2003-07-07 00:00:00 | BULDING REVIEW 2ND CHECKLIST: |
| 1-PAY IMPACT FEES. BRING BACK STAMPED |
| DRAWINGS AND RECEIPT. |
| 2-WILL NEED TO RECORD A NOTICE OF |
| COMMENCEMENT. |
| 3-FOOTING PAD AT REAR PORCH COLUMN IS |
| ENCROACHING INTO NEIGHBOR'S PROPERTY. |
| REVISE AS REQUIRED. |
| 4-AIR HANDLING UNIT HANGING DETAIL: |
| A)DOESN'T PROVIDE THE CLEARANCES REQ'D |
| BY SEC. 603.1.3 MECHANICAL FLORIDA |
| BUILDING CODE 2001. |
| B)IS UNIT BUILT TO BE HANGED FROM SIDE |
| WALL OF UNIT?. IS IT REINFORCED?. |
| PROVIDE MANUFACTURER'S INFORMATION |
| THAT SHOWS THIS TYPE OF INSTALLATION. |
| C)HOW IS VIBRATION TAKEN CARE OF. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| |
| 5-PROVIDE COMPLETE DETAILS/SPECS FOR |
| INSTALLATION OF CEILING AT FRONT AND |
| REAR PORCH. SPECIFY MATERIALS,FASTENER |
| TYPE AND SPACING. SEE ASTM C-926 AND |
| ASTM C-1063. |
| 6-PROVIDE COMPLETE DETAIL FOR GABLE END. |
| NEED TO SPECIFY TRUSS ANCHOR & SPACING |
| SEE SEC. 2117 FBC 2001. |
| 7-UPDATE TRUSS ANCHOR SCHEDULE AND ALL |
| DETAILS THAT ARE AFFECTED BY SECTION |
| 1609.4.3 FBC 2001. SEE SIMPSON HIGH |
| WIND-RESISTANT CONSTRUCTION CATALOGUE |
| WHICH HAS THE REVISED VALUES. |
| 8-PROVIDE STRUCTURAL 2X BUCK DETAIL FOR |
| ENTRY DOORS AND FIXED WINDOWS AS REQ'D |
| ON THE PRODUCT APPROVALS. ALSO, SEE |
| SEC. 1707.4.4.2 FBC 2001 FOR SPECIFIC |
| BUCK INSTALLATION REQUIREMENTS. |
| 9-PROVIDE PRODUCT APPROVAL FOR: |
| A)FIXED WINDOW WITH SIZE AS SHOWN ABOVE |
| SLIDING GLASS DOORS AND ABOVE WINDOW |
| IN THE GREAT ROOM AREA. |
| B)GLASS BLOCK WITH LEGIBLE DRAWINGS. |
| C)LEGIBLE DRAWINGS FOR ENTRY DOOR WITH |
| RENEWAL STAMP BY DADE COUNTY. |
| |
| 10-REVISE STORM SHUTTERS INFORMATION: |
| A)REVISE MEAN ROOF HEIGHT AND DESIGN |
| PRESSURES. |
| B)REVISE MINIMUM AND MAX PANEL SPAN. |
| SEE ENGINEERED DRAWINGS. |
| C)INSTALLATION SCHEDULE: SPECIFY ANCHOR. |
| D)DESIGN PRESSURES ARE MEASURED BY PSF |
| NOT PSI. |
| E)ADDITIONAL ENGINEERED DRAWINGS ARE NOT |
| ALLOWED TO BE USED, UNLESS THEY ARE |
| PART OF THE PRODUCT APPROVAL APPROVED |
| BY SBCCI. |
| F)CLEARLY MARK ON DRAWINGS SPECIFIC |
| MOUNTING CONDITIONS, AND ANCHOR TYPE |
| TO BE USED ACCORDING TO THE DESIGN |
| PRESSURES, EDGE DISTANCE, PANEL SPAN, |
| CONNECTION TYPE AND STRUCTURE TO BE |
| ATTACHED TO. SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. |
| |
| 11-CONTRACTOR TO UPDATE INSURANCE. SEE |
| CLERK TO UPDATE INFORMATION. |
| 12-SPECIFY SAFETY GLASS FOR GLASS BLOCK |
| AT TUB IF FACE THICKNESS IS LESS THAN |
| 0.25". SEC. 2405.2 FBC 2001. |
| 13-OWES $104.10 FOR UPDATED VALUATION |
| AND RADON FEES. |
| 14-PLEASE CLOUD ALL CHANGES IN THE |
| DRAWINGS IN ORDER TO EXPEDITE THE |
| REVIEW PROCESS. |
| |
| |
| PLEASE CALL JULIO GOMEZ IF YOU HAVE ANY |
| QUESTIONS OR NEED CLARIFICATION ON ANY |
| OF THESE COMMENTS. |