2003-06-17 00:00:00******CORRECTIONS********
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEPARATE PERMITS REQUIRED.
  
 2.)SHOW THE CLEAR NET OPENING HEIGHT
 (FROM THE MANUFACTURER) OF THE SINGLE
 HUNG 60" HIGH EGRESS WINDOWS TO SHOW
 COMPLIANCE WITH FBC1005.4.
  
 3.)ADDITIONAL FEES DUE, $376.61 (SEE
 ATTACHED FOR VALUATION ADJUSTMENT).
  
 4.)INSULATION ON THE WALLS ARE TO BE
 A MINIMUM OF 4.2 PER ENERGY CALCS;
 REVISE WALL SECTION.
  
 5.)UPLIFT FOR TRUSS ANCHORS
 SPECIFIED EXCEEDS UPLIFT ALLOWED IN THE
 2003 CATALOG.REVISE.
  
 6.)FOOTER IS REQUIRED TO BE A MINIMUM
 OF 12" BELOW GRADE PER FBC 1804.1.3.
  
 7.)SPECIFY THE SPACING OF SOFFIT
 SCREEN VENTS, COMPLY WITH FBC 2309.7.
  
 8.)INSULATION BETWEEN CONDITIONED AND
 UNCONDITIONED SPACE IS REQUIRED PER
 ENERGY CALC (ADJACENT WALL).
  
 9.)PROVIDE A WINDOW AND DOOR BUCK
 ATTACHMENT DETAIL; COMPLY WITH FBC
 1707.4.4.2.
  
 10.) PROVIDE A HURRICANE SHUTTER
 ANCHORING SCHEDULE, SEE ATTACHED.
  
 11.) SPECIFY DESIGN PRESSURE FOR DOOR
 #5.
  
 12.)PROVIDE TWO COPIES OF THE GARAGE
 DOOR PRODUCT APPROVAL.
  
 13.)PROVIDE DESIGN INFORMATION ON THE
 PLAN, FBC 1606.1.7.
  
 14.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND THE ORIGINAL RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 233-5025