Plan Review Notes For Permit 03042700 |
Permit Number |
03042700 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-06-11 00:00:00 | ******CORRECTIONS******** | | | | 1.)A NOTICE OF COMMENCEMENT MUST BE | | FILED WITH THE CLERK OF COURT BEFORE | | A PERMIT CAN BE ISSUED. | | | | 2.)DESIGN INFORMATION IS REQUIRED TO | | BE ON THE PLAN, FBC 1606.1.7, NOT ON | | WIND LOAD CERTIFICATION FORM. | | | | 3.)BEDROOMS ARE REQUIRED TO HAVE | | EMERGENCY EGRESS FBC 1005.4.A 24 S/H | | WINDOW DOES NOT MEET THE HEIGHT | | REQUIREMENT. | | | | 4.)SAFETY GLASS REQUIRED FOR THE | | WINDOWS AT THE TUB AND SHOWER,FBC2405.2. | | NOTE ON FLOOR PLAN. | | | | 5.)SPECIFY MATERIAL AND ATTACHMENTS | | FOR PORCH CEILING. | | | | 6.)WALL SECTON SHOWS R3 INSULATION | | ON WALLS, ENERGY CALC SHOWS 4.2. | | | | 7.)UPLIFT SPECIFIED FOR ATTACHMENTS | | EXCEED PRODUCT LIMITATIONS, SEE | | ATTACHED.REVISE; DO NOT INCLUDE | | STRESS INCREASE FOR STEEL; USE 2003 | | CATALOGS. | | | | 8.)ADDITIONAL FEES REQUIRED. | | | | 9.)SUBMIT TWO COPIES OF PRODUCT | | APPROVALS FOR THE DOUBLE FRENCH DOORS | | AND THE WINDOW MULLIONS. |
|