2003-06-11 00:00:00 | BUILDING REVIEW CHECKLIST: |
| 1-PAY IMPACT FEES. BRING BACK RECEIPT & |
| STAMPED PLANS. |
| 2-ENERGY CALCULATIONS: A)A/C AREA DOES |
| NOT MATCH PLANS. SEE PLANS. |
| B)ENERGY CALCULATIONS FOR A MODEL NEEDS |
| TO BE WORST CASE SCENARIO. OTHERWISE, |
| SITE SPECIFIC ORIENTATION IS REQUIRED. |
| ORIENTATION FOR THIS HOUSE DOES NOT |
| MATCH ENERGY CALCULATIONS. REVISE AS |
| REQUIRED. WORST CASE OR SITE SPECIFIC. |
| C)REVISE UNDER ATTIC AREA TO COMPLY WITH |
| SEC. 602.1ABC.1.2 CHAPTER 13 FBC 2001. |
| 3-PROVIDE SOIL TEST REPORT. |
| 4-PROVIDE GENERAL SPECIFICATIONS FOR |
| FIREBLOCKING AT ALL CONCEALED SPACES. |
| SEC. 2305 FBC 2001. |
| 5-DETAIL 5/A5 NEED TO BE REVISED. NEED |
| 2X TO SUPPORT WINDOW. SEE PRODUCT |
| APPROVAL. |
| 6-PROVIDE COMPLETE SPECS FOR GARAGE DOOR |
| STRUCTURAL BUCK. NEED ANCHOR EMBEDMENT |
| AND WASHER. SEC. 104.2.1.2 CITY AMEND. |
| 7-REVISE ROOF NAILING ZONE DIAPHRAGM. |
| SEE FIGURE 1606.2(C) FBC 2001 FOR ALL |
| CONSIDERED ZONE AREA 3. |
| 8-UPDATE TRUSS ANCHOR SCHEDULE AND ALL |
| DETAILS THAT NEED TO BE REVISE TO |
| COMPLY WITH SEC. 1606.9.4.3 FBC 2001. |
| 9-PROVIDE PRODUCT APPROVAL FOR: |
| A)ROOF TILE. |
| B)ENTRY DOORS WITH UPDATED DADE COUNTY |
| REPORT WITH LOGO AT BOTTOM LEFT OF |
| FIRST PAGE. ALSO, LEGIBLE DRAWINGS W/ |
| UPDATED DADE COUNTY STAMP. |
| C)GARAGE DOOR WITH LEGIBLE DRAWINGS. |
| D)AS PER THE BUILDING OFFICIAL ALL SITE |
| SPECIFIC PRODUCT APPORVALS TO HAVE |
| PROFESSIONAL OF RECORD SIGNING AND |
| SEALING SAME SITE SPECIFIC FORM (OR |
| LETTER CLEARLY IDENTIFYING ALL SITE |
| SPECIFIC PRODUCT THAT WERE APPROVED). |
| **SEE COMMENTS ON RETURNED PRODUCT |
| APPROVALS. |
| E)PRODUCT APPROVAL FOR STRUCTURAL |
| MULLION ABOVE SLIDING GLASS DOORS. |
| F)GLASS BLOCK WITH LEGIBLE DRAWINGS. |
| 10-SPECIFY PRODUCT APPROVAL WERE REQ'D. |
| SEE PLANS FOR COMMENTS. |
| 11-SPECIFY SIZE OF WOOD COLUMNS SHOWN |
| ON FRAMING PLAN. SEE SHEET A-5 FOR |
| ADDITIONAL COMMENTS. |
| 12-SEE SHEET A6 FOR ADDITIONAL COMMENTS. |