Plan Review Notes
Plan Review Notes For Permit 03041636
Permit Number 03041636
Review Stop B
Sequence Number 2
Notes
Date Text
2003-07-01 00:00:00BUILDING REVIEW PROCESS.
 1-PROVIDE PRODUCT APPROVAL FOR ENTRY
 DOOR WITH SIDELITE SINGLE ASSEMBLY AS
 SHOWN ON PLANS.
 2-UPDATE TRUSS ANCHOR SCHEDULE AND ALL
 DETAILS THAT ARE AFFECTED BY SECTION
 1609.4.3 FBC 2001, WHICH DOES NOT
 ALLOW STEEL STRESS TO BE INCREASED.
 3-GLASS BLOCK AT BATH TUB TO BE SAFETY
 GLASS IF FACE THICKNESS IS LESS THAN
 0.25". SEC. 2405.2 FBC 2001.