAN 54" FROM
 THE REAR WALL (REF: FIGURE 29(B)).THE
 DIMENSIONS ARE SHOWN INCORRECTLY ON ONE
 OF THE TWO DETAILS.AMEND THE PLANS.
  
 38) FBC 11-4.16.2SHEET A.67, CLEAR
 FLOOR SPACE AT WATER CLOSETS.THE
 LAVATORY SHALL BE AT LEAST 18" FROM THE
 CENTER-LINE OF THE W.C. AND 36" FROM THE
 SIDE WALL (REF: FIGURE 28).AMEND THE
 PLANS.
  
 39) FBC 11-4.15.2SHEET A.67, SPOUT
 HEIGHT AND KNEE CLEARANCE.THE HEIGHT
 FROM FINISHED FLOOR TO THE SPOUT (NOT
 THE TOP OF THE FOUNTAIN TRAY) SHALL BE A
 MAXIMUM OF 36" (REF: FIGURE 27(A)).THE
 DIMENSIONS ARE SHOWN INCORRECTLY ON ONE
 OF THE TWO DETAILS.AMEND THE PLANS.
  
 40) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]