2003-05-27 00:00:00 | BUILDING DENIED |
| |
| 1) IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 2) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 3) SUBMIT A SOIL BORING TEST REPORT AS |
| REQUIRED BY CITY AMEND. TO FBC 1804.2.2. |
| |
| 4) THE NOTE AT THE BOLLARD ON A1 REFERS |
| TO DETAIL #54. THERE IS NO DETAIL #54. |
| |
| 5) INDICATE ON THE PLANS THAT THE FRAME |
| WALLS ADJACENT TO THE GARAGE ARE |
| REQUIRED TO BE INSULATED AND THE DOOR TO |
| THE CONDITIONED SPACE FROM THE GARAGE IS |
| REQUIRED TO BE SOLID CORE OR INSULATED. |
| SEE FBC CHAPTER 13. |
| |
| 6) THE UPLIFT VALUES IN DETAIL 2 ON A5 |
| ARE INCORRECT. THE MAXIMUM NUMBER OF |
| NAILS IS SEVEN IN EACH MEMBER FOR THE |
| "USP" RT22T, WHICH HAS A MAXIMUM UPLIFT |
| VALUE OF 1125#. ADDING MORE NAILS TO THE |
| STRAP THAN THE MAXIMUM AMOUNT SPECIFIED |
| WILL NOT INCREASE THE UPLIFT VALUES DUE |
| TO THE FAILURE OF THE CONNECTOR ITSELF. |
| SEE 2003 "USP" CATALOG. |
| |
| 7) REVISE LOAD VALUES IN DETAIL 8 ON A5. |
| THE LOAD VALUES FOR THE "USP" THD 28 |
| WITH (16) 10D X 1-1/2" AND (28) 16D IN |
| HEADER IS 3965# GRAVITY ROOF LOADING AND |
| 2025# UPLIFT MAXIMUM WITH NO FUTHER |
| INCREASE PERMITTED. SEE 2003 USP CATALOG |
| PAGE 174. |
| |
| 8) PLEASE CLARIFY THE TRUSS CONNECTIONS |
| AT THE TOP OF THE (2) STEEL COLUMNS ON |
| THE FRAMING PLAN ON A5. DETAIL 7 ON A5 |
| DOES NOT APPEAR TO MATCH THE CONDITION |
| ON THE PLAN. |
| |
| 9) REVISE THE TRUSS CONNECTOR SCHEDULE |
| ON A6 TO LOAD VALUES THAT DO NOT INCLUDE |
| A STRESS INCREASE ON THE STEEL |
| CALCULATIONS. THE MAXIMUM UPLIFT FOR A |
| SINGLE TA ANCHOR IS 1205#. SEE THE 2003 |
| USP CATALOG AND FBC 1609.4. |
| |
| 10) DETAIL 9 ON A5 SHOWS A "SIMPSON" |
| HUS CONNECTOR WITH ONE OF THE FLANGES |
| ANGLED AND THE OTHER ONE STRAIGHT. THIS |
| CONFIGURATION IS NOT LISTED IN THE 2003 |
| SIMPSON CATALOG AND FIELD BENDING OF THE |
| CONNECTORS IS NOT ALLOWED. PLEASE |
| CLARIFY. |
| |
| 11) THE BRACING PLAN ON A6 REFERS TO |
| DETAILS ON A6. THERE ARE NO DETAILS ON |
| A6. PLEASE CORRECT. |
| |
| 12) SUBMIT PRODUCT APPROVALS FOR THE |
| DOUBLE OUTSWING GLAZED DOOR. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)659-8096 EXT.8202 |