Date |
Text |
2003-05-14 00:00:00 | UNSAT |
| ~~~~~ |
| ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| PLEASE PROVIDE THE FOLLOWING |
| INFORMATION,MAKE ANY NECESSARY CHANGES |
| ON THE PLANS AND RESUBMIT FOR REVIEW. |
| |
| 1} PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW EQUIPMENT BEING INSTALLED. |
| MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| THE AVAILABLE FAULT CURRENT PER 110-9. |
| |
| 2} PLEASE SHOW THE GROUNDING ELECTRODE |
| SYSTEM IN COMPLIANCE WITH 250-50(A,B & |
| C) |
| |
| 3} THE CALCULATION FOR THE A/C SYSTEM ON |
| THE PANEL SCHEDULE AND THE LOAD CALC'S |
| DO NOT CORRELATE. |
| |
| 4} THE SMALL APPLIANCE CIRCUITS MUST BE |
| CALCULATED @ 1500 VA.EA PER 220-16(A). |
| |
| 5} THERE IS ONLY ONE GENERAL LIGHTING |
| CIRCUIT ON THE PANEL SCHEDULE.THERE |
| MUST BE A MINIMUM OF THREE @ 15AMPS. |
| |
| 6} PLEASE LIST THE REQ'D BATH(S) |
| CIRCUIT(S). PER 210-11-C-3 |
| MUST BE 20A AND #12AWG. |
| |
| 7} SMOKE DETECTORS ARE REQUIRED |
| INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| PER 8-1.4.2,NFPA-72. |
| |
| 8} PLEASE LIST THE REQ'D ARC |
| FAULT PROTECTED CIRCUITS ON PANEL |
| SCHEDULE OR NOTE ON PLANS FOR BRANCH |
| CIRCUIT PROTECTION. PER 210-12 |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLAN REVIEW |
| 561/805-6718 |