Date |
Text |
2003-05-22 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 03041784 |
| ADD: 2626 SANDY CAY |
| CONT: TAZ CONSTRUCTION |
| TEL: (954)340-1744 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| |
| ACTION: DENIED |
| |
| 1)SITE SPECIFIC ENGINEERING (PRODUCT |
| APPROVAL) REQUIRES THE WET SIGNATURE, |
| DATE AND EMBOSSED SEAL OF THE ENGINEER |
| CERTIFYING THE PRODUCT AND SIGNATURE |
| AND SEAL OF THE DESIGN PROFESSIONAL |
| OF RECORD. |
| MISSING ADDRESS OF LOT FOR SITE SPECIFIC |
| ENGINEERING, MISSING SEAL AND SIGNATURE |
| OF DESIGN PROFESSIONAL. |
| |
| 2)1609.4.3 LOAD REDUCTION. |
| WHEN STRUCTURAL EFFECTS DUE TO TWO OR |
| MORE LOADS IN COMBINATION WITH DEAD LOAD |
| ARE INVESTIGATED IN LOAD COMBINATIONS OF |
| 1609.4.1 OR 1609.4.2, THE COMBINED |
| EFFECTS DUE TO THE TWO OR LOADS MULTI- |
| PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD |
| LOADS SHALL NOT BE LESS THAN THE EFFECTS |
| FROM THE LOAD COMBINATION OF THE DEAD |
| LOAD PLUS THE LOAD PRODUCING THE LARGEST |
| EFFECTS. INCREAS IN ALLOWABLE STRESS SPE |
| CIFIED IN THE MATERIALS SECTIONS OF THIS |
| CODE OR A REFRENCED STANDARD SHALL NOT |
| BE USED WITH THESE LOAD COMBINATIONS |
| EXCEPT THAT A DURATION OF LOAD INCREASE |
| SHALL BE PERMITTED IN ACCORDANCE WITH |
| CHAPTER 23. |
| |
| RE-EVALUATE TRUSS ANCHOR SCHEDULE!!! |
| |
| 3) SHEET A-5 DETAIL 15 THE WRONG APPLICA |
| TION FOR A MSH 218 (STRAP HANGER) NOT |
| A HOLD DOWN DEVICE!!!!! |
| |
| 4) SHEET A-5 DETAIL 8 MSTA 18 STRAP, |
| RE-EVALUATE USING 2003 CATALOG. |
| |
| 5) SHEET 5 DETAIL 6 IS THIS CORRECT |
| USING THROUGH BOLTS? |
| |
| BEFORE A PERMIT TO CONSTRUCT, MAY |
| BE ISSUED, IMPACT FEES MUST BE PAID TO |
| PALM BEACH COUNTY. THE ACTUAL PERMIT |
| SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT |
| ATTACHED TO THE PERMIT APPLICATION. |
| PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| LOOK FOR COMMENTS BY THE OTHER PLAN |
| REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| ON THE APPLICATION, PLANS, OR ATTACHED |
| SEPARATELY. WHEN RESUBMITTING PLANS |
| PLEASE CLEARLY INDICATE THE REVISION AND |
| REMOVE AND REPLACE ANY PAGES AS NECESS- |
| ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| THE PLANS WHEN RESUBMITTING PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN |
| BE FOUND, WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| JIM WITMER |
| BUILDING PLAN REVIEW |
| TEL: (561)659-8096 X 8412 |
| FAX: (561)659-8026 |