Date |
Text |
2003-07-01 00:00:00 | ********CORRECTIONS******** |
| |
| SAMANTHA THYNG, BUILDING PLANS EXAMINER |
| [email protected] |
| |
| 1.)SEE THE PREVIOUS CORRECTIONS |
| REGARDING THE ATTACHMENT OF THE NEW SLAB |
| TO THE EXISTING.THE EMBEDMENT LENGTH |
| IS STILL NOT ON THE PLAN.AGAIN, I |
| HAVE CIRCLED THE DETAIL SO THAT YOU |
| CORRECT THE RIGHT ONE. |
| |
| 2.)SEE THE CORRECTION NOTE #5 DATED |
| 6/12/3.I HAD A CONVERSATION WITH THE |
| DESIGNER EXPLAINING THIS CORRECTION.HE |
| INDICATED THAT HE UNDERSTOOD THE |
| CORRECTION.IT IS NOT CHANGED ON THE |
| PLAN.THE R VALUE SPECIFIED ON THE |
| PLAN IN NOT CONSISTENT WITH THE |
| MINIMUMS SPECIFIED ON THE ENERGY CALC. |
| I HAVE CIRCLED THE INCORRECT RVALUE ON |
| THE PLAN. |
| |
| 3.)THE PRODUCT APPROVALS FOR THE |
| HURRICANE SHUTTERS ARE ILLEGIBLE. |
| |
| 4.)PROVIDE A HURRICANE SHUTTER |
| ANCHORING SCHEDULE, SEE ATTACHED. |
| |
| 5.)SHOW THE DIMENSIONS ABOVE & BELOW |
| GRADE FOR THE FOOTER, CBS WALL SECTION. |
| |
| 6.)THE WINDOW PRODUCT APPROVALS ARE |
| INCOMPLETE.SUBMIT TWO COMPLETE COPIES. |
| |
| 7.)ADDITIONS OVER 25% MUST COMPLY |
| WITH FBC3401.7.1.2.SHOW, FOR THE |
| EXISTING HOUSE, THE FOLLOWING: |
| EMERGENCY EGRESS FOR BEDROOMS,FBC1005.4 |
| SMOKE DETECTORS FOR BEDROOMS,FBC905.2.2 |
| BATHROOM TO COMPLY WITH FBC11-11(1) |
| FRONT DOOR TO COMPLY WITH 1004 |
| |
| 8.)SIGN THE OWNER/AGENT LINE OF THE |
| ENERGY CALC. |