Plan Review Notes For Permit 03041736
Permit Number 03041736
Review Stop B
Sequence Number 1
Notes
Date Text
2003-05-27 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE UPDATED SBCCI REPORT FOR STORM
 SHUTTERS.
 2-REVISE DETAIL S21 FOR COLUMN BETWEEN
 GARAGE AND STAIRWAY TO MATCH THOSE
 CONDITIONS SHOWN ON THE 2ND FLOOR
 FRAMING PLAN. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 3-WINDOW 34 SH DOESN'T PROVIDE THE 24"
 CLEAR HEIGHT REQUIRED BY SEC. 1005.4
 FBC 2001. REVISE AS REQUIRED.
 4-REVISE TRUSS ANCHOR SCHEDULE TO COMPLY
 WITH SEC. 1609.4.3 FBC 2001, WHICH
 DOESN'T ALLOW THE 33% ALLOWABLE STRESS
 INCREASE TO BE USED. SEE USP 2003
 CATALOGUE FOR REVISED VALUES.