2003-05-16 00:00:00 | ********CORRECTIONS********** |
| |
| 1.)A NOTICE OF COMMENCEMENT IS |
| REQUIRED TO BE FILED WITH THE CLERK OF |
| COURTS BEFORE A PERMIT CAN BE ISSUED. |
| |
| 2.)IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY.CALL 233-5025 FOR MORE |
| INFORMATION.THE PLANS MUST BE STAMPED |
| AND THE RECEIPT ATTACHED TO THE |
| APPLICATION. |
| |
| 3.)WINDOW V REQUIRES SAFETY GLASS. |
| REVISE BOTH THE FLOOR PLAN AND THE |
| WINDOW SCHEDULE. |
| |
| 4.)THE WINDOW/SGD AND 'REPAIR |
| MASONRY GAPS' DETAILS (A12) MUST COMPLY |
| WITH FBC 1707.4.4.2. |
| |
| 5.)THE GARAGE DOOR ATTACHMENT DETAIL |
| (A12) CONFLICTS WITH THE PRODUCT |
| APPROVAL. |
| |
| 6.)THE ROOF SPECS AND SINGLE HUNG |
| WINDOW PRODUCT APPROVALS ARE ILLEGIBLE. |
| PROVIDE LEGIBLE COPIES. |
| |
| 7.)THE UPLIFT VALUES FOR SOME OF THE |
| CONNECTORS ARE INCORRECT.REFER TO |
| USP 2003 CATALOG. |
| |
| 8.)SPECIFY CEILING FINISH AT THE |
| ENTRY, WITH ATTACHMENTS. |
| |
| 9.)PROVIDE A STAIR SECTION WITH |
| FIREBLOCKING, FBC 2305.1.4. |
| |
| 10.) PROVIDE A STRUCTURAL PLAN FOR THE |
| STAIRS INDICATING HOW STAIRS AND |
| LANDING WILL BE SUPPORTED. |
| |
| 11.)PROVIDE A SOILS INVESTIGATION |
| REPORT. |
| |
| 12.)WOOD BALCONY RAILING DETAIL (A12) |
| TO COMPLY WITH FBC 1015.3. |
| |