Plan Review Notes For Permit 03041551 |
Permit Number |
03041551 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-05-21 00:00:00 | ******CORRECTIONS******* | | | | SAMANTHA THYNG, BUILDING PLANS EXAMINER | | [email protected] | | | | 1.)SEPARATE PERMIT REQUIRED; ROOF. | | | | 2.)UPLIFT VALUES ARE INCORRECT FOR | | THE USP CONNECTORS (A-5.1).REFER TO | | THE USP 2003 CATALOG. | | | | 3.)HUGHES STRAPS ARE NO LONGER MADE; | | SPECIFY ANOTHER ATTACHMENT (AS1, GABLE | | END DETAIL). | | | | 4.)THE WINDOW & SGD JAMB DETAIL MUST | | COMPLY WITH FBC 1707.4.4.2. | | | | 5.)THE DESIGN PRESSURES FOR THE 9'6" | | FIXED GLASS WINDOW EXCEEDS THE PRESSURE | | ALLOWED ON THE MULLION PRODUCT APPROVAL. | | | | 6.)EVERY EXTERIOR DOOR IS GLAZED. ONE | | DOOR MUST EITHER BE IMPACT, OR HAVE | | HURRICANE SHUTTERS WHICH CAN BE | | INSTALLED AND REMOVED FROM THE INSIDE. | | | | 7.)ADDITIONAL FEES DUE. |
|