Plan Review Notes
Plan Review Notes For Permit 03041481
Permit Number 03041481
Review Stop B
Sequence Number 1
Notes
Date Text
2003-05-16 00:00:00********CORRECTIONS**********
  
 1.)A NOTICE OF COMMENCEMENT IS
 REQUIRED TO BE FILED WITH THE CLERK OF
 COURTS BEFORE A PERMIT CAN BE ISSUED.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.CALL 233-5025 FOR MORE
 INFORMATION.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.
  
 3.)WINDOW V REQUIRES SAFETY GLASS.
 REVISE BOTH THE FLOOR PLAN AND THE
 WINDOW SCHEDULE.
  
 4.)THE WINDOW/SGD AND 'REPAIR
 MASONRY GAPS' DETAILS (A12) MUST COMPLY
 WITH FBC 1707.4.4.2.
  
 5.)THE GARAGE DOOR ATTACHMENT DETAIL
 (A12) CONFLICTS WITH THE PRODUCT
 APPROVAL.
  
 6.)THE ROOF SPECS AND SINGLE HUNG
 WINDOW PRODUCT APPROVALS ARE ILLEGIBLE.
 PROVIDE LEGIBLE COPIES.
  
 7.)THE UPLIFT VALUES FOR SOME OF THE
 CONNECTORS ARE INCORRECT.REFER TO
 USP 2003 CATALOG.
  
 8.)SPECIFY CEILING FINISH AT THE
 ENTRY, WITH ATTACHMENTS.
  
 9.)PROVIDE A STAIR SECTION WITH
 FIREBLOCKING, FBC 2305.1.4.
  
 10.) PROVIDE A STRUCTURAL PLAN FOR THE
 STAIRS INDICATING HOW STAIRS AND
 LANDING WILL BE SUPPORTED.
  
 11.)PROVIDE A SOILS INVESTIGATION
 REPORT.
  
 12.)WOOD BALCONY RAILING DETAIL (A12)
 TO COMPLY WITH FBC 1015.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]