2003-06-03 00:00:00 | BULDING REVIEW CHECKLIST: |
| 1-REVISE ENERGY CALCULATIONS: A)A/C AREA |
| DON'T MATCH ARCHITECT'S DRAWINGS. |
| B)INSULATION SPECIFIED ON EXTERIOR CONC. |
| BLOCK WALL DOESN'T MATCH ARCHITECT'S |
| PLANS. REVISE EITHER ONE AS REQUIRED. |
| C)COMPLETE ALL INFORMATION ON TOP OF |
| FORM. EG: OWNER, ETC. |
| D)PROVIDE ORIGINAL SIGNATURES ON BOTTOM |
| OF FORM. SEC. 103.0 CHAPTER 13 FBC/01. |
| |
| 2-SOIL TEST REPORT PROVIDED IS FOR LOT |
| 21. THIS IS LOT 4. REVISE AS REQ'D. |
| 3-IF EGRESS FROM BEDROOM IS THRU ZERO |
| LOT WALL, THEN NEED RECORDED PLAT |
| SHOWING EASEMENT TO ALLOW FOR EGRESS |
| THRU NEIGHBOR'S PROPERTY AS REQUIRED |
| BY THE BUILDING OFFICIAL. |
| 4-PROVIDE SPECS FOR WWM SUPPORTS IN CONC |
| SLAB. SEE SEC. 1909.3 FBC 2001. |
| 5-GLASS BLOCK BY TUB AREA TO BE SAFETY |
| GLASS IF FACE THICKNESS IS LESS THAN |
| 0.25". SEE SEC. 2405.2 FBC 2001. |
| 6-ENERGY CALCULATIONS TAKE THE CEILING |
| FAN CREDIT, THEN, SPECIFY SIZE AND # |
| OF CEILING FANS IN ALL ROOMS AS REQ'D |
| BY TABLE 6-6 CHAPTER 13 FBC 2001. |
| **NOTE: WHEN TAKING THIS CREDIT, CEILING |
| FANS SHALL BE INSTALLED. THEY ARE NOT |
| OPTIONAL AS CALLED FOR DEN ROOM. |
| 7-STORM PANELS EXCEED THE MAXIMUM PANEL |
| SPAN ALLOWED BY TABLE 1 OF ENGINEERED |
| DRAWINGS ACCORDING TO THE DESIGN |
| PRESSURES CALCULATED BY THE ENGINEER |
| OF RECORD. REVISE INSTALLATION SCHED. |
| AS REQUIRED. SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. |
| 8-PROVIDE 2X STRUCTURAL BUCK DETAIL FOR |
| ENTRY DOORS AS REQUIRED BY THE PRODUCT |
| APPROVAL SUBMITTED. |
| 9-OWES $38.46 FOR UPDATED VALUATION AND |
| RADON FEES. |
| 10-UPDATE THE TRUSS ANCHOR SCHEDULE AND |
| ALL DETAILS THAT ARE AFFECTED BY SEC. |
| 1609.4.3 FBC 2001, WHICH DOES NOT |
| ALLOW THE 33% INCREASE IN THE ALLOWA- |
| BLE STRESS OF THE STEEL. |