Plan Review Notes
Plan Review Notes For Permit 03041481
Permit Number 03041481
Review Stop B
Sequence Number 5
Notes
Date Text
2004-01-10 00:00:00****CORRECTIONS*****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE DESIGN PRESSURE FOR THE DOORS
 (WW, SHEET A1) IS +51.7/-56.5.THE
 PRODUCT APPROVALS SUBMITTED HAVE A MAX
 PRESSURE OF +48/-51 FOR DOUBLE DOORS
 WITH SIDELITES.