2003-07-22 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 03050043 |
| ADD: 610 CLEMATIS STREET |
| CONT: THE WHITING-TURNER CO. |
| TEL: 954)325-6893 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| |
| ACTION: DENIED |
| |
| 1) UNITY OF TITLE : INFORMATION PROVIDED |
| ON LOTS DOES NOT INDICATE A UNITITY OF |
| TITLE. THE DEEDS SUBMITTED INDICATE |
| SEPERATE LOTS/ SEPERATE PROPERTY CONTROL |
| NUMBERS. |
| |
| 2) THE ALLEYWAY ABANDOMENT, AGAIN NO IN- |
| FORMATION HAS BEEN SUBMITTED. |
| |
| 3) A LETTER FROM THE PROPERTY OWNERS TO |
| THE WEST (U. S. POSTAL SERVICE) GIVING |
| PERMISSION TO ALLOW SOIL NAILS ON THEIR |
| PROPERTY. A HOLD HARMLESS LETTER OR A |
| BOND FOR DAMAGES. |
| |
| 4) ARDAMAN & ASSOC. SUBSURFACE EXPLORA- |
| TION & GEOTECHNICAL REPORT; PAGE 4, PAR- |
| AGRAPH 2, THE REPORT INDICATES THAT |
| THERE WILL BE DAMAGE TO THE CITY STREETS |
| THE CITY WILL NEED A GARENTEE THAT IF |
| DAMAGE TO STREETS OR INTRASTRUCTURE |
| THE CONTRACTOR WILL REPAIR OR REPLACE |
| TO CURRENT CONDITION OR BETTER. |
| |
| 5) SHEET# 4 PARAGRAPH # 6, THE CITY |
| REQUIRES THAT THE VIBROFLOTATION BE COMP |
| LETED AT THE 10'-0" ABOVE THE FINAL |
| EXCAVATION LEVEL, AS REQUESTED BY THE |
| GEOTECHNICAL ENGINEER. |
| |
| 6) THIS ITEM DEALS ACTAULLY WITH THE |
| FOUNDATION, ARDAMAN REPORT PAGE 4 |
| PARAGRAPH# 5, QUOTES THAT VENTS IN THE |
| FLOOR VS. WATERPROOFING FLOOR & WALLS & |
| TO WITHSTAND WATER PRESSURE (UPLIFT) |
| DUE TO RISING WATER. HOW WILL THIS ISSUE |
| BE ADDRESSED? |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |