Plan Review Notes For Permit 03041736 |
Permit Number |
03041736 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-05-27 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | 1-PROVIDE UPDATED SBCCI REPORT FOR STORM | | SHUTTERS. | | 2-REVISE DETAIL S21 FOR COLUMN BETWEEN | | GARAGE AND STAIRWAY TO MATCH THOSE | | CONDITIONS SHOWN ON THE 2ND FLOOR | | FRAMING PLAN. SEC. 104.2.1.2 CITY | | AMENDMENTS TO FBC 2001. | | 3-WINDOW 34 SH DOESN'T PROVIDE THE 24" | | CLEAR HEIGHT REQUIRED BY SEC. 1005.4 | | FBC 2001. REVISE AS REQUIRED. | | 4-REVISE TRUSS ANCHOR SCHEDULE TO COMPLY | | WITH SEC. 1609.4.3 FBC 2001, WHICH | | DOESN'T ALLOW THE 33% ALLOWABLE STRESS | | INCREASE TO BE USED. SEE USP 2003 | | CATALOGUE FOR REVISED VALUES. |
|