Plan Review Notes
Plan Review Notes For Permit 03041476
Permit Number 03041476
Review Stop B
Sequence Number 1
Notes
Date Text
2003-05-15 00:00:00**********CORRECTIONS***********
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY; CALL 233-5025 FOR MORE
 INFORMATION.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.
  
 3.)THE COLUMN LEGEND ON SHEET A3 IS
 PARTIALLY ILLEGIBLE.
  
 4.)SHOW WINDOWS BB AND U AS TEMPERED
 ON THE FLOOR PLAN, SHEET A6.
  
 5.)SHOW WINDOWS Q AND R AS TEMPERED
 ON THE WINDOW SCHEDULE, A1.
  
 6.)THE WINDOW AND SGD JAMB DETAIL,
 AND THE 'REPAIR MASONRY GAPS' DETAIL,
 SHEET A12, MUST COMPLY WITH FBC
 1707.4.4.2.
  
 7.)SOME VALUES FOR THE USP CONNECTORS
 ARE INCORRECT (SHEET A8).REFER TO
 THE 2003 CATALOG.
  
 8.)PROVIDE LEGIBLE PRODUCT APPROVALS
 (SINGLE HUNG WINDOW, TILE SPECS).
  
 9.)SOME PANEL LENGTHS ON THE
 HURRICANE SHUTTER INSTALLATION SCHEDULE
 EXCEED THE MAX LENGTH FOR THE DESIGN
 PRESSURE INDICATED.REVISE.
  
 10.)SHEET A5, BEARING WALL NOTE IS
 ILLEGIBLE.
  
 11.)PROVIDE A SOILS INVESTIGATION
 REPORT.
  