2003-06-30 00:00:00 | *******CORRECTIONS******* |
| |
| SAMANTHA THYNG, BUILDING PLANS EXAMINER |
| [email protected] |
| |
| WHEN RESUBMITTING, ALL CHANGES SHOULD |
| BE MARKED ON THE PLAN.SUBMIT A COPY |
| OF THE OLD SHEETS. |
| |
| 1.)SEE PREVIOUS CORRECTION LIST, #4, |
| NAILING OF ROOF SHEATHING IN THE WALL |
| SECTION DOES NOT COMPLY WITH CITY OF |
| WEST PALM BEACH AMENDMENTS TO THE FBC, |
| TABLE 2306.1 (SEE ATTACHED). |
| |
| 2.) SUBMIT 2 COPIES OF PRODUCT APPROVALS |
| FOR THE FRONT DOOR. |
| |
| 3.)R19 INSULATION MIN. IS REQUIRED |
| FOR A 2X6 FRAME WALL, FBC602.1.C.1.1. |
| |
| 4.)THE ORIGINAL PLAN SHOWED AN |
| EXISTING STUDY.THIS IS NOW SHOWN AS |
| AN EXISTING PORCH.ADDITION OF AIR |
| CONDITIONED LIVING SPACE REQUIRES: |
| ENERGY CALCS FBC13-103.1.2 |
| IMPACT FEES |
| |
| 5.)IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY.THE PLANS MUST BE |
| STAMPED AND THE ORIGINAL RECEIPT |
| ATTACHED TO THE APPLICATION. 233-5025 |
| |
| 6.)BEFORE RESUBMITTING, COMPARE THE |
| MINIMUM INSULATION R VALUES ON THE |
| ENERGY CALC TO THE PLAN. |
| |
| 7.)THERE IS A HOLD ON THIS PROPERTY |
| (SEE ATTACHED).SEE ATTACHED. |
| |
| 8.)THE NAME OF THE DESIGNER IS |
| REQUIRED TO BE ON THE PLAN, FBC104.2.1. |
| |
| 9.)ADDITIONAL PERMITS REQUIRED. |
| |
| 10.) HOW WILL THE PROPOSED NEW ROOF |
| TRUSSES BE ATTACHED TO THE EXISTING |
| HOUSE?GIVE UPLIFT VALUES FOR ALL |
| CONNECTORS. |
| |
| 11.)DESIGN INFORMATION IS REQUIRED |
| TO BE ON THE PLAN, FBC1606.1.7. |
| |
| 12.)AREA CALCULATIONS ARE REQUIRED |
| TO BE ON THE PLAN (EXISTING, PROPOSED, |
| NEW TOTALS). |