Plan Review Notes
Plan Review Notes For Permit 03042078
Permit Number 03042078
Review Stop B
Sequence Number 2
Notes
Date Text
2003-06-04 00:00:00******CORRECTIONS*******
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEE #2 ON PREVIOUS CORRECTION
 LIST; ENERGY CALCS REQUIRED.
  
 2.)SEPARATE PERMITS REQUIRED.
  
 3.)FOR THE ATTACHMENTS OF THE NEW
 SLAB TO THE EXISTING, SHOW THE LENGTH
 OF THE DOWELS AND EMBEDMENT.
  
 4.)THE CEILING INSULATION IS TO BE
 R19 MINIMUM (FBC 13-404.1.C).IT WAS
 CORRECT ON THE ORIGINAL PLAN, THEN WAS
 CHANGED TO R11.CORRECTION #5
 REFERRED TO THE WALL INSULATION.
 SPECIFY THE INSULATION R-VALUE FOR THE
 WALLS.
  
 5.)THE NOTE ABOVE THE BEAM PLAN ON THE
 ROOF PLAN SHOWS 6" AND 8" EMBEDMENT.
 CLARIFY.ALSO SAYS "INTO EX. CONC FTG".
 ISN'T THIS FOR THE BEAM, NOT THE
 FOOTING?IT IS ON THE ROOF PLAN.
  
 6.)SEE PREVIOUS CORR. NOTE #7.THE
 SHEATHING SCHEDULE STILL DOES NOT
 COMPLY.
  
 7.)THE ATTACHMENT OF THE NEW FOOTING
 TO EXISTING SHOWS BOTH 6" AND 8"
 EMBEDMENT.CLARIFY.
  
 8.)TWO COPIES OF ALL PRODUCT APPROVALS
 MUST BE SUBMITTED.
  
 9.)THE ROOF PRODUCT APPROVAL IS TO
 RE-COVER AN EXISTING DECK WITH AN
 EXISTING ROOF.YOU MAY SUBMIT THE
 CORRECT PRODUCT APPROVAL NOW OR SUBMIT
 IT WITH THE ROOF PERMIT APPLICATION.