2003-07-15 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: |
| 1-REVISE ENERGY CALCULATIONS. UNDER |
| ATTIC AREA IS INCORRECT. SEE SECTION |
| 602.1.ABC.1.2 CHAPTER 13 FBC 2001. |
| 2-PROVIDE SOIL TEST REPORT PRIOR TO |
| CONSTRUCTION. |
| 3-REVISE ROOF NAILING ZONE DIAPHRAGM. |
| GABLE ENDS TO BE NAILED AS ZONE 3. |
| SEE CHAPTER 23 CITY AMENDMENTS TO FBC. |
| 4-WHERE IS DETAIL 1/A6 KEYED ON ROOF |
| FRAMING PLAN SHEET A-6. |
| 5-CLARIFY DETAIL 7/A5. CONNECTOR IS |
| DESIGNED AS WOOD TO WOOD CONNECTOR. |
| CLARIFY WHERE IT SAYS THAT DIFFERENT |
| FASTENERS MAY BE USED IF NOT EXCEEDING |
| 25% OF THE ULTIMATE CAPACITY. ALSO, |
| HOW ARE CONNECTORS ADAPTED TO RECEIVE |
| DIFFERENT NAILS THAN DESIGNED FOR?. |
| 6-REVISE/UPDATE DETAIL 2/A5 TO COMPLY |
| WITH SEC. 1609.4.3 FBC 2001. SPECIFY |
| HOW WERE THE VALUES DETERMINED FOR |
| THE SPECIFIED LOADS ON THIS TABLE. |
| 7-PROVIDE PRODUCT APPROVAL FOR: |
| A)ROOF TILE. B)ENTRY DOORS WITH LEGIBLE |
| DRAWINGS WITH RENEWAL STAMP AND DADE |
| COUNTY LOGO ON BOTTOM FORM OF PRODUCT |
| APPROVAL REPORT. C)GARAGE DOORS WITH |
| LEGIBLE DRAWINGS. D)NEED SITE SPECIFIC |
| FORM FILLED FOR STRUCTURAL MULLIONS TO |
| BE USED. CLEARLY INDICATE MULLIONS AND |
| FASTENERS TO BE USED. |