2003-05-13 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 03050043 |
| ADD: 610 CLEMATIS ST |
| CONT: WHITING-TURNER |
| TEL: (954)776-0800 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| |
| 1) PROVIDE NOC RECORDED WITH THE CLERK |
| OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| |
| 2) PROVIDE DOCUMENTATION OF UNITY OF |
| TITLE, SECOND THAT THE CITY ABANDONED |
| THE ALLEY WAY AND EASEMENT RIGHTS. |
| |
| 3) NO SURVEY!(3) COPIES! |
| |
| 4)FL S. S. 553.71(7) " THRESHOLD |
| BUILDING" MEANING ANY BUILDING WHICH IS |
| GREATER THAN (3) STORIES OR 50 FT IN |
| HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN |
| CY CLASSIFICATION AS DEINED IN THE |
| FLORIDA BUILDING CODE WHICH EXCEEDS |
| 5,000 SQ FT IN AREA AND AN OCCUPANT |
| CONTENT OF GREATER THAN 500 PERSONS. |
| 105.13.1 THE ENFORCING AGENCY SHALL |
| REQUIRE A SPECIAL INSPECTOR TO PERFORM |
| SRUCTURAL INSPECTIONS ON A THRESHOLD |
| BUILDING PURSUANT TO A STRUCTURAL INSPEC |
| TION PLAN PREPARED BY THE ENGINEER OF |
| RECORD. THE STRUCTURAL INSPECTION PLAN |
| MUST BE SUBMITTED TO THE ENFORCING AGEN- |
| CY PRIOR TO THE ISSUANCE OF A BUILDING |
| PERMIT FOR THE CONSTRUCTION OF A THRESH- |
| OLD BUILDING. THE PURPOSE OF THE SRUCTUR |
| AL INSPECTION PLAN IS TO PROVIDE SPECIF- |
| IC INSPECTION PROCEDURES AND SCHEDULES |
| SO THAT THE BUILDING CAN BE ADEQUATELY |
| INSPECTED FOR COMPLIANCE WITH THE |
| PERMITTED DOCUMENTS. |
| |
| 5) FL BLD CODE 1804.2.2 QUESTIONABLE |
| SOILS, WHERE THE BEARING CAPACITY IS |
| NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| |
| PLEASE PROVIDE COPIES OF THE SEALED |
| SOILS REPORT PREFORMED BY ARDAMAN & |
| ASSOCISATES, GEOTECNICAL REPORT |
| # 01-2233 BASED ON 10-01-02 INVESTIGA- |
| TION. |
| |
| 6) MEET THE REQUIREMENTS OF CHAPTER 35 |
| SITE WORK & CONSTRUCTION. |
| A) 3305.1 CONSTRUCTION OF WALKWAYS, |
| FENCES AND PROTECTIVE COVERINGS |
| B) 3303.2 GAIN WRITTEN APPROVAL FROM |
| ENGINEERING FOR THE USE OF SOIL |
| NAILS IN THE RIGHT OF WAY. |
| C) PROVIDE INFORMATION OF UTILITY LOCA- |
| TION IN THE RIGHT OF WAY THAT THE |
| SOIL NAILS MAY INTERFERE WITH. |
| UNDERGROUND POWER LINES, TELEPHONE, |
| CABLE, GAS, WATER & SEWER. |
| |
| 7) 3309 CLEANING OF SIDEWALKS AND |
| STREETS. |
| |
| 8) GEO/ENVIRONMENTAL ASSOCIATES,(CALCS) |
| PLANS, SPECIFICATIONS,REPORTS OR |
| OTHER DOCUMENTS PREPARED BY THE DESIGN |
| PROFESSIONAL AND BEING FILED FOR PUBLIC |
| RECORD SHALL HAVE THE SIGNATURE AND |
| SEAL OF THE DESIGN PROFESSIONAL AFFIXED |
| TO THE DOCUMENT. |
| FL STATE STAT: 61G15-23.002 ENGINEERS |
| FL ATATE STAT: 61G16.003 ARCHITECTS |
| |
| 9) GEO/ ENVIRONMENTAL DOCUMENT, |
| CANTILEVER SHEETPILE WALL ANALYSIS: |
| CALCULATION IS FOR HIGHEST CANTILEVERED |
| WALL 13', WHEREAS IN THE REPORT THERE |
| ARE PAGES INDICATING 20.0' BEHIND THE |
| CREST AT WALL TOE. EVEN IF THE REMAINDER |
| OFA 30' PILE IS USED 10'OR LESS WOULD |
| BE EMBEDDED. |
| |
| ALSO WITH NO SOILS REPORT SUPPLIED, WHEN |
| THE POLICE STATION GARAGE WAS BUILT, |
| SUPPOSEDLY A ARTESIAN WELL WAS HIT. |
| WE DEFINITLY NEED TO SEE THESE REPORTS |
| TO SEE IF ALL AREAS OF CONCERN WERE |
| REVIEWED? |
| |
| LOOK FOR COMMENTS BY THE OTHER PLAN |
| REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| ON THE APPLICATION, PLANS, OR ATTACHED |
| SEPARATELY. WHEN RESUBMITTING PLANS |
| PLEASE CLEARLY INDICATE THE REVISION AND |
| REMOVE AND REPLACE ANY PAGES AS NECESS- |
| ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| THE PLANS WHEN RESUBMITTING PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN |
| BE FOUND, WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| JIM WITMER |
| BUILDING PLAN REVIEW |