Plan Review Notes
Plan Review Notes For Permit 03050068
Permit Number 03050068
Review Stop B
Sequence Number 1
Notes
Date Text
2003-06-12 00:00:00BUILDING REVIEW CHECKLIST:
 1-PAY IMPACT FEES BRING BACK STAMPED
 DRAWINGS AND PAID RECEIPT.
 2-NEED RECORDED NOTICE OF COMMENCEMENT.
 3-FOOTING PAD AT REAR PORCH COLUMN IS
 ENCROACHING NEIGHBOR'S PROPERTY.
 REVISE AS REQUIRED.
 4-AIR HANDLER UNIT: CLARIFY WHY IS THIS
 UNIT ATTACHED TO THE SIDE WALL AND NOT
 TO TOP OF TRUSSES AS TYPICALLY DONE.
 IS THIS UNIT BUILT/REINFORCED ON THE
 SIDE TO BE MOUNTED THIS WAY. AND, WHAT
 ABOUT VIBRATION OF THE UNIT. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 5-PROVIDE DETAILS AND SPECIFICATIONS FOR
 INSTALLATION OF CEILING AT FRONT AND
 REAR PORCH. SPECIFY MATERIALS AND
 FASTENER TYPE AND SPACING. SEE ASTM
 C-926 AND ASTM C-1063.
 6-PROVIDE COMPLETE DETAIL FOR GABLE END.
 SEE SEC. 2117 FBC 2001 FOR SPECIAL
 WIND PROVISIONS FOR MASONRY.
 7-UPDATE TRUSS ANCHOR SCHEDULE AND ALL
 DETAILS THAT ARE AFFECTED BY SECTION
 1609.4.3 FBC 2001, WHICH DOESN'T ALLOW
 THE STREES INCREASE IN STEEL. SEE
 CURRENT CONNECTOR CATALOGUES FOR
 REVISED VALUES.
 8-REVISE DETAIL 1/4-8 FOR FOOTING AREA
 AT GARAGE INTERIOR BEARING WALL. SHOW
 FOOTING WITH 6" RECESS AND DIMENSIONS
 SPECIFIED ON FOUNDATION PLAN.SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 9-PROVIDE STRUCTURAL 2X BUCK DETAIL FOR
 ENTRY DOORS AND FIXED WINDOWS AS REQ'D
 ON THE PRODUCT APPROVALS. ALSO, SEE
 SEC. 1707.4.4.2 FBC 2001 FOR SPECIFIC
 BUCK INSTALLATION REQUIREMENTS.
 10-PROVIDE PRODUCT APPROVAL FOR:
 A)FIXED WINDOW WITH SIZE AS SHOWN ABOVE
 SLIDING GLASS DOORS AND ABOVE WINDOW
 IN THE GREAT ROOM AREA.
 B)WINDOW & DOOR MULLIONS. SEE PLANS.
 C)GLASS BLOCK WITH LEGIBLE DRAWINGS.
 D)UPDATED ROOF TILE. SBCCI REPORT THAT
 WAS SUBMITTED WAS DELETED BY SBCCI.
 E)COMPLETE REPORT FOR GARAGE DOORS.
 F)UPDATED REPORT FOR ENTRY DOORS WITH
 SIDELITE. REPORT TO HAVE DADE COUNTY
 LOGO AT BOTTOM LEFT OF PAGE. ALSO,
 NEED UPDATED LEGIBLE DRAWINGS WITH
 RENEWAL STAMP BY DADE COUNTY.
  
 11-STORM SHUTTERS: A)MEAN ROOF HEIGHT IS
 +/-18'-0" REVISE AS REQUIRED.
 B)SEE ENGINEERED DWGS FOR MAXIMUM AND
 MINIMUM PANEL SPAN ALLOWED AND REVISE
 INSTALLATION SCHEDULE AS REQUIRED.
 C)SEE ENGINEERING DWGS FOR ANCHOR TYPE &
 SPACING TO BE USED AND REVISE INSTALLA
 TION SCHEDULE AS REQUIRED.
 D)DWG 1 OF 1 OF ENGINEERED DWGS: REVISE
 DESIGN PRESSURES ACCORDING TO THE MEAN
 ROOF HEIGHT AND CLEARLY MARK ANCHOR
 TYPE AND SPACING.
  
 12-ENERGY CALCULATIONS BY EARTH SMART
 AND ARCHITECT'S ENERGY CALCS DON'T
 MATCH. REVISE AS REQUIRED.
 13-CONTRACTOR INSURANCE IS EXPIRED.
 UPDATE AS REQUIRED.
 14-SHEET GN AND SHEET A-1: UPDATE CONC.
 GENERAL NOTE. SEE SEC. 1901 FBC 2001
 AND COMMENTS ON DRAWINGS.
 15-SPECIFY SAFETY GLASS FOR GLASS BLOCK
 AT TUB IF FACE THICKNESS IS LESS THAN
 0.25". SEC. 2405.2 FBC 2001.
 16-MEAN ROOF HEIGHT IS TAKEN FROM FINISH
 GRADE, NOT FROM FINISH FLOOR. REVISE
 ELEVATIONS AS REQUIRED.
 17-SHEET A-5A AND A-5B:
 A)UPDATE DETAIL 1/A-5A. HUGHES IS OUT
 OF BUSINESS.
 B)CLARIFY CONSTRUCTION AT ENTRY TOWER.
 IS THERE A LEDGER SUPPORTING TRUSSES
 OR ARE TRUSSES RESTING ON THE WALL?.
 DETAIL 3/A8 DOESN'T SHOW IT.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 C)THERE ARE SOME CONNECTORS MISSING. SEE
 PLANS FOR COMMENTS.
 D)REVISE ROOF NAILING DIAPHRAGM. ZONE
 3 TO BE INCLUDED. SEE FIGURE 1606.2(C)
  
 18-OWES $104.10 FOR UPDATED VALUATION
 AND RADON FEES.