Plan Review Notes
Plan Review Notes For Permit 03041303
Permit Number 03041303
Review Stop P
Sequence Number 1
Notes
Date Text
2003-05-10 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 1) PIPING SCHEMATIC AND POOL LAYOUT DO
 NOT MATCH. NO VACUUM LINE SHOWN ON PIP-
 ING SCHEMATIC.
 2) 61G15-23.002 A PROFESSIONAL ENGINEER
 SHALL SIGN HIS NAME ON THE SEAL. ALSO
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED SHALL BE ENTERED ON THE PLANS.
 THE SIGNATURE ON THE ADDITIONAL PAGE IS
 A COPY AND NO DATE ON SIGNATURE OF PLANS
 3) FBC-2001 424.2.14.4 CONNECTIONS, ALL
 WATER HEATING EQUIPMENT SHALL BE INSTAL-
 LED WITH FLANGES OR UNION CONNECTIONS
 ADJACENT TO THE HEATER. (ADD TO NOTES)
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692