2003-06-12 00:00:00 | *******CORRECTIONS******** |
| |
| SAMANTHA THYNG, BUILDING PLANS EXAMINER |
| [email protected] |
| |
| 1.)SEE #2 ON FIRST CORRECTION LIST, |
| #1 ON 2ND CORRECTION LIST.THIS IS |
| THE THIRD REQUEST FOR ENERGY CALCS.A |
| PERMIT CANNOT BE ISSUED UNTIL ENERGY |
| CALCS ARE SUBMITTED. |
| |
| 2.)SEPARATE PERMITS REQUIRED. |
| |
| 3.)SEE PREVIOUS CORRECTION #3, |
| FOR THE ATTACHMENTS OF THE NEW SLAB TO |
| THE EXISTING, SHOW THE LENGTH OF THE |
| DOWELS AND THE EMBEDMENT.THIS IS |
| FOUND ON THE WALL SECTION; I HAVE |
| CIRCLED IT SO THAT YOU CHANGE THE |
| CORRECT DETAIL. |
| |
| 4.)SEE PREVIOUS CORRECTION #5; STILL |
| SHOWS BOTH A 6" AND 8" EMBEDMENT.I |
| HAVE MARKED THIS AS WELL. |
| |
| 5.)YOU HAVE SPECIFIED 4.2 FOIL |
| INSULATION ON THE WALL.THIS MUST BE |
| CONSISTENT WITH THE ENERGY CALCS.IF |
| THEY SUBMIT A SHORT FOR ENERGY CALC, |
| THE MINIMUM R VALUE FOR A BLOCK WALL |
| IS R5.DO NOT RESUBMIT UNTIL YOU HAVE |
| SEEN THE ENERGY CALC AND HAVE CONFIRMED |
| THAT THE R VALUES STATED ON THE ENERGY |
| CALC ARE CONSISTENT WITH OR LESS THAN |
| SPECIFIED BY YOUR PLAN. |