2003-06-12 00:00:00*******CORRECTIONS********
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEE #2 ON FIRST CORRECTION LIST,
 #1 ON 2ND CORRECTION LIST.THIS IS
 THE THIRD REQUEST FOR ENERGY CALCS.A
 PERMIT CANNOT BE ISSUED UNTIL ENERGY
 CALCS ARE SUBMITTED.
  
 2.)SEPARATE PERMITS REQUIRED.
  
 3.)SEE PREVIOUS CORRECTION #3,
 FOR THE ATTACHMENTS OF THE NEW SLAB TO
 THE EXISTING, SHOW THE LENGTH OF THE
 DOWELS AND THE EMBEDMENT.THIS IS
 FOUND ON THE WALL SECTION; I HAVE
 CIRCLED IT SO THAT YOU CHANGE THE
 CORRECT DETAIL.
  
 4.)SEE PREVIOUS CORRECTION #5; STILL
 SHOWS BOTH A 6" AND 8" EMBEDMENT.I
 HAVE MARKED THIS AS WELL.
  
 5.)YOU HAVE SPECIFIED 4.2 FOIL
 INSULATION ON THE WALL.THIS MUST BE
 CONSISTENT WITH THE ENERGY CALCS.IF
 THEY SUBMIT A SHORT FOR ENERGY CALC,
 THE MINIMUM R VALUE FOR A BLOCK WALL
 IS R5.DO NOT RESUBMIT UNTIL YOU HAVE
 SEEN THE ENERGY CALC AND HAVE CONFIRMED
 THAT THE R VALUES STATED ON THE ENERGY
 CALC ARE CONSISTENT WITH OR LESS THAN
 SPECIFIED BY YOUR PLAN.