Plan Review Notes For Permit 03041636 |
Permit Number |
03041636 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-05-22 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | 1-GLASS BLOCK TO BE SAFETY GLASS IF FACE | | THICKNESS IS LESS THAN 0.25". SECTION | | 2405.2.2 FBC 2001. | | 2-PROVIDE INFORMATION FOR STORM SHUTTERS | | UPDATED SBCCI REPORT. | | 3-REVISE FASTENER SPECIFICATIONS ON | | DETAIL 3 ON S-2 TO MATCH THE DIAPHRAGM | | SCHEDULE. | | 4-PROVIDE GENERAL SPECIFICATIONS FOR | | FIREBLOCKING AT ALL CONCEALED SPACES | | AS REQUIRED BY SEC. 2305 FBC 2001. | | 5-ENTRY SECTION ON SHEET A-3: REVISE | | RECESS HEIGHT TO ALLOW FOOTING TO BE | | 12" BELOW GRADE. SEE COMMENTS ON SHEET | | A-3. SEC. 1804.1.3 FBC 2001. | | 6-PROVIDE PRODUCT APPROVAL FOR ENTRY | | DOOR WITH SIDELITE SINGLE ASSEMBLY AS | | SHOWN ON PLANS. |
|