2003-06-30 00:00:00*******CORRECTIONS*******
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 WHEN RESUBMITTING, ALL CHANGES SHOULD
 BE MARKED ON THE PLAN.SUBMIT A COPY
 OF THE OLD SHEETS.
  
 1.)SEE PREVIOUS CORRECTION LIST, #4,
 NAILING OF ROOF SHEATHING IN THE WALL
 SECTION DOES NOT COMPLY WITH CITY OF
 WEST PALM BEACH AMENDMENTS TO THE FBC,
 TABLE 2306.1 (SEE ATTACHED).
  
 2.) SUBMIT 2 COPIES OF PRODUCT APPROVALS
 FOR THE FRONT DOOR.
  
 3.)R19 INSULATION MIN. IS REQUIRED
 FOR A 2X6 FRAME WALL, FBC602.1.C.1.1.
  
 4.)THE ORIGINAL PLAN SHOWED AN
 EXISTING STUDY.THIS IS NOW SHOWN AS
 AN EXISTING PORCH.ADDITION OF AIR
 CONDITIONED LIVING SPACE REQUIRES:
 ENERGY CALCS FBC13-103.1.2
 IMPACT FEES
  
 5.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND THE ORIGINAL RECEIPT
 ATTACHED TO THE APPLICATION. 233-5025
  
 6.)BEFORE RESUBMITTING, COMPARE THE
 MINIMUM INSULATION R VALUES ON THE
 ENERGY CALC TO THE PLAN.
  
 7.)THERE IS A HOLD ON THIS PROPERTY
 (SEE ATTACHED).SEE ATTACHED.
  
 8.)THE NAME OF THE DESIGNER IS
 REQUIRED TO BE ON THE PLAN, FBC104.2.1.
  
 9.)ADDITIONAL PERMITS REQUIRED.
  
 10.) HOW WILL THE PROPOSED NEW ROOF
 TRUSSES BE ATTACHED TO THE EXISTING
 HOUSE?GIVE UPLIFT VALUES FOR ALL
 CONNECTORS.
  
 11.)DESIGN INFORMATION IS REQUIRED
 TO BE ON THE PLAN, FBC1606.1.7.
  
 12.)AREA CALCULATIONS ARE REQUIRED
 TO BE ON THE PLAN (EXISTING, PROPOSED,
 NEW TOTALS).