2003-07-10 00:00:00 | SECOND CHECKLIST: |
| 1-ENERGY CALCULATIONS WERE NOT REVISED: |
| A)A/C AREA DOESN'T MATCH A/C AREA SHOWN |
| ON PLANS. |
| B)ENERGY CALCULATIONS NEED TO BE DONE |
| WORST CASE SCENARIO FOR A PARTICULAR |
| MODEL OR SITE SPECIFIC. ENERGY CALCS. |
| SUBMITTED ARE NEITHER OF THE ABOVE. |
| REVISE AS REQUIRED. |
| C)REVISE UNDER ATTIC AREA TO COMPLY WITH |
| SEC. 602.1ABC.1.2 CHAPTER 13 FBC 2001. |
| |
| 2-PROVIDE SOIL TEST REPORT. |
| 3-PROVIDE PRODUCT APPROVAL FOR: |
| A)ROOF TILE. (IT'S SEPARATE PERMIT |
| BECAUSE SUBCONTRACTOR DIDN'T SIGN THE |
| APPLICATION, BUT INFORMATION STILL IS |
| REQUIRED). |
| B)ENTRY DOORS WITH UPDATED DADE COUNTY |
| REPORT WITH LOGO AT BOTTOM LEFT OF 1ST |
| PAGE AND WITH LEGIBLE DRAWINGS WITH |
| RENEWAL STAMP. |
| C)GARAGE DOORS WITH LEGIBLE DRAWINGS. |
| D)SITE SPECIFIC ENGINEERING NEED SITE |
| SPECIFIC INFORMATION FOR A SPECIFIC |
| BUILDING. INFORMATION SUBMITTED FOR |
| THE MULLIONS IS GENERIC. NEED COMPLETE |
| INFORMATION SPECIFIC TO THIS JOB SITE. |
| CLEARLY SPECIFY ALL COMPONENTS TO BE |
| USED IN THIS PROJECT. MULLION SIZE, |
| ANCHORS, DESIGN PRESSURES ETC. ALSO, |
| NEED TO INDICATE THE ADDRESS OF THIS |
| PROJECT. |
| **ALSO, COMPLETE SITE SPECIFIC FORM AS |
| DONE FOR THE SITE SPECIFIC ARCHED |
| WINDOWS. |
| E)NEED PRODUCT APPROVAL FOR STRUCTURAL |
| HEADER ABOVE SLIDING GLASS DOORS. SEE |
| PLANS FOR SIZE SPECIFIED. |
| F)NEED GLASS PRODUCT APPROVAL WITH |
| LEGIBLE DRAWINGS. |
| |
| 4-REVISE BOLT SIZE SPECIFIED FOR ANCHOR |
| SHOWN ON DETAIL 10/A5. SEE SIMPSON |
| CATALOGUE. ALSO: NEED TO USE SIMPSON |
| CATALOGUE FOR HIGH WIND-RESISTANT |
| CONSTRUCTION CATALOGUE SINCE IS THE |
| ONLY ONE BEEN REVISED TO COMPLY WITH |
| SECTION 1609.4.3 FBC 2001. |
| 5-REVISE GABLE END CONSTRUCTION AT |
| FAMILY ROOM AREA TO COMPLY WITH SEC. |
| 2117.1.2 FBC 2001. |
| **ALSO, CLARIFY CONSTRUCTION OF GABLE |
| AT REAR PORCH. DETAILS 2/A5 AND 6/A5 |
| DON'T APPLY. SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. |
| 6-OWES $774.32 FOR WESTERN EXPANSION |
| FEES AND RADON FEES. |
| |