2003-06-04 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: |
| 1-ENERGY CALCULATIONS: REVISE THE UNDER |
| ATTIC AREA TO COMPLY WITH SECTION |
| 602.1ABC.1.2 CHAPTER 13 FBC 2001. |
| 2-PROVIDE SOIL TEST REPORT PRIOR TO |
| CONSTRUCTION. |
| 3-PROVIDE SPECIFICATIONS FOR FIREBLOCK'G |
| AT ALL CONCEALED SPACES AS REQUIRED BY |
| SEC. 2305 FBC 2001. |
| 4-REVISE COLS. SPECIFIED AT ENTRY DOORS. |
| IT'S NOT A C1. SEE SIZE SHOWN ON FOUN- |
| DATION PLAN. |
| 5-DETAIL 5/A5 NEED TO BE REVISED. NEED |
| 2X STRUCTURAL BUCK TO SUPPORT WINDOW. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| 6-PROVIDE COMPLETE SPECS FOR GARAGE DOOR |
| STRUCTURAL BUCK DETAIL. NEED ANCHOR |
| EMBEDMENT AND WASHER. SEC. 104.2.1.2 |
| CITY AMENDMENTS TO FBC 2001. |
| 7-ENTRY TOWER: PROVIDE COMPLETE DETAIL |
| AND SPECIFICATIONS FOR ATTACHMENT OF |
| WINDOWS TO ROPE COLUMN SHOWN ON THE |
| FRONT ELEVATION.SECTION 104.2.1.2 |
| CITY AMENDMENTS TO FBC 2001. |
| 8-REVISE ROOF NAILING ZONE DIAPHRAGM. |
| SEE FIGURE 1606.2(C) FBC 2001 FOR |
| ZONE 3 AREA NOT SHOWN IN DRAWINGS. |
| 9-WHERE ARE DETAILS 1/A6 AND 1/A8 THAT |
| WERE KEYED ON ROOF FRAMING PLANS? |
| 10-DETAIL 7/A5: CLARIFY WHERE ARE |
| CONNECTORS HUC48,410,412,414 TAKEN |
| FROM. SIMPSON 2003 CATALOGUE DON'T |
| SHOW THEM. ALSO, NEED MASONRY HANGER. |
| WHY USING A WOOD TO WOOD HANGER?. |
| 11-DETAIL 2/A5: UNABLE TO FIND RT22 IN |
| USP CATALOGUE. IS THIS A CUSTOM MADE |
| CONNECTOR?. CLARIFY. ALSO, UPDATE |
| VALUES TO COMPLY WITH SEC. 1609.4.3 |
| FBC 2001. |
| 12-MISSING TRUSS ANCHOR SCHEDULE. |
| 13-PROVIDE PRODUCT APPROVAL FOR: |
| A)ROOF TILE. |
| B)ENTRY DOORS WITH LEGIBLE DRAWINGS. |
| C)GARAGE DOORS WITH LEGIBLE DRAWINGS. |
| D)AS PER THE BUILDING OFFICIAL ALL SITE |
| SPECIFIC PRODUCT APPROVALS TO HAVE THE |
| SEAL AND SIGNATURE OF THE ARCHITECT/ |
| ENGINEER OF RECORD OR TO PROVIDE A |
| SIGNED & SEALED LETTER CLEARLY IDENTI- |
| FYING ALL SITE SPECIFIC WINDOWS AND |
| ASSEMBLIES THAT WHERE REVIEWED AND |
| APPROVED. |