Plan Review Notes
Plan Review Notes For Permit 03041692
Permit Number 03041692
Review Stop B
Sequence Number 1
Notes
Date Text
2003-05-19 00:00:00BUILDING DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SUBMIT THE PAID RECEIPT FOR THE
 COUNTY IMPACT FEES.
  
 3) THE OWNER AND BUILDER LISTED ON THE
 ENERGY CALCULATIONS DO NOT MATCH THE
 INFORMATION ON THE APPLICATION.
  
 4) PROVIDE A SOIL BORING TEST REPORT AS
 REQUIRED BY CITY AMEND. TO FBC 1804.2.2.
  
 5) SPECIFY THE LENGTH/EMBEDMENT DEPTH OF
 THE 1/2" DIAMETER ANCHORS AT THE WOOD
 FRAME TO CONCRETE WALL CONNECTION DETAIL
 ON A5. SEMCO WAS PURCHASED BY USP LAST
 YEAR. UPDATE THE SEMCO CONNECTOR THAT IS
 SPECIFIED FOR THE STUD TO PLATE
 CONNECTION.
  
 6) CLARIFY NOTE 1 UNDER STAIRS ON A4.
 HANDRAILS ARE REQUIRED TO BE NOT LESS
 THAN 34" OR MORE THAN 38" ABOVE THE
 LEADING EDGE OF TREADS PER 1007.5.1.
 GUARDRAILS FOR DWELLINGS CAN BE A
 MINIMUM OF 36" HIGH PER FBC 1026.5.1.
  
 7) REVISE THE STUCCO SOFFIT SPECS. ON
 A4. INDICATE THE FASTENER SIZE IN NOTE 3
 NOTES 4 AND 5 ARE THE SAME. INDICATE IN
 NOTE 7 THAT 3/8" HIGH RIB METAL LATH IS
 REQUIRED TO BE FASTENED AT EVERY RIB
 (4"O.C.) PER ASTM C 1063.
  
 8) CLARIFY THE CONNECTION AT STEEL
 COLUMN DETAIL 4 ON S2. THE PLAN APPEARS
 TO INDICATE THAT TWO GIRDERS ARE CARRIED
 BY THIS COLUMN. HOWEVER, THE DETAIL ONLY
 SHOWS ONE.
  
 9) THE BUCKET IN DETAIL C ON S2 IS SHOWN
 ON AN ANGLE ON THE ROOF PLAN. THIS IS
 NOT INDICATED ON THE DETAIL.
  
 10) DETAIL E ON S3 WHICH IS A TRUSS TO
 WOOD CONNECTOR IS INCORRECTLY INDICATED
 AT THE MASONRY WALL AT THE MASTER
 BEDROOM.
  
 11) REVISE THE CONNECTOR VALUES TO
 REFLECT VALUES THAT DO NOT INCLUDE A
 STRESS INCREASE ON THE STEEL CALCS.
 SEE FBC 1609.4.3.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202