Plan Review Notes For Permit 03042700
Permit Number 03042700
Review Stop E
Sequence Number 1
Notes
Date Text
2003-05-14 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE ANY NECESSARY CHANGES
 ON THE PLANS AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} PLEASE SHOW THE GROUNDING ELECTRODE
 SYSTEM IN COMPLIANCE WITH 250-50(A,B &
 C)
  
 3} THE CALCULATION FOR THE A/C SYSTEM ON
 THE PANEL SCHEDULE AND THE LOAD CALC'S
 DO NOT CORRELATE.
  
 4} THE SMALL APPLIANCE CIRCUITS MUST BE
 CALCULATED @ 1500 VA.EA PER 220-16(A).
  
 5} THERE IS ONLY ONE GENERAL LIGHTING
 CIRCUIT ON THE PANEL SCHEDULE.THERE
 MUST BE A MINIMUM OF THREE @ 15AMPS.
  
 6} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 7} SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 PER 8-1.4.2,NFPA-72.
  
 8} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718