2003-07-01 00:00:00********CORRECTIONS********
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEE THE PREVIOUS CORRECTIONS
 REGARDING THE ATTACHMENT OF THE NEW SLAB
 TO THE EXISTING.THE EMBEDMENT LENGTH
 IS STILL NOT ON THE PLAN.AGAIN, I
 HAVE CIRCLED THE DETAIL SO THAT YOU
 CORRECT THE RIGHT ONE.
  
 2.)SEE THE CORRECTION NOTE #5 DATED
 6/12/3.I HAD A CONVERSATION WITH THE
 DESIGNER EXPLAINING THIS CORRECTION.HE
 INDICATED THAT HE UNDERSTOOD THE
 CORRECTION.IT IS NOT CHANGED ON THE
 PLAN.THE R VALUE SPECIFIED ON THE
 PLAN IN NOT CONSISTENT WITH THE
 MINIMUMS SPECIFIED ON THE ENERGY CALC.
 I HAVE CIRCLED THE INCORRECT RVALUE ON
 THE PLAN.
  
 3.)THE PRODUCT APPROVALS FOR THE
 HURRICANE SHUTTERS ARE ILLEGIBLE.
  
 4.)PROVIDE A HURRICANE SHUTTER
 ANCHORING SCHEDULE, SEE ATTACHED.
  
 5.)SHOW THE DIMENSIONS ABOVE & BELOW
 GRADE FOR THE FOOTER, CBS WALL SECTION.
  
 6.)THE WINDOW PRODUCT APPROVALS ARE
 INCOMPLETE.SUBMIT TWO COMPLETE COPIES.
  
 7.)ADDITIONS OVER 25% MUST COMPLY
 WITH FBC3401.7.1.2.SHOW, FOR THE
 EXISTING HOUSE, THE FOLLOWING:
 EMERGENCY EGRESS FOR BEDROOMS,FBC1005.4
 SMOKE DETECTORS FOR BEDROOMS,FBC905.2.2
 BATHROOM TO COMPLY WITH FBC11-11(1)
 FRONT DOOR TO COMPLY WITH 1004
  
 8.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC.