2 |
|
Notes |
Date |
Text |
2003-07-23 00:00:00 | ******CORRECTIONS****** | | | | 1.)ADDITIONAL PERMITS REQUIRED. | | | | 2.)SEE PREVIOUS LIST, #2, SHOW THE | | CLEAR NET OPENING HEIGHT (FROM THE | | MANUFACTURER) OF THE SINGLE HUNG 60" | | HIGH EGRESS WINDOWS TO SHOW COMPLIANCE | | WITH FBC1005.4. | | | | 3.)SEE PREVIOUS LIST #10, PROVIDE A | | HURRICANE SHUTTER ANCHORING SCHEDULE. | | | | 4.)PAGE 3 OF THE ROOF PRODUCT APPROVAL | | IS MISSING. | | | | 2.)THE PRODUCT APPROVAL FOR THE | | OPAQUE DOOR IS MISSING SHEETS REFERRED | | TO IN ITEM 2.1. | | | | 3.)THE SINGLE HUNG WINDOW PRODUCT | | APPROVAL IS EXPIRED. | | | | 4.)PROVIDE A PRODUCT APPROVAL FOR | | DOOR #5. | | | | 5.)PROVIDE A SOILS INVESTIGATION | | REPORT. | | | | 6.)SEE PREVIOUS LIST REGARDING IMPACT | | FEES, ITEM #14. | | | | SAMANTHA THYNG, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] |
|